Fire water tank capacity calculator: the underground and terrace tank your building needs

Updated By Flamekite Editorial DeskFacts checked against official sources on

Fire tank capacity calculation for your building: the underground and terrace tank in litres and the fire pump set, from the NBC 2016 Table 7 row. Free.

Five-star hotel, underground
2,50,000 litres
With 20,000 litres on the terrace
Tank table 
Smallest terrace tank
5,000 litres
Flats, small hotels and small shops below 15 m
Tank table 
Basement over 200 m²
+5,000 litres
On the terrace, in rows below 15 m (Note 6)
Method 

National model · NBC 2016 Table 7

1,00,000 litres underground and 10,000 litres on the terrace

Underground tank
1,00,000 L
Terrace tank
10,000 L
Fire water in all
1,10,000 L
110 kL
Pump set
A 2,280 litre a minute pump set (Note 10)

Same row also asks: Wet riser and yard hydrant; sprinklers in the whole building; manual alarm and automatic detection.

See the full table this row comes from

A state applies Table 7 only as its own rules adopt it; NBC 2016 was withdrawn on 30 April 2026 and some states still apply it by order. The fire service decides.

Minimums from the published table, not a design. A fire engineer sizes the system; the fire service approves it.

Quick answer

A building's fire water tank comes from one row of NBC 2016 Part 4 Table 7, picked by its use, height and floor area. Many buildings below 15 m need only a terrace tank of 5,000 to 25,000 litres. Offices, shops, hotels, hospitals and halls between 15 m and 24 m add an underground tank of 1,00,000 to 1,50,000 litres, while flats and schools of that height still need only a 25,000 litre terrace tank.

The largest rows are a five-star hotel (2,50,000 litres underground) and a mall with a cinema or food court (2,00,000 litres) at any height. Enter your building below for its row, the pump set and the source. Maharashtra is read from its own Schedule-I of 2023.

