Fire systems 18 min read

Fire suppression system in India: clean agent, CO2, kitchen wet chemical and panel systems, where the rules ask for them, safety limits and checks

Updated By Flamekite Editorial DeskFacts checked against official sources on

Fire suppression system in India: clean agent, CO2 and kitchen wet chemical types, where rules ask for them, the 9 percent HFC 227ea limit and 6-monthly checks.

HFC 227ea safe limit (NOAEL)
9 percent
LOAEL 10.5 percent; above it only in unoccupied rooms
Gas safety limits 
Gas agent checked
Every 6 months
Refill at more than 5 percent loss (IS 15496)
Maintenance 
Battery container suppression
1 April 2027
Compulsory in every BESS container above 650 V (CEA)
The CEA rule 
Kitchen hood suppression
Starred hotels
NBC Annex G; malls and food courts under the DGFS checklist
Kitchen rules 

Quick answer

A fire suppression system is a fixed installation that puts out a fire in one room or one piece of equipment automatically with something other than sprinkler water: a clean agent gas such as HFC 227ea, an inert gas such as IG-541, carbon dioxide, a wet chemical over a kitchen hood, or water mist and spray. A detector triggers it, an alarm warns people, and after a delay the agent floods the space or the hazard.

No Indian rule asks it of every building. NBC 2016 asks for clean agent or CO2 for special rooms and electrical panels in some business buildings, NBC Annex G and the DGFS mall checklist ask kitchen suppression in starred hotels and food courts, NBCS 2026 Annex F asks it for data halls, and the CEA asks it in every battery container from 1 April 2027. Gas systems are kept to IS 15496: agent checked every 6 months, refilled at more than 5 percent loss.

Fire suppression system IS codes and key numbers at a glance

The Indian Standards for gas, mist and spray suppression that Flamekite read, their status where confirmed, and the numbers searchers ask about.
WhatThe ruleSource
Gaseous systems, general requirementsIS 15493:2004, withdrawn by BIS on 14 March 2022; a 2021 revision is cited but was not readBIS standards database
Inspection and maintenance of gas systemsIS 15496:2004, Code of PracticeIS 15496:2004
HFC 227ea (heptafluoropropane) systemsIS 15517:2004IS 15517:2004
Carbon dioxide systemsIS 15528:2004: total flooding and local application, high and low pressureIS 15528:2004
Water mistIS 15519:2004: design, installation and commissioning with potable waterIS 15519:2004
Water spray (e.g. transformers)IS 15325:2003: automatic high and medium velocity water sprayIS 15325:2003
Commercial kitchensNBCS 2026 points to IS 18271:2023 and defines a wet chemical system for Class K grease fires (5.2.2.7)BIS, SP 7:2026
HFC 227ea least design concentration7.5 percent by volume, whatever the fuel (IS 15517)IS 15517:2004
CO2 in occupied roomsNormally used in unoccupied areas: discharge leaves too little oxygen to breathe (IS 15528 foreword)IS 15528:2004
Gas system yearly checkEvery system inspected and tested yearly by competent persons; no discharge test needed (IS 15496)IS 15496:2004

Types of fire suppression system: clean agent, inert gas, CO2, wet chemical and mist

