Glossary 20 min read

High-rise building: the height line in NBC 2016, NBCS 2026 and every state

Updated By Flamekite Editorial DeskFacts checked against official sources on

Quick answer

A high-rise building is one 24 m or above in height, whatever its use, under the National Building Construction Standards 2026 (SP 7:2026, Part F, clause 2.39). NBC 2016, withdrawn on 30 April 2026, used 15 m (Part 4, clause 2.38).

Neither number decides your fire NOC by itself. Your state's fire act, rules or bye-laws set the line, and on 24 October 2026 those lines ran from 14.5 m in West Bengal to more than 30 m in Madhya Pradesh. Most states still use 15 m; Andhra Pradesh and Tripura use 24 m, and Telangana uses 24 m for residential apartments only.

NBCS 2026 high-rise line
24 m
Clause 2.39, any occupancy
At a glance
NBC 2016 high-rise line
15 m
Clause 2.38, withdrawn 30 April 2026
Both codes compared
Lowest state line
14.5 m
West Bengal, section 2(ha)
36-state matrix
Highest state line
30 m
Madhya Pradesh: more than 30 m or 10 storeys
36-state matrix

High-rise building at a glance

The national definitions of a high-rise building and how they reach a building, with the source of each fact.
WhatThe ruleSource
Definition nowA building 24 m or above in height, irrespective of its occupancy (NBCS 2026, Part F, clause 2.39)BIS, SP 7:2026
Definition until 30 April 2026A building 15 m or above in height, irrespective of its occupancy (NBC 2016, Part 4, clause 2.38)BIS, NBC 2016 Part 4
How height is measuredTo the floor of the last occupiable floor, from the grade where the fire tender stands (NBCS 2026, clause 2.6)BIS, SP 7:2026
Legal forceNone by itself: Part F is guidance for state governments and local authorities, which may change its thresholdsBIS, SP 7:2026
Who sets the binding lineThe state: fire services are a state subject and a municipal function (Article 243W, Twelfth Schedule)Legislative Department, Ministry of Law and Justice
Model Fire Bill lineFire safety certificate for buildings above 15 m (Revised Model Bill 2019, section 24(3))DGFS, MHA
State lines foundFrom 14.5 m (West Bengal) to more than 30 m or 10 storeys (Madhya Pradesh); 2 of 36 states and UTs publish no line Flamekite could findIndian Kanoonnews report
States at 24 mAndhra Pradesh (stilt included), Tripura, Mizoram (signed, not yet gazetted) and Telangana for residential apartmentsDirectorate of Fire and Emergency Services, Tripura
Extra rules NBCS 2026 attachesAnnex D: firefighting shafts, refuge areas above 24 m, at least 2 staircases, construction-stage fire waterBIS, SP 7:2026
Last verified24 October 2026, against BIS texts and state acts, rules, bye-laws and circularsNot stated

High-rise building in NBC 2016 and NBCS 2026

What the national code said about a high-rise building before and after 30 April 2026, clause by clause.
OptionNBC 2016 (SP 7:2016), Part 4NBCS 2026 (SP 7:2026), Part FSource
Definition clause2.38: 15 m or above, irrespective of occupancy2.39: 24 m or above, irrespective of occupancyBIS, SP 7:2026
Status on 24 October 2026Withdrawn by BIS on 30 April 2026; still named in some state rulesCurrent, voluntary and non-bindingGazette of India
Where the fire chapter appliesClause 1.2: all high-rise buildings, plus special buildings such as schools and hospitals of 9 m, assembly buildings and floors over 500 m²Clause 1.2: a height or floor area per occupancy, from 9 m for schools to 24 m for homesBIS, NBC 2016 Part 4
Residential trigger15 m, as a high-rise24 m or 750 m²BIS, SP 7:2026
Hospitals and custodial buildings9 m and above, as special buildings15 m or 500 m²BIS, NBC 2016 Part 4
Height limits by construction typeHeights and areas limited by occupancy and construction type (the then Table 2)Height restrictions eliminatedBIS, SP 7:2026
Refuge areasIntroduced for apartment buildings of 60 m and aboveIn buildings over 24 m, at or just above 24 m and then about every 15 m, unless refuge spaces are plannedBIS, SP 7:2026
Wording"shall""should"The Times of Indianews report

How to find the high-rise building line that applies to you

  1. Measure the height the way your rules do

    Most rules measure to the last occupied floor, not the roof, and some count the stilt floor. Note both the height in metres and the number of floors above ground.

  2. Find your state in the matrix below

    Read whether the state's number is a definition of high-rise, a fire NOC trigger or a risk class. A building can be under the high-rise line and still need a NOC.

  3. Read the instrument's own words

    Open the act, rule or bye-law named in the matrix. Check whether it says "above", "or above" or "exceeding": a building of exactly 15 m or 18.3 m depends on it.

  4. Check your city's development rules

    Building bye-laws often carry their own definition, as in Kerala's rule 80, Tamil Nadu's rule 2(58) or Meghalaya's A2.30, and the plan sanction follows them.