Fire tank capacity in litres by building: NBC 2016 Table 7

Every NBC 2016 Table 7 row the calculator uses, with the underground tank, the terrace tank and the pump set. Each row links to the page where it is proof-read.
OptionUnderground tankTerrace tankPump setSource
A-3, A-4 below 15 mNone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceNBC 2016, Table 7
A-3, A-4 from 15 m to 35 mNone25,000 litresNot stated in the rows Flamekite has proof-readNBC 2016, Table 7
A-3, A-4 above 35 m to 45 m75,000 litres5,000 litresElectric and diesel pumps of 2,280 litres a minute and a 180 litre a minute jockeyNBC 2016, Table 7
A-3, A-4 above 45 m to 60 m1,50,000 litres10,000 litres2 electric pumps, a diesel standby and 2 jockeysNBC 2016, Table 7
A-3, A-4 above 60 m2,00,000 litres10,000 litresPumps of 2,850 litres a minuteNBC 2016, Table 7
A-1 lodging below 15 m, up to 15 roomsNone5,000 litres, 5,000 more with a basement over 200 m²No pump for this rowRajasthan UDH
A-1 lodging below 15 m, 16 to 30 roomsNone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceRajasthan UDH
A-1 lodging below 15 m, over 30 roomsNone10,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceNBC 2016, Table 7
A-5 below 15 m, no floor over 300 m²None5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceBIS, NBC 2016 Part 4
A-5 below 15 m, a floor of 300 m² to 1,000 m²10,000 litres per 500 m² of floor area, at least 50,000 litres10,000 litresA 1,620 litre a minute set with the wet riser; 450 litres a minute at the terraceBIS, NBC 2016 Part 4
A-5 below 15 m, a floor over 1,000 m²1,00,000 litres10,000 litresA 1,620 litre a minute setBIS, NBC 2016 Part 4
A-5 from 15 m to 30 m1,50,000 litres20,000 litresTwo electric and one diesel at 2,280 litres a minuteBIS, NBC 2016 Part 4
A-5 above 30 m2,00,000 litres20,000 litresTwo electric and one diesel at 2,280 litres a minuteBIS, NBC 2016 Part 4
A-6 five-star, any height2,50,000 litres20,000 litresTwo electric and one diesel at 2,850 litres a minuteBIS, NBC 2016 Part 4
B below 15 mNone10,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace, 450 more with a basement over 200 m²BIS, NBC 2016 Part 4
B from 15 m to 24 mNone25,000 litres900 litres a minute at the terraceBIS, NBC 2016 Part 4
B above 24 m to 30 m50,000 litresNone; 5,000 litres with a basement over 200 m²Electric and diesel pumps of 1,620 litres a minute and a 180 litre a minute jockey (Note 14)BIS, NBC 2016 Part 4
C-1 below 15 m on a plot over 1,000 m²1,00,000 litres10,000 litresElectric and diesel pumps of 1,620 litres a minute and a 180 litre a minute jockeyNBC 2016, Part 4
C-1 up to ground plus 1, no bedsNoneNone; 5,000 litres with a basement over 200 m²450 litres a minute at the terrace, only with a basement over 200 m²NBC 2016, Part 4
C-1 up to ground plus 1, with bedsNone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace, plus 450 with a basement over 200 m²NBC 2016, Part 4
C-1 ground plus 2 or more, no bedsNone10,000 litres, 5,000 more with a basement over 200 m²900 litres a minute at the terrace, plus 450 with a basement over 200 m²NBC 2016, Part 4
C-1 ground plus 2 or more, with beds75,000 litres10,000 litresElectric and diesel pumps of 1,620 litres a minute and a 180 litre a minute jockeyNBC 2016, Part 4
C-1 from 15 m to 24 m1,50,000 litres20,000 litresElectric and diesel pumps of 2,280 litres a minute and a 180 litre a minute jockeyNBC 2016, Part 4
C-1 above 24 m to 45 m2,00,000 litres20,000 litresTwo electric and one diesel pump of 2,280 litres a minute, two 180 litre a minute jockeysNBC 2016, Part 4
D-1 to D-5 below 10 m, up to 300 personsNone20,000 litres450 litres a minute at the terraceNBC 2016, Part 4
D-1 to D-5 below 10 m, more than 300 personsNone25,000 litres900 litres a minute at the terraceNBC 2016, Part 4
D-1 to D-5 from 10 m to 15 m1,00,000 litres5,000 litresOne electric and one diesel set at 2,280 litres a minuteNBC 2016, Part 4
D-1 to D-5 above 15 m to 24 m1,50,000 litres10,000 litresOne electric and one diesel set at 2,280 litres a minuteNBC 2016, Part 4
D-1 to D-5 above 24 m to 30 m2,00,000 litres20,000 litresTwo electric and one diesel set at 2,280 litres a minuteNBC 2016, Part 4
D-6 mall with cinema or food court, any height2,00,000 litres20,000 litresTwo electric and one diesel at 2,850 litres a minuteBIS, NBC 2016 Part 4
E below 10 mNone10,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceNBC 2016, Table 7
E above 10 m to 15 m50,000 litres5,000 litresPumps of 1,620 litres a minute (Note 14)NBC 2016, Table 7
E above 15 m to 24 m1,00,000 litres10,000 litresA 2,280 litre a minute pump set (Note 10)NBC 2016, Table 7
E above 24 m to 30 m1,50,000 litres20,000 litres2,280 litre a minute pump sets (Note 11)NBC 2016, Table 7
E above 30 m2,00,000 litres20,000 litresPumps of 2,850 litres a minute (Note 12)NBC 2016, Table 7
F-1, F-2 below 15 m, ground plus 1, up to 500 m² in allNone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terraceNBC 2016, Table 7
F-1, F-2 below 15 m, ground plus 1 over 500 m²None20,000 litres, 5,000 more with a basement over 200 m²900 litres a minute at the terraceNBC 2016, Table 7
F-1, F-2 below 15 m, more than ground plus 1None25,000 litres, 5,000 more with a basement over 200 m²900 litres a minute at the terraceNBC 2016, Table 7
F-1, F-2 from 15 m to 24 m1,00,000 litres10,000 litresOne electric and one diesel at 2,280 litres a minuteNBC 2016, Table 7
F-1, F-2 above 24 m to 30 m2,00,000 litres20,000 litresTwo electric and one diesel at 2,280 litres a minuteNBC 2016, Table 7
H below 15 m, under 250 m²None25,000 litres900 litres a minute at the terraceNBC 2016, Part 4
H below 15 m, over 250 m², ground floor only50,000 litres10,000 litresElectric and diesel pumps of 1,620 litres a minute, a 180 litre a minute jockey, 450 litres a minute at the terraceNBC 2016, Part 4
H below 15 m, over 250 m², ground plus 175,000 litres10,000 litresElectric and diesel pumps of 2,280 litres a minute, a 180 litre a minute jockey, 450 litres a minute at the terraceNBC 2016, Part 4
H below 15 m, over 250 m², more than ground plus 11,00,000 litres10,000 litresElectric and diesel pumps of 2,280 litres a minute, a 180 litre a minute jockey, 450 litres a minute at the terraceNBC 2016, Part 4
G-1 up to 100 m²NoneNone; 5,000 litres with a basement over 200 m²450 litres a minute at the terrace, only with a basement over 200 m²BIS, NBC 2016 Part 4
G-1, 100 to 500 m²None20,000 litres450 litres a minute at the terraceBIS, NBC 2016 Part 4
G-1, over 500 m², up to 15 mNone20,000 litres450 litres a minute at the terraceBIS, NBC 2016 Part 4
G-1, over 500 m², above 15 m75,000 litres5,000 litresPumps of 1,620 litres a minute (Note 14)BIS, NBC 2016 Part 4
G-2 up to 100 m²None10,000 litres450 litres a minute at the terraceBIS, NBC 2016 Part 4
G-2, 100 to 500 m²None20,000 litres900 litres a minute at the terraceBIS, NBC 2016 Part 4
G-2, 500 to 1,000 m², up to 15 mNone50,000 litres900 litres a minute at the terraceBIS, NBC 2016 Part 4
G-2, over 1,000 m²1,50,000 litres20,000 litres2,280 litre a minute pump sets (Note 11)BIS, NBC 2016 Part 4
G-3 up to 50 m²None10,000 litres900 litres a minute at the terraceBIS, NBC 2016 Part 4
G-3, 50 to 150 m²None25,000 litres900 litres a minute at the terraceBIS, NBC 2016 Part 4
G-3, 150 to 300 m²50,000 litres10,000 litresPumps of 1,620 litres a minuteBIS, NBC 2016 Part 4
G-3, 300 to 500 m²1,00,000 litres20,000 litres2,280 litre a minute pump sets (Note 10)BIS, NBC 2016 Part 4
G-3, over 500 m²1,50,000 litres20,000 litres2,280 litre a minute pump setsBIS, NBC 2016 Part 4