The five families of special suppression used in Indian buildings, with the code Flamekite read for each and where the rules point to it.
OptionHow it puts the fire outPeople in the roomIndian code readWhere rules point to itSource
Halocarbon clean agent (HFC 227ea)Floods the room to a design concentrationAllowed up to the NOAEL of 9 percent; above 10.5 percent only in unoccupied roomsIS 15517:2004Data halls (NBCS Annex F), special rooms in business buildings (NBC 6.5.2(b))IS 15517:2004
Inert gas (IG-541, IG-55, IG-100, IG-01)Lowers oxygen with nitrogen, argon or a CO2 blendNOAEL 43 percent, LOAEL 52 percentIS 15493:2004 (withdrawn) for limitsElectrical panels, as inert gas flooding (NBC 6.5.2(b))IS 15493:2004 (withdrawn)
Carbon dioxide (CO2)Total flooding or local application on the hazardNormally unoccupied areas only, with lock-off valveIS 15528:2004Electrical panels (NBC 6.5.2(b)); MV and lift panels in Gujarat's inspection sheetIS 15528:2004
Wet chemical (kitchen hood)Liquid reacts with hot fat to a soapy layer that cools and smothersOver the cooking line, manual release tooIS 18271:2023 by reference (not read)Starred hotel kitchens (NBC Annex G), mall food courts (DGFS items 27, 31)BIS, SP 7:2026
Water mist and water sprayFine droplets cool and smother; spray drenches a transformer or tankSafe for peopleIS 15519:2004, IS 15325:2003Server rooms (NBCS Table 9 for mist); transformers (Gujarat IN2.3)IS 15519:2004

Fire suppression system installation in 8 steps, from risk to handover

  1. Name the hazard

    Room, panel, kitchen line or battery container, its fuel (Class A surface, Class B liquid, cooking fat, live electrics) and whether people work in it.

  2. Check which rule asks for it

    NBC 2016 or NBCS 2026 clause, the DGFS checklist, CEA regulations or your state's order, and what the fire officer's NOC conditions say.

  3. Choose the agent

    Within its safety limit for an occupied room: HFC 227ea up to 9 percent, inert gases up to 43 percent; CO2 only where the room is normally empty (IS 15493 Table 2; IS 15528).

  4. Seal the enclosure

    The room must be strong and tight enough to hold the agent; openings are kept to the minimum, and ceiling tiles are anchored within 1.5 m of each nozzle (IS 15493 cl. 7, 8).

  5. Fit detection, alarms and delay

    Detectors to IS 2189, audible and visual pre-discharge alarms inside, a time delay to let people out, and lock-off valves where the concentration could harm them (cl. 6, 9).

  6. Pressure-test the pipework

    Open-ended pipes held at 3 bar for 10 minutes, with a drop of no more than 20 percent (IS 15493 cl. 10.2.11).

  7. Prove it holds

    A full-scale discharge test where the authority insists, otherwise an enclosure integrity test (cl. 10.10).

  8. Hand over with the logbook

    Certificate, as-installed drawings and flow calculations to the owner, and a signed site logbook started for IS 15496 maintenance.

Fire suppression system components: 10 parts and their job

IS 15493 defines the parts and safeguards of a gas system. A kitchen or panel system has the same chain on a smaller scale.

Agent container
Cylinder marked with the agent, its tare and gross weight and its pressure, mounted so it can be weighed and inspected (IS 15493 cl. 8). IS 15493:2004 (withdrawn)
Manifold and non-return valves
Join several containers and stop agent escaping if one is removed for service (cl. 8). IS 15493:2004 (withdrawn)
Pipework and nozzles
Non-combustible pipe blown clean before use; flow calculation must predict each nozzle's agent within minus 5 to plus 10 percent (IS 15517). IS 15517:2004
Detectors
Smoke or heat detectors to IS 2189 that start the release; in data halls aspirating detection (NBCS Annex F). NBCS 2026 Annex F
Control panel
Receives detection, runs the delay and fires the release; status lamps green for Auto, yellow for Manual, red for Discharge (IS 15493 cl. 9). IS 15493:2004 (withdrawn)
Pre-discharge alarm
Distinct sound and light inside the room that warns before discharge and keeps going until acknowledged (cl. 9). IS 15493:2004 (withdrawn)
Time delay
Pause between alarm and discharge sized to how long people take to leave (cl. 6.2, 9.6). IS 15493:2004 (withdrawn)
Lock-off valve
Mechanical valve that stops agent reaching the room while people work in it (cl. 3, 6.1). IS 15493:2004 (withdrawn)
Abort switch
Not recommended; if fitted, inside near the exit and only working while held pressed (cl. 9). IS 15493:2004 (withdrawn)
Manual release
Hand release for the hood's extinguishing medium in a large kitchen (NBCS 2026 cl. 4.7.2). BIS, SP 7:2026

How a gas fire suppression system works: detection to discharge

A gas system floods a closed room within seconds of release, so the sequence before release is built round getting people out.