  5. Confirm with the fire service in writing

    Where the act and the bye-laws give different lines, as in Karnataka, ask the fire officer which one your file will be judged against before you fix the drawings.

High-rise building height in every state and UT

Flamekite read the line in all 36 states and union territories. 13 define a high-rise building; most others set a fire NOC height instead. Two publish neither in a text Flamekite could find.

Height lineWhat the number isWhere it is written
Andhra Pradesh G.O.Ms.No.27324 m or more, stilt floor includedDefinitionAP Building Rules as amended by G.O.Ms.No.273 of 19 December 2025
Arunachal Pradesh Government of Arunachal PradeshNot foundNone foundFire and Emergency Services Act 2026 (Act 12 of 2026)
Assam Assam Act XIII of 202615 m until 14 August 2026; now left to the Government, with no notification foundDefinition, now delegated; Schedule I still treats 15 m and above as high riskAct LIII of 2025, section 2(oo), amended by Act XIII of 2026
Bihar Bihar Rules 202115 m and aboveFire NOC trigger for multi-storey buildingsFire Service Rules 2021, rule 15, clause (i)
Chhattisgarh Home Department, ChhattisgarhAbove 15 m, or ground plus 4 floorsFire NOC trigger for residential buildingsSection 14(1) notification of 29 November 2022, class 2
Goa DFES Goa charterMore than 15 mFire NOC trigger; 14.2 m survives only as a fee classSection 13 notification of 17 December 2014
Gujarat Gujarat Fire Safety Compliance Portal15 m and above for flats, hostels and dormitoriesFire safety certificate triggerRegulations 2023, Third Schedule, Table 1
Haryana Government of HaryanaNo height in the Act; homes up to 16.5 m are exceptedFire NOC trigger for all other high-risesAct 14 of 2022, section 18(2)(a)
Himachal Pradesh Department of Fire Services, Himachal PradeshAbove 15 mFire NOC trigger on building plansFire Fighting Services Act 1984, section 15-A
Jharkhand Indian Kanoonnews report16.40 m; 15 m for fire regulationDefinition of multi-storey or high-rise buildingBuilding Bye-laws 2016, clause 2.94
Karnataka Government of Karnataka21 m or above, any occupancyDefinition in the Act; Seva Sindhu lists above 15 mFire Force Act, section 13(3), 2023 amendment
Kerala KMBR 201916 m or more, or more than 4 floors above basementsDefinitionKerala Municipality Building Rules 2019, rule 80
Madhya Pradesh MP Town PlanningMore than 30 m or more than 10 storeysDefinition; fire drawings already due above 12.5 mBhumi Vikas Rules 2012, rules 2(38) and 87(2)
Maharashtra MCGM BRC 69No statewide definition read; Mumbai splits at 32 mFee class; residential above 70 m is a section 45 high-risk buildingMCGM BRC 69 of 2026-27; Amendment Act 2023
Manipur Manipur UBBL 2024Over 15 m, or 17.5 m with stiltsDefinition in the bye-laws; the 2026 Act covers homes over 15 m or ground plus 4Unified Building Bye-Laws 2024, bye-laws 6(2)(a) and 51
Meghalaya Bye-Laws 2021Exceeding 15 m, any occupancyDefinitionBuilding Bye-Laws 2021, A2.30
Mizoram Mizoram Home Dept24 m and above; 15 m in the 2019 ruleDefinition in a rule signed 20 August 2026, in force once gazettedNotification B-20011/2/2026-HM(F&ES)
Nagaland Directorate of Fire and Emergency Services, NagalandAbove 15 mFire NOC trigger for multi-storey buildingsFire and Emergency Services Act (Act 5 of 2023)
Odisha Odisha Rules 201915 m and above for residential buildingsFire NOC classFire Prevention and Fire Safety Rules, rule 9(1), 2019 amendment
Punjab Punjab GazetteNo height definition found; up to 17.5 m with stilt parking counts as low-riseRelief line for independent floorsFire and Emergency Service Act 2024, section 24(2)
Rajasthan Rajasthan UDHAbove 15 m, every useMulti-storey and high-risk classModel Building Regulations 2025, regulation 14.5
Sikkim Government of SikkimAbove 15 m from plinthFire certificate trigger; commencement not foundFire and Emergency Services Act 2023
Tamil Nadu TNCDBR 2019Exceeding 18.30 mDefinition; the Director clears these as Multi Storied BuildingsCombined Development and Building Rules 2019, rule 2(58)
Telangana TGFD circular 345524 m and above for residential apartments, from 7 October 2026 (18 m before); more than 15 m for commercial buildingsProvisional fire NOC triggerCircular Rc.No.3455/MSB/2026
Tripura Directorate of Fire and Emergency Services, Tripura24 m or more, any occupancyDefinitionFire Safety Rules 2026, rule 2(49)
Uttar Pradesh UP Act 16 of 2022More than 15 mFire safety certificate trigger for multi-storied buildingsAct 16 of 2022, section 26(3)(i)
Uttarakhand Uttarakhand Gazette 202212 m and above for homes (15 m before 2022)Fire NOC triggerAct No. 06 of 2022, section 15(4)
West Bengal Indian Kanoonnews report14.5 m or moreDefinition; every high-rise is a high-risk buildingFire Services Act 1950, section 2(ha)
Andaman and Nicobar Islands Gazette of India Extraordinary, Part II Section 1, No. 19, 25 May 2026Above 15 mFire certificate trigger; commencement not foundRegulation 5 of 2026
Chandigarh Gazette of IndiaHigh-rises except homes up to 16.5 m; height alone is not a limiting factorFire certificate triggerHaryana Act as extended by S.O. 2264(E) of 6 May 2026
Dadra and Nagar Haveli and Daman and Diu Gazette of India ExtraordinaryAbove 15 mFire certificate triggerRegulation 6 of 2026, section 29(2), in force 7 July 2026
Delhi DFSOver 15 m or 5 storeys for homes; over 12 m for hotelsFire NOC trigger; stilt and mezzanine floors count as storeysFire Service Rules 2010, Rule 27, as amended in 2025
Jammu and Kashmir J&K GazetteHigher than 15 m, or above 17.5 m with stilts; tall above 50 mDefinitionUnified Building Bye-Laws 2021, chapter 9
Ladakh Gazette notification S.O. 140Up to 15 m and above 15 mRequirement tables split at this heightFire Prevention and Fire Safety Rules 2025, Schedule I
Lakshadweep Lakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026Not foundNone foundFire and Emergency Services Rules 2026
Puducherry Puducherry G.O. 61Above 17 m for apartmentsCategory A risk classG.O.Ms.No.61 of 10 September 2025