How the fire tank capacity is worked out, in 6 steps

  1. Fix the occupancy group

    NBC 2016 Part 4 sorts buildings into groups: A-3 and A-4 for hostels and flats, A-5 hotels, B schools, C-1 hospitals, D assembly, E offices, F shops, G factories and H storage. Each group has its own rows.

  2. Measure height, floors and area

    Take the height from ground level to the top floor's roof, count the floors including the ground floor, and note the covered area of the largest floor. Hotels, shops, hospitals, storage and factories change rows by area as well as height.

  3. Find the row

    Read the row whose height band and area band hold your building. The row gives the underground static tank, the terrace tank and the risers, sprinklers and alarms that go with them.

  4. Add the basement top-up

    In the rows below 15 m, a basement over 200 m² adds 5,000 litres to the terrace tank and 450 litres a minute to the terrace pump (Table 7 Note 6).

  5. Read the pump set

    Rows with an underground tank name a pump set at that tank, from 1,620 to 2,850 litres a minute. Each set carries a 180 litre a minute jockey pump, and Note 22 asks one set per 100 hydrants, up to 2 sets.

  6. Check what your state applies

    NBC 2016 was withdrawn on 30 April 2026 and the 2026 standard is voluntary, so a state applies these rows only as its own rules adopt them. Maharashtra has its own Schedule-I, which the calculator reads instead.