  1. 1. Detection

    A detector in the room or under the floor senses smoke or heat and signals the suppression panel. NBCS 2026 Annex F

  2. 2. Warning

    Pre-discharge sounders and lights inside the room start at once, distinct from every other alarm (IS 15493 cl. 9). IS 15493:2004 (withdrawn)

  3. 3. Delay

    A time delay lets occupants leave; it may be cut only where a fast fire would make a delay more dangerous (cl. 9.6). IS 15493:2004 (withdrawn)

  4. 4. Release

    The panel opens the container valves; the agent reaches its design concentration, which for CO2 on a surface fire is within 1 minute (IS 15528). IS 15528:2004

  5. 5. Hold

    The closed room keeps the agent above extinguishing concentration for the holding time; leaks through openings let it escape (IS 15493 cl. 3, 7). IS 15493:2004 (withdrawn)

  6. 6. Recharge and reset

    Containers are refilled, and a container more than 5 years from its last test is retested first (IS 15496). IS 15496:2004

Fire suppression gas safety limits: NOAEL and LOAEL by agent

Every gas agent has a level with no observed harm (NOAEL) and a level where harm was first seen (LOAEL). The design concentration must respect them where people may be present.

NOAEL (percent by volume)LOAEL (percent by volume)In a normally occupied room
HFC 227ea (heptafluoropropane) IS 15493:2004 (withdrawn)910.5Up to NOAEL; above LOAEL never
IG-541 (nitrogen, argon, CO2 blend) IS 15493:2004 (withdrawn)4352Up to NOAEL; above LOAEL never
IG-100 (nitrogen) IS 15493:2004 (withdrawn)4352Up to NOAEL; above LOAEL never
Carbon dioxide IS 15528:2004Not givenNot givenNormally unoccupied areas only; enter only with the lock-off valve closed

Values from Table 2 of IS 15493:2004, a withdrawn edition; check the current edition and the agent's listing. HFC 227ea above 10.5 percent is only for normally unoccupied rooms, and not above 10.5 percent where escape takes 30 seconds to 1 minute (IS 15517).

Where Indian rules call for a fire suppression system

Suppression is asked room by room, not building by building. These are the rules Flamekite found that name it.

  1. IfA business building in groups E-3 to E-5 with special rooms or electrical panels

    NBC 2016 clause 6.5.2(b): clean agents, mist or hypoxic air for special locations, CO2 or inert gas flooding for electrical panels. Offices BIS, NBC 2016 Part 4

  2. IfA data centre

    NBCS 2026 Annex F: clean agents such as heptafluoropropane or a fluorinated ketone in data halls, and their own suppression for UPS, transformer and generator rooms. Fire NOC for Data Centre NBCS 2026 Annex F

  3. IfA centrally air-conditioned starred hotel kitchen

    NBC 2016 Annex G asks for a kitchen suppression system. Hotels BIS, NBC 2016 Part 4

  4. IfA mall, multiplex or food court

    The DGFS checklist (advisory) asks automatic wet chemical suppression over restaurant hoods, items 27 and 31. Malls and shops DGFS mall checklist

  5. IfA battery energy storage system above 650 V

    CEA regulation 122F(2): automatic suppression in every battery container from 1 April 2027. CEA Battery Storage (BESS) Fire Safety Rules 2026 CEA

  6. IfA one-floor shop, clinic or coaching centre under 500 m² in Uttarakhand

    The 6 June 2025 order asks automatic extinguishers on the electrical panel, UPS and DG set. Fire NOC Uttarakhand Uttarakhand GO 2025

Kitchen hood fire suppression system: what Indian rules ask

Kitchen suppression is written narrowly. Four rules name it; none makes it compulsory for every restaurant.