Definition = the instrument defines "high-rise building". Trigger = the height at which a fire NOC or certificate is needed. Class = a risk or fee band. A building below every line here can still need a NOC for its use or floor area: schools from 9 m in Delhi, Haryana and Bihar, for example.

What the NBCS 2026 definition of a high-rise building says

The definition is one line. What it does depends on whether your state adopts it.

Word for word

A building 24 m or above in height (irrespective of its occupancy).

National Building Construction Standards 2026 (SP 7:2026), Part F, clause 2.39 BIS, SP 7:2026

NBC 2016 used the same words with 15 m, in clause 2.38 of Part 4. Part F says it is only for guidance and referral for the state government or local authority, and a note to clause 1.2 lets them change its height and area thresholds. Only Assam had written NBCS 2026 into its fire law by 24 October 2026, and the same Assam amendment of 14 August 2026 removed the 15 m figure from its own definition and left the height to a Government notification.

How high-rise building height is measured, rule by rule

Two buildings of the same height can fall on different sides of the line, because the rules measure from different points and count different floors.

  • NBCS 2026, clause 2.6

    From the fire tender's grade to the last occupied floor

    Height runs from the ground where the fire tender stands to the floor level of the last occupiable floor; on a sloping site, from the lowest level a fire vehicle can reach. BIS, SP 7:2026

  • West Bengal, section 2(ha)

    From the street's centre line to the highest point

    The 14.5 m line is measured from the average level of the centre line of the abutting street. Indian Kanoonnews report

  • AP G.O.Ms.No.273

    The stilt floor is counted

    Since 19 December 2025 the 24 m line includes the stilt floor. G.O.Ms.No.273

  • J&K bye-laws, chapter 9

    Stilts add 2.5 m

    Higher than 15 m without stilts, or above 17.5 m with stilts kept for parking. J&K H&UDD

  • Punjab Act, section 24(2)

    Stilt parking keeps 17.5 m low-rise

    An independent floor up to 17.5 m with stilt parking gets low-rise fire norms; shops in the stilts end the relief. Punjab Gazette

  • Kerala KMBR, rule 80

    Floors count as well as metres

    16 m or more, or more than 4 floors excluding basements: a low-ceilinged 5-floor block is a high-rise. KMBR 2019

  • MP Bhumi Vikas, rule 2(38)

    Storeys or metres, whichever comes first

    More than 10 storeys or more than 30 m. MP Town Planning

  • Delhi Rule 27

    Stilt and mezzanine floors are storeys

    A stilt plus 4 floors is 5 storeys, which brings a home in even below 15 m. DFS

What NBCS 2026 asks of a high-rise building

Part F's Annex D and the clauses it points to add these duties once a building reaches 24 m. They apply where your state adopts NBCS 2026 or a contract names it.