Maharashtra Schedule-I fire tank rows

Maharashtra's 2023 Schedule-I copies most national rows but changes a few: a hotel of 500 m² to 1,000 m² a floor needs a 20,000 litre terrace tank and no underground tank, and a warehouse under 1,000 m² needs a 50,000 litre underground tank and no terrace tank.

Underground tankTerrace tankPump set
A-3, A-4 below 15 m MH Act 2023 Schedule-INone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace
A-3, A-4 from 15 m to 35 m MH Act 2023 Schedule-INone25,000 litres900 litres a minute at the terrace
A-1 lodging below 15 m MH Act 2023 Schedule-INone5,000 litresNo pump for this row
A-1 lodging from 15 m to 35 m MH Act 2023 Schedule-INone25,000 litres900 litres a minute at the terrace
A-1 lodging above 35 m to 45 m MH Act 2023 Schedule-I75,000 litres5,000 litresNote 10 set: one 2,280 litre a minute electric pump, one diesel standby and one 180 litre a minute jockey per 100 hydrants
A-5 below 15 m, no floor over 500 m² MH Act 2023 Schedule-INone5,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace
A-5 below 15 m, a floor of 500 m² to 1,000 m² MH Act 2023 Schedule-INone20,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace
A-5 below 15 m, a floor over 1,000 m² MH Act 2023 Schedule-I1,00,000 litres10,000 litresOne electric and one diesel at 2,280 litres a minute
A-5 from 15 m to 30 m MH Act 2023 Schedule-I1,50,000 litres20,000 litresOne electric and one diesel at 2,280 litres a minute
A-5 above 30 m MH Act 2023 Schedule-I2,00,000 litres20,000 litresTwo electric and one diesel at 2,280 litres a minute
A-6 five-star MH Act 2023 Schedule-I2,50,000 litres20,000 litresTwo electric and one diesel at 2,850 litres a minute
B below 15 m MH Act 2023 Schedule-INone10,000 litres, 5,000 more with a basement over 200 m²450 litres a minute at the terrace
B from 15 m to 24 m MH Act 2023 Schedule-INone25,000 litres900 litres a minute at the terrace
B above 24 m to 30 m MH Act 2023 Schedule-I50,000 litresNone; 5,000 litres with a basement over 200 m²Not stated in the rows Flamekite has proof-read
D-6 MH Act 2023 Schedule-I2,00,000 litres20,000 litresTwo electric and one diesel at 2,850 litres a minute
F-1, F-2 below 15 m, ground plus 1, up to 500 m² in all MH Schedule-I 2023None5,000 litres450 litres a minute at the terrace
F-1, F-2 below 15 m, ground plus 1 over 500 m² MH Schedule-I 2023None20,000 litres900 litres a minute at the terrace
F-1, F-2 below 15 m, more than ground plus 1 MH Schedule-I 2023None25,000 litres900 litres a minute at the terrace
F-1, F-2 from 15 m to 24 m MH Schedule-I 20231,00,000 litres10,000 litresOne electric and one diesel at 2,280 litres a minute
F-1, F-2 above 24 m to 30 m MH Schedule-I 20232,00,000 litres20,000 litresTwo electric and one diesel at 2,280 litres a minute
H below 15 m, under 1,000 m² MH Act 2023 Schedule-I50,000 litresNoneElectric and diesel pumps of 1,620 litres a minute and a 180 litre a minute jockey (Note 14)

Read off the page images of the 2023 gazette as reproduced in the Flamekite records for hotels, schools, malls, hostels, guest houses and warehouses. Rows for offices, factories, hospitals and halls were not proof-read, so the calculator says "ask us" for them in Maharashtra and shows the national row for comparison.

Fire tank capacity calculation: 7 worked buildings

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's arithmetic from the rows above, for buildings we describe. Each names the row it uses.

  1. Case 1

    A 20 m office block of 800 m² floors

    Business (E), 6 floors, national model.

    What applies The E row above 15 m to 24 m: 1,00,000 litres underground and 10,000 on the terrace, 1,10,000 litres in all, with a 2,280 litre a minute pump set, a wet riser, a yard hydrant and sprinklers. NBC 2016, Table 7

  2. Case 2

    A 14 m hotel in Pune with 800 m² floors

    Hotel (A-5), no basement, Maharashtra.