  • NBC 2016 Annex G

    Starred hotels

    A centrally air-conditioned starred hotel's kitchen needs a kitchen suppression system, not just extinguishers. BIS, NBC 2016 Part 4

  • NBC 4.7.2, NBCS 4.7.2

    Hood detectors in high-rise kitchens

    Large kitchens in high-rise hotels, hospitals and similar buildings get thermal detectors in the hood that trip the exhaust fan and shut off gas, with a manual release for the hood's extinguishing medium. BIS, SP 7:2026

  • DGFS items 27, 31

    Malls and food courts

    Restaurant kitchens compartmented by at least 60 minutes, with automatic wet chemical suppression over the hoods (advisory checklist). DGFS mall checklist

  • NBCS 2026 5.2.2.7

    What the system is

    A fixed wet chemical system for Class K cooking-oil fires; NBCS sends commercial kitchens to IS 18271:2023 for detail. BIS, SP 7:2026

Electrical panel and server room suppression: do's and don'ts

Panels and server rooms are where gas and tube systems are most often fitted. The codes set these limits.

Do

  • Use CO2 or inert gas flooding for electrical panels where NBC 2016 clause 6.5.2(b) applies. BIS, NBC 2016 Part 4
  • Use aspirating smoke detection in server areas to trigger suppression early (NBCS Annex F, F-3.1, F-3.2). NBCS 2026 Annex F
  • Fit a lock-off valve and keep the system on manual while anyone is inside a CO2-protected room (IS 15528). IS 15528:2004
  • Seal every new cable or duct hole through the protected room's walls, and inspect the enclosure at least every 12 months (IS 15496). IS 15496:2004

Don’t

  • Do not use clean agent or water mist in a lithium-ion battery room: NBCS Table 9 marks them not suitable; use pre-action sprinklers or water spray. NBCS 2026 Table 9
  • Do not flood a normally occupied room with CO2: it creates a dangerous lack of oxygen (IS 15528 foreword). IS 15528:2004
  • Do not design HFC 227ea above 10.5 percent for a room people work in (IS 15517). IS 15517:2004

Fire suppression system numbers from the Indian codes

Six figures that recur in gas system design and upkeep.

  • 7.5 percent

    Least design concentration of HFC 227ea for any fuel (IS 15517) IS 15517:2004

  • 30 percent

    Factor added to the theoretical CO2 concentration to get the design figure (IS 15528) IS 15528:2004

  • 20 min

    Least time a 30 percent CO2 concentration is held round enclosed rotating electrical machines (IS 15528) IS 15528:2004

  • 40 percent

    Extra CO2 stored in high-pressure cylinders, since only the liquid part is effective (IS 15528) IS 15528:2004

  • 1.5 m

    Radius round each nozzle within which ceiling tiles are anchored (IS 15493) IS 15493:2004 (withdrawn)

  • 3 bar

    Pneumatic test of open-ended pipework for 10 minutes, drop at most 20 percent (IS 15493 cl. 10.2.11) IS 15493:2004 (withdrawn)

What a fire inspector checks on a fire suppression system

Gujarat's inspection sheet is the one state form Flamekite read that names suppression items. The rest come from the codes an inspector applies.

Fire suppression system maintenance: monthly to every 5 years

IS 15496 sets the cycle for gas systems, with a signed logbook entry for each visit.

  1. Weekly

    Only where the authority deems it necessary: switches and indicators checked and the alarm to the fire control station confirmed. IS 15496:2004

  2. Monthly

    Simulated alarm on each zone to the fire control station; alarm bell and indicators checked, with the agent isolated first. IS 15496:2004

  3. Every 6 months

    Agent quantity and pressure checked and logged. Halocarbon: refill at more than 5 percent loss of agent or 10 percent of pressure. Inert gas: at more than 5 percent pressure loss. IS 15496:2004

  4. Every 6 months (CO2)

    High-pressure CO2 cylinders weighed; refill or replace at a net loss of more than 10 percent (IS 15528). IS 15528:2004

  5. Yearly

    Whole system inspected and tested by competent persons; detectors checked for sensitivity; hoses examined; enclosure checked for new openings. IS 15496:2004

  6. Every 5 years

    Containers visually inspected and retested before recharge; system hoses pressure-tested. IS 15496:2004

CEA rule that makes battery container suppression compulsory

The one Indian regulation Flamekite found that makes automatic suppression compulsory in so many words, for every battery container from 1 April 2027.