  • At least 2 staircases for every high-rise and special building, with the required fire exit stairs recommended to be free of FAR (clause 4.4.2) BIS, SP 7:2026
  • One firefighting shaft for each residential tower and each educational block, and one per compartment in institutional, assembly, business and mercantile buildings; 2 shafts where a floor has 3 or more compartments (Annex D, D-2) BIS, SP 7:2026
  • Below 60 m, the firefighting shaft on an external wall, discharging straight outside; at 60 m and above it may sit in the core but must discharge through an exit passageway (clause 4.2.10) BIS, SP 7:2026
  • Refuge spaces in the firefighting shaft's lift lobby of at least 12 m², or 5% of the floor's occupants at 0.45 m² each, whichever is higher (D-4.2) BIS, SP 7:2026
  • Where refuge areas are used instead, one at or just above 24 m and then about every 15 m, sized for 2 floors' occupants at 0.3 m² each and at least 15 m², sprinklered and signed in letters of at least 75 mm (D-4.2) BIS, SP 7:2026
  • Above 60 m, stair pressurisation checked so a door opens with a force of not more than 133 N (D-2) BIS, SP 7:2026
  • During construction: a dry riser of at least 100 mm with outlets on finished floors, 2,000-litre water drums with 2 buckets on each floor and a tank of at least 20,000 litres (clause 3.5.3.2) BIS, SP 7:2026

One 20 m high-rise building tested in six cities

The same block of flats, 20 m to its last occupied floor, 6 floors and 2,400 m², is a high-rise in some states and not in others.

  1. Case 1

    Hyderabad

    A fresh Provisional NOC application filed after 7 October 2026.

    What applies Below Telangana's 24 m line for residential apartments, so no Provisional fire NOC is needed for this block; a commercial block of the same height would still need one above 15 m. TGFD circular 3455

  2. Case 2

    Bengaluru

    Plan sanction from the city corporation.

    What applies Below the 21 m high-rise line in section 13(3) of the Karnataka Fire Force Act, but Seva Sindhu lists eligibility from 15 m: ask KSFES in writing which line applies. Government of Karnataka

  3. Case 3

    Kolkata

    Inside the Kolkata Municipal Corporation area.

    What applies Above West Bengal's 14.5 m line, so a high-rise and a high-risk building; 2,400 m² is also over the 500 m² cap for self-certification, so it needs the recommendation and the certificate. WB notification 1930

  4. Case 4

    Chennai

    Planning permission from CMDA.

    What applies Over the 18.30 m line in TNCDBR rule 2(58), so a high-rise: the Director of Fire and Rescue Services issues the NOC. TNCDBR 2019

  5. Case 5

    Indore

    Building permission from the municipal corporation.

    What applies Not a high-rise until it passes 30 m or 10 storeys, but above 12.5 m it must submit fire drawings and fit the systems before occupancy. MP Town Planning

  6. Case 6

    Kochi

    Permit under the Kerala Municipality Building Rules.

    What applies A high-rise twice over: 16 m or more, and more than 4 floors. Over 15 m it also needs the fire NOC under rule 5(4). KMBR 2019

How state high-rise building lines were set, 2012 to 2025

Before NBCS 2026 most states copied 15 m from the code. These are the ones that wrote their own line, and when.

  1. 30 May 2012

    Madhya Pradesh's Bhumi Vikas Rules define a high-rise as more than 10 storeys or 30 m. MP Town Planning

  2. 17 December 2014

    Goa's section 13 notification lists high-rise buildings of more than 15 m. DFES Goa charter

  3. 2016

    NBC 2016 Part 4 defines a high-rise as 15 m or above, irrespective of occupancy (clause 2.38). BIS, NBC 2016 Part 4

  4. 4 February 2019

    Tamil Nadu's Combined Development and Building Rules set the line at exceeding 18.30 m. TNCDBR 2019

  5. 8 November 2019

    Kerala's Municipality Building Rules define a high-rise as 16 m or more, or more than 4 floors. KMBR 2019

  6. 25 March 2021

    Meghalaya's Building Bye-Laws define a high-rise as exceeding 15 m, any occupancy. Bye-Laws 2021

  7. 24 December 2021

    J&K's Unified Building Bye-Laws set 15 m, 17.5 m with stilts, and call buildings above 50 m tall. J&K Gazette

  8. 2023

    Karnataka's amendment adds section 13(3): a high-rise is 21 m or above, any occupancy. Government of Karnataka

  9. 19 December 2025

    Andhra Pradesh moves to 24 m, stilt floor included, by G.O.Ms.No.273. G.O.Ms.No.273

  10. 24 December 2025

    Assam's new fire Act defines a high-rise as 15 m or above in section 2(oo). Assam Act LIII of 2025

High-rise building line changes in 2026

From news reports, not yet an official source.

Four definitions moved toward 24 m in 2026 and one state handed the number to its Government. Flamekite rechecks state gazettes and fire service circulars and updates this list.

  • BIS replaces NBC 2016 with NBCS 2026 (SP 7:2026); the high-rise line in Part F becomes 24 m. Gazette of India

  • Tripura's Fire Safety Rules 2026 are gazetted with a 24 m high-rise definition in rule 2(49). Directorate of Fire and Emergency Services, Tripura

  • Assam's Jan Vishwas Act removes 15 m from section 2(oo); the height is now whatever the Government specifies. No notification had followed by 24 October 2026. Assam Act XIII of 2026

  • Mizoram signs amended rules naming high-rise buildings as 24 m and above; they start on publication in the Mizoram Gazette, a date Flamekite has not found. Mizoram Home Dept

  • Punjab's building rules amendment makes every staircase in a building above 21 m a fire-exit staircase. Indian Mastermindsnews report

  • Bihar uploads draft Building Bye-laws 2026 for objections; press reports say self-certified buildings up to 24 m would need no separate fire NOC. Not notified. GKTodaynews report

  • Telangana's 24 m line for residential apartments takes effect for fresh Provisional NOC applications; fire towers and fire command centres move to 24 m for all uses. TGFD circular 3455

High-rise building and the terms used next to it

Rules use several near-synonyms, and each one carries its own number.