    What applies Schedule-I's 500 m² to 1,000 m² row: a 20,000 litre terrace tank and a 450 litre a minute terrace pump, no underground tank. Under NBC 2016 the same floors would need an underground tank of at least 50,000 litres. MH Act 2023 Schedule-I

  3. Case 3

    A 40 m apartment tower

    Flats (A-4), national model.

    What applies The row above 35 m to 45 m: 75,000 litres underground and 5,000 on the terrace, with electric and diesel pumps of 2,280 litres a minute and a jockey. NBC 2016, Table 7

  4. Case 4

    A 12 m nursing home with beds on 4 floors

    Hospital (C-1), ground plus 3, plot under 1,000 m².

    What applies The ground plus 2 or more, with beds row: 75,000 litres underground and 10,000 on the terrace, with 1,620 litre a minute electric and diesel pumps. NBC 2016, Part 4

  5. Case 5

    An 18 m school

    Educational (B), national model.

    What applies The 15 m to 24 m row asks no underground tank: a 25,000 litre terrace tank and a 900 litre a minute terrace pump, with a down-comer. BIS, NBC 2016 Part 4

  6. Case 6

    A 400 m² single-storey godown

    Storage (H), 7 m.

    What applies Over 250 m² on the ground floor only: 50,000 litres underground and 10,000 on the terrace. In Maharashtra the under 1,000 m² row asks the same 50,000 litres underground and no terrace tank. NBC 2016, Part 4

  7. Case 7

    A 600 m² workshop of moderate hazard

    Factory (G-2), one floor, 8 m.

    What applies The 500 m² to 1,000 m² row up to 15 m: a 50,000 litre terrace tank and a 900 litre a minute pump, with sprinklers and automatic detection. BIS, NBC 2016 Part 4

Where the table stops and what to do instead

The calculator gives a number only where a proof-read row holds the building. These are the cases where it does not, and the next step for each.

  • If The use is barred at that height

    Table 7 Note 16 bars schools, halls and shops above 30 m, Note 20 bars storage at 15 m and above, and Notes 18 and 19 bar factories above 15 or 18 m. A taller building in those uses needs a change of use or a special approval. NBC 2016, Table 7

  • If A Maharashtra warehouse over 1,000 m²

    Schedule-I sizes the water by design to IS 13039, IS 15105 and IS 15325 for the whole occupancy (Notes 18 and 21(a)), so there is no fixed figure to read. MH Act 2023 Schedule-I

  • If A building designed to NBCS 2026

    The 2026 standard grades buildings by protection level and sizes the tank and pumps by hydraulic calculation. It is voluntary until a state adopts it. BIS, SP 7:2026

  • If A row Flamekite has not proof-read

    The calculator says "ask us" instead of guessing. Send the building on the free fire NOC check and we read the row your state applies. NBC 2016, Part 4

  • If A height exactly on a band line

    At 15 m, 24 m or 30 m the record's wording decides which row applies; the calculator flags it, and the fire service makes the final reading.

Questions about fire water tank capacity

How is fire water tank capacity calculated?

It is read, not calculated: NBC 2016 Part 4 Table 7 gives each occupancy and height band a fixed underground and terrace tank. You find your building's row by use, height and floor area, then add 5,000 litres on the terrace for a basement over 200 m² in the rows below 15 m.

What is the minimum fire water tank capacity for a building?

The smallest terrace tank in Table 7 is 5,000 litres, for flats and small hotels below 15 m and for shops of up to 500 m² in all. A clinic of up to ground plus 1 without beds, or a small low-hazard unit, needs a tank only if it has a basement over 200 m².

What fire tank capacity does a building of 15 m to 24 m need?

Offices and shops need 1,00,000 litres underground and 10,000 on the terrace; hotels, hospitals and halls 1,50,000 underground with 10,000 to 20,000 on the terrace. Flats up to 35 m and schools up to 24 m need only a 25,000 litre terrace tank.

How is fire pump capacity worked out?