Word for word

Every battery container shall be provided with automatic fire suppression system as per relevant standard.

Regulation 122F(2), CEA (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026 CEA

It applies to battery energy storage connected above 650 V and names no agent: the CEA's list of relevant standards was still to be issued on 26 October 2026. NBCS 2026 separately marks clean agent and water mist not suitable for lithium-ion battery rooms in buildings.

Fire suppression faults that fail an inspection

Each fault breaks a clause of IS 15493, IS 15496 or IS 15528, or a rule above.

  • If Gas cylinders never weighed, or no logbook

    Weigh and log every 6 months and keep the signed logbook on site (IS 15496). IS 15496:2004

  • If Agent loss above the limit

    Refill or replace: halocarbon over 5 percent agent or 10 percent pressure, inert gas over 5 percent pressure, CO2 over 10 percent of mass. IS 15496:2004

  • If Room altered after design: new cable holes, false ceiling or extra racks

    Seal penetrations and have the design concentration rechecked; changes in volume or contents change the concentration (IS 15493 cl. 6.1). IS 15493:2004 (withdrawn)

  • If CO2 system left on Auto while staff work in the room

    Close the lock-off valve before anyone enters (IS 15528). IS 15528:2004

  • If No pre-discharge alarm or time delay

    Fit distinct sounders and lights inside and a delay sized to the escape time (IS 15493 cl. 9.6). IS 15493:2004 (withdrawn)

  • If Clean agent fitted in a lithium-ion battery room

    Replace with pre-action sprinklers or water spray (NBCS 2026 Table 9, Note 15). NBCS 2026 Table 9

Fire suppression system myths the codes contradict

Five claims about suppression that the codes and rules do not support.

  • You may have read

    Every restaurant must fit a wet chemical hood system.

    Myth

    What the sources say

    NBCS 2026 defines the system and asks hood detectors only of large kitchens in high-rise hotels, hospitals and similar buildings; the state and the fire officer decide the rest. BIS, SP 7:2026

  • You may have read

    A gas system must be test-discharged every year.

    Myth

    What the sources say

    IS 15496 asks a yearly inspection and test and says discharge tests are not necessary. IS 15496:2004

  • You may have read

    CO2 is a safe agent for an office server room with staff.

    Myth

    What the sources say

    IS 15528 says CO2 creates a dangerous lack of oxygen and should normally be used in unoccupied areas. IS 15528:2004

  • You may have read

    The CEA has named the gas for battery containers.

    Myth

    What the sources say

    Regulation 122F(2) says automatic suppression as per relevant standard and nothing more. CEA

  • You may have read

    A suppression system replaces the building's sprinklers and extinguishers.

    Myth

    What the sources say

    It protects one room or hazard; NBC 2016 Table 7 still sets the building's sprinklers, hydrants and extinguishers. NBC 2016, Table 7

Fire suppression for 3 rooms: worked examples

Flamekite's reading of the codes and rules above for three common cases. Your fire service's reading prevails.

  1. Case 1

    A 40 m² server room in a 20 m office

    Staffed during the day, inside a sprinklered office building.

    What applies No separate NOC. NBCS Table 9 points to aspirating detection with clean agent or pre-action sprinklers; an HFC 227ea design must stay at or below 9 percent with a pre-discharge alarm and delay, because people work there. NBCS 2026 Table 9

  2. Case 2

    The kitchen of a 5-star hotel

    Centrally air-conditioned, 30 m tall.

    What applies NBC Annex G asks a kitchen suppression system, and clause 4.7.2 thermal detectors in the hoods that trip the exhaust and shut the gas, with a manual release. BIS, NBC 2016 Part 4

  3. Case 3

    A containerised BESS beside a substation

    Lithium-ion, connected above 650 V, commissioned in 2027.