Tall building
NBCS 2026 uses 60 m and above for tall buildings (clause 4.2.10); the J&K bye-laws use more than 50 m. BIS, SP 7:2026
Special building
In NBC 2016 Part 4, clause 1.2(b): non-high-rise buildings the fire chapter still covers, such as schools and hospitals of 9 m, every assembly building and any floor over 500 m². BIS, NBC 2016 Part 4
Multi-storey building
Uttar Pradesh's Act uses it for buildings more than 15 m; Jharkhand's bye-laws put it at 16.40 m, or 15 m for fire. UP Act 16 of 2022
Multi Storied Building (Tamil Nadu)
18.3 m and above on the single window portal: the Director of Fire and Rescue Services issues these NOCs, the District Officer the rest. TNSWP
High-risk building (West Bengal)
A high-rise of 14.5 m or more, or any occupancy the state notifies; notification 279 of 2003 lists 19. West Bengal Fire and Emergency Services
Section 45 building (Maharashtra)
The Act's high-risk class: above 30 m for listed uses and residential buildings above 70 m, with a licensed fire audit every 2 years. Amendment Act 2023
Firefighting shaft
An enclosed shaft of 120-minute fire resistance holding a staircase, a fire lift and its lobby (NBCS 2026, clause 2.24). BIS, SP 7:2026
Refuge area
A space for temporary use during escape, open to air on at least one side, required above 24 m in NBCS 2026 where refuge spaces are not planned. BIS, SP 7:2026

High-rise building lines across India, counted

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's count from the 36-row matrix above, on 24 October 2026.

Four myths about the high-rise building line

  • You may have read

    Since 2026 every building under 24 m is outside the high-rise rules.

    Myth

    What the sources say

    NBCS 2026 is voluntary. Most states still use 15 m in their own acts and bye-laws, and those decide the fire NOC. BIS, SP 7:2026

  • You may have read

    Below the high-rise line, no fire NOC is needed.

    Myth

    What the sources say

    Use and height bands below the high-rise line bring buildings in too: Delhi's Rule 27 covers schools, hospitals and shops over 9 m and hotels over 12 m. DFS

  • You may have read

    Telangana raised the high-rise line to 24 m for all buildings.

    Myth

    What the sources say

    Circular Rc.No.3455/MSB/2026 moves only residential apartments to 24 m; commercial buildings still need a NOC above 15 m. TGFD circular 3455

  • You may have read

    Assam no longer has a high-rise height.

    Myth

    What the sources say

    The definition now waits for a Government notification, but Schedule I of the 2025 Act still makes every building of 15 m or more high risk. Assam Act LIII of 2025

Where the high-rise building line catches owners out

These come from the wording of the rules, not from the number itself.

  • If A building of exactly 18.3 m in Tamil Nadu

    The single window says 18.3 m and above, TNCDBR says exceeding 18.30 m: confirm with TNFRS which officer clears it. TNCDBR 2019

  • If Reading Karnataka's 21 m as the whole story

    Seva Sindhu lists high-rise NOC eligibility from 15 m. Get the fire service's answer in writing before the plan goes in. Seva Sindhu

  • If Filling stilts with shops

    In Punjab and J&K the stilt relief holds only while the stilts stay parking; in Andhra Pradesh the stilt is counted anyway. Punjab Gazette

  • If Counting only metres in Kerala or Delhi

    Kerala counts more than 4 floors, and Delhi counts stilt and mezzanine floors as storeys. KMBR 2019

  • If Dropping the fire tower in a Telangana block below 24 m

    Since 7 October 2026 the fire tower and fire command centre start at 24 m, but every other measure in the approved plan still applies. TGFD circular 3455

What Flamekite could not confirm about high-rise building lines

These gaps are listed so you know where to ask, not filled with guesses.

Telangana's Fire Service Act, 1999 is reported to define a high-rise at 18 m, but the India Code copy refused our requests, so this page uses the department's own circular, which says 18 m and above applied before 7 October 2026.

Odisha's ODA (Planning and Building Standards) Rules, 2020, Gujarat's GDCR, Maharashtra's UDCPR, the Haryana Building Code, 2017 and Delhi's Unified Building Bye-Laws carry their own high-rise definitions, which Flamekite has not read; the matrix shows each state's fire law line instead.

Arunachal Pradesh's Act 12 of 2026 and Lakshadweep's 2026 Regulation and Rules were read for other provisions only. Whether they define a high-rise is not confirmed.