The same Table 7 row names it. Terrace pumps run at 450 or 900 litres a minute; pump sets at an underground tank run at 1,620, 2,280 or 2,850 litres a minute, each with a 180 litre a minute jockey pump. Note 22 asks one set per 100 hydrants, up to 2 sets.

Does every state use the same fire tank capacity?

No. Maharashtra's Schedule-I of 2023 changes some rows, NBC 2016 was withdrawn on 30 April 2026, and the voluntary NBCS 2026 sizes tanks by hydraulic calculation. A state applies a table only as its own rules adopt it, so confirm with your fire service.

How much fire water does a five-star hotel need?

2,50,000 litres underground and 20,000 litres on the terrace at any height, with two electric pumps and a diesel pump of 2,850 litres a minute, under both NBC 2016 and Maharashtra's Schedule-I.

Keep reading

Free tools for this

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)checked 25 October 2026
  2. Urban Development, Housing and Local Self Government Departments, Rajasthan: Joint order No. P.11(9)UDH/2020 Part, 14 September 2023, on the fire safety certificate and fire NOC (18-page Hindi scan) (opens in a new tab)checked 25 October 2026
  3. Bureau of Indian Standards (copy hosted by Puducherry Fire Service): National Building Code of India 2016, Volume 1, Part 4 Fire and Life Safety: Table 7, Minimum Requirements for Fire Fighting Installations, and its notes 6 to 24 (read from the page images) (opens in a new tab)checked 25 October 2026
  4. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: minimum fire fighting installations for apartment houses (A-4) by height, with Notes 1, 4, 6, 10, 11 and 15 (read off the page images, pp. 13 to 15 and 32 to 34) (opens in a new tab)checked 25 October 2026
  5. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: rows (a) lodging and rooming houses (A-1) and (c) hotels (A-5), with Notes 3(d), 4, 5 and 10 (read off the page images, pp. 13 to 16, 32 and 33) (opens in a new tab)checked 25 October 2026
  6. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: Table 7 rows (d) hotels (A-5) and (e) hotels (A-6) with Notes 1 to 15, clause 4.10.1 (Fire Officer for starred hotels) and clause 6.1.1.4 (Subdivision A-5), read off the page images (opens in a new tab)checked 25 October 2026
Show all 15 sourcesShow fewer
  1. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: rows (c) hotels (A-5) and (d) hotels (A-6), gazette pages 16 and 17 (read off the page images) (opens in a new tab)checked 25 October 2026
  2. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clause 3.1.3 (Group B, B-1 and B-2), Table 7 educational rows and Notes 4, 6, 14 and 16, clause 6.2 (educational buildings); Table 7 read off the page-43 image (opens in a new tab)checked 25 October 2026
  3. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: educational buildings (B) by height, with Notes 3(d), 3(f), 4, 6 and 7 (read off the page images, pp. 17 and 33) (opens in a new tab)checked 25 October 2026
  4. Bureau of Indian Standards (copy hosted by Puducherry Fire Service): National Building Code of India 2016, Volume 1, Part 4: Table 7 row (b) for assembly D-6 (malls with cinemas, multiplexes or food courts), with Note 12 (row read off the page image of printed page 45; the mercantile rows are com-nbc2016-table7-ef) (opens in a new tab)checked 25 October 2026
  5. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: assembly row (b) buildings D-6, gazette page 23 (read off the page image; the mercantile rows are com-mh-schedule-1-ef) (opens in a new tab)checked 25 October 2026
  6. Bureau of Indian Standards (copy hosted by Puducherry Fire Service): National Building Code of India 2016, Part 4, Table 7: business (E) and mercantile (F) rows and Notes 4, 6, 10 to 12, 14 and 16, printed pages 46, 47 and 51 (read off the page images) (opens in a new tab)checked 25 October 2026
  7. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: Table 7 industrial buildings (Group G) rows G-1 to G-3 and Notes 4 to 24, read off the page images, pp. 47 to 51 (opens in a new tab)checked 25 October 2026
  8. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, Schedule-I: business and mercantile rows (gazette pages 24 to 26) and Notes 3(b), 8 and 15(b) (pages 33 and 34), read off the page images (opens in a new tab)checked 25 October 2026
  9. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026