    What applies From 1 April 2027 regulation 122F(2) asks automatic suppression in every container, with smoke, gas, heat and flame detection and a third-party fire safety audit. CEA

What Flamekite could not confirm about fire suppression systems

Six facts a reader would expect here are not stated, because no official text was available to read on 29 October 2026.

  • The current edition of IS 15493 (a 2021 revision is cited) and the current BIS status of IS 15496, IS 15517 and IS 15528: the 2004 texts were read instead.
  • IS 18271:2023 on commercial kitchens: not read, so no wet chemical design values are given.
  • An official rate for a gas, kitchen hood or electrical panel suppression system from CPWD, a state schedule or GeM: none found, so no price is given.
  • An Indian Standard for automatic tube or panel suppression units: none read.
  • HSN code and GST rate for suppression systems: not confirmed from a CBIC or GST Council notification.
  • Design values for fluorinated ketone and aerosol systems: no Indian text read.

Questions about fire suppression systems in India

What is a fire suppression system?

A fixed installation that puts out a fire in one room or on one piece of equipment automatically, with a clean agent gas, inert gas, CO2, a kitchen wet chemical, or water mist or spray, after a detector triggers it and an alarm warns people.

Fire suppression system kya hota hai?

Ek sthir pranali jo kisi kamre ya upkaran mein aag ko apne aap bujhati hai: gas (clean agent, inert gas, CO2), kitchen hood ke liye wet chemical, ya water mist. Detector chalu karta hai, alarm chetavni deta hai, phir agent chhoda jata hai.

What gases are used in fire suppression systems?

Halocarbon clean agents such as HFC 227ea (heptafluoropropane), inert gases IG-541, IG-55, IG-100 and IG-01, and carbon dioxide. NBCS 2026 also names a fluorinated ketone for data halls.

Is a clean agent gas safe for people?

Up to its NOAEL: 9 percent for HFC 227ea and 43 percent for inert gases (IS 15493 Table 2). Above the LOAEL it is not allowed in occupied rooms, and a pre-discharge alarm and delay are required.

Can CO2 suppression be used where people work?

IS 15528 says CO2 should normally be used in unoccupied areas, because it leaves too little oxygen. Anyone entering must first lock the system off.

Which buildings need a fire suppression system in India?

No rule asks it of every building. NBC 2016 asks it for special rooms and panels in some business buildings, NBC Annex G for starred hotel kitchens, NBCS 2026 for data halls, the DGFS checklist for mall food courts and the CEA for battery containers from 1 April 2027.

Is a kitchen hood suppression system compulsory?

Only where a rule names it: centrally air-conditioned starred hotels (NBC Annex G), mall and food court kitchens under the DGFS checklist, and large high-rise kitchens that need hood detectors and a manual release. Your state and fire officer decide the rest.

What suppression is used for electrical panels?

NBC 2016 clause 6.5.2(b) names CO2 or inert gas flooding for electrical panels; Uttarakhand's 2025 order asks automatic extinguishers on panels, UPS and DG sets of small premises.

What suppression is used in a server room or data centre?

NBCS 2026 Annex F asks clean agents such as heptafluoropropane or a fluorinated ketone in data halls with aspirating detection; Table 9 also rates water mist and pre-action sprinklers suitable, but not clean agent or mist in lithium-ion battery rooms.

How often is a gas suppression system checked?

Under IS 15496: monthly alarm tests, agent weighed or pressure-checked every 6 months, a full yearly inspection and test, and containers retested every 5 years.

When must a suppression cylinder be refilled?

Halocarbon at more than 5 percent loss of agent or 10 percent of pressure, inert gas at more than 5 percent pressure loss (IS 15496), and high-pressure CO2 at more than 10 percent loss of mass (IS 15528).

What does a fire suppression system cost in India?

Flamekite found no official rate from CPWD, a state schedule of rates or GeM for gas, kitchen or panel suppression, so it gives no price. Cost depends on the room volume, the agent and its design concentration.