West Bengal's Fire Services (Amendment) Act, 2022 is reported to raise the line to 15.5 m for a named local area from a notified date. Its text was not available, so the matrix keeps 14.5 m statewide.

Questions about the high-rise building definition

What is the height of a high-rise building in India?

24 m or above under NBCS 2026, the national standard since 30 April 2026, and 15 m under the withdrawn NBC 2016. The line that binds you is your state's: 15 m in most states, 24 m in Andhra Pradesh and Tripura, 21 m in Karnataka, 18.3 m in Tamil Nadu.

What is the definition of a high-rise building as per NBC?

NBC 2016, Part 4, clause 2.38: a building 15 m or above in height, irrespective of its occupancy. Its replacement, NBCS 2026, Part F, clause 2.39, uses the same words with 24 m.

Is a 15 m building a high-rise?

Under NBC 2016 yes, because it says 15 m or above. Under rules that say above or exceeding 15 m, such as Himachal Pradesh's and Meghalaya's, a building of exactly 15 m is not, so read your state's wording.

Does the stilt floor count in building height?

It depends on the state. Andhra Pradesh counts it in its 24 m line; J&K and Punjab give stilt parking extra room up to 17.5 m; Delhi counts a stilt as a storey.

Is a multi-storey building the same as a high-rise building?

Often the same height, but not always. Jharkhand calls a building multi-storey at 16.40 m but uses 15 m for fire, and Uttar Pradesh's Act uses multi-storied for buildings over 15 m.

Does every high-rise building need a refuge area?

Under NBCS 2026, buildings over 24 m need refuge areas at about every 15 m unless refuge spaces are planned in the firefighting shaft lobbies, and high-rise flats with balconies are exempt. Your state's rules may say otherwise.

Which states use 24 m as the high-rise height?

Andhra Pradesh (stilt included) and Tripura define a high-rise at 24 m; Mizoram has signed the same line, in force once gazetted; Telangana uses 24 m for residential apartments only.

Keep reading

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  2. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016 (SP 7:2016), Part 4: Fire and Life Safety, clauses 1.2, 2.38 and 3.1 (opens in a new tab)checked 25 October 2026
  3. Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)checked 25 October 2026
  4. Legislative Department, Ministry of Law and Justice: The Constitution of India (Twelfth Schedule, item 7: Fire services; Article 243W) (opens in a new tab)checked 24 October 2026
  5. Directorate General Fire Services, Civil Defence and Home Guards (MHA): Revised Model Fire and Emergency Service Bill, 2019 (opens in a new tab)checked 26 October 2026
  6. Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)checked 25 October 2026
Show all 51 sourcesShow fewer
  1. Directorate of Fire and Emergency Services, Tripura: Tripura Fire Safety Rules, 2026 (Tripura Gazette, 2 June 2026) (opens in a new tab)checked 24 October 2026
  2. Government of Andhra Pradesh, MA&UD (M) Department, final notification (copy hosted by Simpliance): G.O.Ms.No.273, 19 December 2025: amendments to the AP Building Rules, 2017 (high-rise at 24 m; Fire NOC before 24 m) (opens in a new tab)checked 24 October 2026
  3. Government of Arunachal Pradesh (PRS copy of AP Gazette Extraordinary No. 128, 11 May 2026): Arunachal Pradesh Fire and Emergency Services Act, 2026 (Act 12 of 2026) (opens in a new tab)checked 24 October 2026
  4. Government of Bihar, Home Department notification (English copy hosted by Bihar Fire Service): Bihar Fire Service Rules, 2021: rules 14 to 27, 33, 34 and 38, Schedules C (fees), D (online NOC), E (pandals) and H (existing buildings) (opens in a new tab)checked 25 October 2026
  5. Home Department, Chhattisgarh (on the CG Fire NOC portal): Notification under section 14(1), 29 November 2022: buildings that need a fire NOC (opens in a new tab)checked 24 October 2026
  6. Directorate of Fire and Emergency Services, Goa: Citizen's Charter, December 2024: 17 fire stations, 3 zones, 1,106 posts, the section 13 notification 3/5/97-HD(G) Part/3934 of 17 December 2014 with Annexures I and II, the 2018 Annexure III on shacks and guest houses, and the 2009 fee rules (opens in a new tab)checked 25 October 2026
  7. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 25 October 2026
  8. Government of Haryana (PRS copy): Haryana Fire and Emergency Services Act, 2022 (Act 14 of 2022) (opens in a new tab)checked 25 October 2026
  9. Department of Fire Services, Himachal Pradesh: Acts and Rules: HP Fire Fighting Services Act, 1984 with the 2000 amendment (section 15-A) (opens in a new tab)checked 24 October 2026
  10. Government of Karnataka (PRS copy): Karnataka Fire Force (Amendment) Ordinance, 2023: section 13(3) high-rise NOC (opens in a new tab)checked 25 October 2026
  11. Local Self Government Department, Government of Kerala (Kerala Gazette copies): Kerala Municipality Building Rules, 2019 (G.O.(P) No.77/2019/LSGD, S.R.O. No.828/2019, 8 November 2019) with the Amendment Rules, 2020 (G.O.(P) No.57/2020/LSGD, S.R.O. No.639/2020): rule 5(4) items 12 and 13, rules 28, 29, 35, 80 and 81, Appendix L (opens in a new tab)checked 25 October 2026
  12. Directorate of Town and Country Planning, Madhya Pradesh: Madhya Pradesh Bhumi Vikas Rules, 2012, English text updated up to 6 March 2025: rules 2(38), 12(2), 26, 42 and 87 (fire audit amendment of 4 September 2020) (opens in a new tab)checked 25 October 2026
  13. Municipal Corporation of Greater Mumbai, Mumbai Fire Brigade: Revised schedule of fees for the year 2026-27, BRC No. 69 dated 30.03.2026 (rows 1 to 6 and 28 read off the page images) (opens in a new tab)checked 24 October 2026
  14. Manipur Gazette Extraordinary No. 253, 5 December 2024 (Town Planning Department copy): The Model Manipur Unified Building Bye-Laws, 2024, notification No. BBL-101/1/2024-MAHUD-MAHUD-Part(1) of 4 December 2024: bye-laws 6, 7, 8, 9, 51, 65 and 85 to 89 (opens in a new tab)checked 25 October 2026
  15. Gazette of Meghalaya No. 12, Part IIA, 25 March 2021 (copy hosted by the Urban Affairs Department): Meghalaya Building Bye-Laws, 2021 (No. UAU.73/2016/Pt/402 of 9 March 2021): A2.30 high-rise, A2.59 special buildings, A4.1.3, A10 occupancy and fire clearance, C11 (opens in a new tab)checked 25 October 2026
  16. Home Department, Government of Mizoram (copy on the Mizoram Fire and Emergency Services site): Notification No. B-20011/2/2026-HM(F&ES), 20 August 2026: Mizoram Fire and Emergency Services (Superintendence and Control of the Fire Force and Fire Safety and Prevention) (Amendment) Rules, 2026, substituting Rule 57 and inserting Rules 57(A) and 57(B) (opens in a new tab)checked 25 October 2026
  17. Directorate of Fire and Emergency Services, Nagaland: Nagaland Fire and Emergency Services Act (Act No. 5 of 2023), Nagaland Gazette, 31 August 2023 (opens in a new tab)checked 24 October 2026
  18. Home Department, Government of Odisha: Odisha Fire Prevention and Fire Safety (Amendment) Rules, 2019, notification No. 10573/H of 6 March 2019: rule 9(1) classes, rules 10, 13(3) and 22(5) (opens in a new tab)checked 24 October 2026
  19. Punjab Government Gazette (Extraordinary), copy hosted by PRS Legislative Research: Punjab Govt. Gazette (Extra), 26 November 2024: the Punjab Fire and Emergency Service Act, 2024 (Punjab Act No. 12 of 2024), Notification No. 12-Leg./2024 of 27 October 2024 (opens in a new tab)checked 25 October 2026
  20. Urban Development Department, Rajasthan: Model Rajasthan Building Regulations, 2025, order No. P-11(5)/UDH/Bhavan Viniyam-2025/2025 (listed 12 May 2025): Regs 2.36, 2.75, 2.77, 4.6.2, 5.4, 11.2, 14.5 and Schedules 2 and 3 (opens in a new tab)checked 25 October 2026
  21. Government of Sikkim (PRS copy of Gazette Extraordinary No. 226): Sikkim Fire and Emergency Services Act, 2023 (Act 4 of 2023) (opens in a new tab)checked 24 October 2026