Keep reading

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15493:2004, Gaseous Fire Extinguishing Systems, General Requirements (withdrawn by BIS on 14 March 2022): definitions, safety precautions, Table 2 toxicity values, alarms, time delays, commissioning and enclosure integrity (opens in a new tab)checked 29 October 2026
  2. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15496:2004, Inspection and Maintenance of Gaseous Fire Extinguishing Systems, Code of Practice: yearly inspection, 6-monthly agent checks, 5-year container tests, logbook and monthly to yearly procedures (opens in a new tab)checked 29 October 2026
  3. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15517:2004, Gaseous Fire Extinguishing Systems, HFC 227ea (Heptafluoropropane) Extinguishing Systems: occupancy limits, design concentration and flow verification (opens in a new tab)checked 29 October 2026
  4. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15528:2004, Gaseous Fire Extinguishing Systems, Carbon Dioxide Total Flooding and Local Application (Sub-floor and In-cabinet), High and Low Pressure (Refrigerated) Systems (opens in a new tab)checked 29 October 2026
  5. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15519:2004, Water Mist Fire Protection Systems, System Design, Installation and Commissioning, Code of Practice (scope read) (opens in a new tab)checked 29 October 2026
  6. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15325:2003, Design and Installation of Fixed Automatic High and Medium Velocity Water Spray System, Code of Practice (scope read) (opens in a new tab)checked 29 October 2026
Show all 18 sourcesShow fewer
  1. Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  2. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clause 3.1.6 (Group E, E-1 to E-5), 3.4.7.4 exit signs, 3.4.8 air handling and ducts, 3.4.10 glazing, 3.4.11 surface interior finishes, 4.3 and Table 3 occupant load, 4.4 egress, Tables 4 and 5, 6.5 business buildings, Annex D fire drills and Fire Safety Plan, Annex E high-rise (read off the page images, pp. 15, 24 to 26, 29 to 32, 64, 65, 81 to 84, 87 and 88) (opens in a new tab)checked 25 October 2026
  3. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  4. Central Electricity Authority (Gazette of India Extraordinary, Part III Section 4, No. 231): CEA (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026, F. No. CEA-PS-16/1/2021-CEI Division, gazetted 30 March 2026, in force 1 April 2027 (scanned copy) (opens in a new tab)checked 26 October 2026
  5. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards, Part F: Annex F Requirements for data centres (F-1 to F-9, printed pages 152 to 155) and clause 3.1.6 Group E with subdivision E-II, read off the page images (opens in a new tab)checked 25 October 2026
  6. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: Table 7 rows (d) hotels (A-5) and (e) hotels (A-6) with Notes 1 to 15, clause 4.10.1 (Fire Officer for starred hotels) and clause 6.1.1.4 (Subdivision A-5), read off the page images (opens in a new tab)checked 25 October 2026
  7. Directorate General Fire Services, Civil Defence and Home Guards, MHA (copy on the CG Fire NOC portal): Fire Safety Audit / Inspection Checklist for Mix Occupancy Building (shopping complex, mall, multiplex, restaurants and parking), F. No. VIII-11011/07/2025-DGCD (F), 19 numbered pages, advisory (opens in a new tab)checked 25 October 2026
  8. Government of Uttarakhand, Home (Adhishthan) Section-3 (copy hosted by Uttarakhand Fire and Emergency Services): Government order No. 304272/XX-3/2025-02(10)/2024, 6 June 2025: amended NBC 2016 Part 4 Table 7 fire installations for low-rise (below 12 m) and mixed occupancy buildings, Annexures A to G (opens in a new tab)checked 24 October 2026
  9. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 Part F, Table 9 Fire detection and suppression systems: rows for UPS rooms, lithium-ion battery rooms, server rooms and data halls, network and electrical rooms, printed page 103, read off the page image (opens in a new tab)checked 26 October 2026
  10. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 28 October 2026
  11. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
  12. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)checked 25 October 2026