  22. Chennai Metropolitan Development Authority (copy of Tamil Nadu Government Gazette Extraordinary No. 43): Tamil Nadu Combined Development and Building Rules, 2019 (G.O. Ms. No. 18, MAWS, 4 February 2019): rules 2(58), 7, 20, 39, 64 and Annexure IX (opens in a new tab)checked 25 October 2026
  23. Telangana Fire, Disaster Response, Emergency and Civil Defence Department: Circular Memorandum Rc.No.3455/MSB/2026, 26 September 2026: revised requirements for Fire NOCs in the context of G.O.Ms.No.95 (in force 7 October 2026) (opens in a new tab)checked 25 October 2026
  24. Uttar Pradesh Gazette Extraordinary, 13 December 2022 (copy hosted by PRS Legislative Research): Uttar Pradesh Fire and Emergency Services Act, 2022 (U.P. Act No. 16 of 2022), English translation: sections 1, 26 to 29, 33 to 39, 45, 48, 58 and 66 (opens in a new tab)checked 24 October 2026
  25. Government of Uttarakhand, Sarkari Gazette Extraordinary, 21 July 2022 (copy hosted by Uttarakhand Fire and Emergency Services): Uttarakhand Fire & Emergency Service, Fire Prevention and Fire Safety (Amendment) Act, 2022 (Uttarakhand Act No. 06 of 2022), assented 20 July 2022, notification 191/XXXVI(3)/2022/36(1)/2022: sections 15(4) and 18 at 12 m and 500 m2 (opens in a new tab)checked 24 October 2026
  26. Gazette of India Extraordinary, Part II Section 1, No. 19, 25 May 2026: Andaman and Nicobar Islands Fire and Emergency Service Regulation, 2026 (No. 5 of 2026) (opens in a new tab)checked 24 October 2026
  27. Gazette of India, Ministry of Home Affairs (copy hosted by TaxHeal): S.O. 2264(E) of 6 May 2026: the Haryana Fire and Emergency Services Act, 2022 extended to the Union territory of Chandigarh, with modifications (opens in a new tab)checked 25 October 2026
  28. Gazette of India Extraordinary (CG-DL-E-02062026-273069): Dadra and Nagar Haveli and Daman and Diu Fire and Emergency Service Regulation, 2026 (No. 6 of 2026) (opens in a new tab)checked 24 October 2026
  29. Delhi Fire Service (copy of Delhi Gazette Extraordinary, Part IV): Delhi Fire Service (Amendment) Rules, 2025, notification F.No. DFS/HQ/Misc/2025/01(E-259159)/237, gazetted 26 May 2026 (opens in a new tab)checked 25 October 2026
  30. Jammu and Kashmir Official Gazette (Extraordinary), copy hosted by the Housing and Urban Development Department: J&K Official Gazette, Vol. 134, No. 39-4, 24 December 2021: the Jammu and Kashmir Unified Building Bye-Laws, 2021 (opens in a new tab)checked 24 October 2026
  31. Gazette notification S.O. 140 (copy hosted by Simpliance): Ladakh Fire Prevention and Fire Safety Rules, 2025 (S.O. 140, 28 November 2025) (opens in a new tab)checked 24 October 2026
  32. Lakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026: Lakshadweep Fire and Emergency Services Rules, 2026 (Rule 12: 5-year fire safety certificate) (opens in a new tab)checked 24 October 2026
  33. Government of Puducherry, Home Department (copy hosted by the Fire Service Department): G.O.Ms.No.61, 10 September 2025: Fire Safety Audit and Issue of NOC, Third Party Fire Safety Audit, Categories A, B and C, renewal, temporary licences, and Annexures I to V on licensed agencies and the Category C protocol (opens in a new tab)checked 25 October 2026
  34. Housing and Urban Development Department, J&K (copy hosted by NITI for States): Jammu and Kashmir Unified Building Byelaws 2021 (February 2021): use classes, high-rise and tall buildings, fire access and Fire Consultant on Record (opens in a new tab)checked 25 October 2026
  35. Department of Fire and Emergency Services, Government of West Bengal: Notification 1930/FES/O/MISC-08/2023, 1 March 2024: 12 occupancies moved to yearly self-certification (with forwarding letter 1961 of 5 March 2024) (opens in a new tab)checked 25 October 2026
  36. Assam Gazette Extraordinary No. 811, 24 December 2025 (PRS copy of the gazette): The Assam Fire and Emergency Services Act, 2025 (Assam Act No. LIII of 2025), notification No. LGL.52/2025/3: sections 1 to 67 and Schedule I (opens in a new tab)checked 25 October 2026
  37. Guidance Tamil Nadu, Tamil Nadu Single Window Portal: No Objection Certificate for Multi Storied Buildings (18.3 m and above) from TNFRS: procedure, documents, timelines and fees (opens in a new tab)checked 24 October 2026
  38. West Bengal Fire and Emergency Services: FAQ: fire safety certificate, 14.5 m line, compounding under section 38B (opens in a new tab)checked 24 October 2026
  39. Government of Maharashtra (copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023 (Mah. Act No. XXIV of 2023), first published 11 May 2023 (opens in a new tab)checked 25 October 2026
  40. Seva Sindhu, Government of Karnataka: Application for No Objection Certificate (High rise Building) - Fire & Emergency: documents, fee under G.O. of 13-09-2019, 60 working days (opens in a new tab)checked 24 October 2026
  41. Indian Kanoon (legal database copy of the 1996 text): West Bengal Fire Services Act, 1950: sections 2(ha), 2(hb), 11C to 11K and 38B (copy predates the 2018 and 2022 amendments) (opens in a new tab)News report · checked 24 October 2026
  42. Indian Kanoon (legal database copy; gazette not read): Section 2 in Jharkhand Building Byelaws 2016: definitions, 2.94 multi-storey building (opens in a new tab)News report · checked 24 October 2026
  43. Indian Masterminds: Punjab Building Rules 2026: Second Amendment notified 7 September 2026, fire-exit staircases above 21 m (10 September 2026) (opens in a new tab)News report · checked 24 October 2026
  44. GKToday, 2 October 2026: Bihar drafts new building map approval rules (draft uploaded by the Patna Metropolitan Area Authority on 30 September 2026) (opens in a new tab)News report · checked 24 October 2026
  45. The Times of India: Govt replaces building code with a new standard, retains fire safety provisions as 'advisory' (30 April 2026) (opens in a new tab)News report · checked 24 October 2026