Fire suppression system in India: clean agent, CO2, kitchen wet chemical and panel systems, where the rules ask for them, safety limits and checks
Updated By Flamekite Editorial DeskFacts checked against official sources on
Fire suppression system in India: clean agent, CO2 and kitchen wet chemical types, where rules ask for them, the 9 percent HFC 227ea limit and 6-monthly checks.
- HFC 227ea safe limit (NOAEL)
- 9 percent
- LOAEL 10.5 percent; above it only in unoccupied rooms
- Gas safety limits
- Battery container suppression
- 1 April 2027
- Compulsory in every BESS container above 650 V (CEA)
- The CEA rule
- Kitchen hood suppression
- Starred hotels
- NBC Annex G; malls and food courts under the DGFS checklist
- Kitchen rules
Quick answer
A fire suppression system is a fixed installation that puts out a fire in one room or one piece of equipment automatically with something other than sprinkler water: a clean agent gas such as HFC 227ea, an inert gas such as IG-541, carbon dioxide, a wet chemical over a kitchen hood, or water mist and spray. A detector triggers it, an alarm warns people, and after a delay the agent floods the space or the hazard.
No Indian rule asks it of every building. NBC 2016 asks for clean agent or CO2 for special rooms and electrical panels in some business buildings, NBC Annex G and the DGFS mall checklist ask kitchen suppression in starred hotels and food courts, NBCS 2026 Annex F asks it for data halls, and the CEA asks it in every battery container from 1 April 2027. Gas systems are kept to IS 15496: agent checked every 6 months, refilled at more than 5 percent loss.
Free, on WhatsApp. Or a free fire NOC check
Fire suppression system IS codes and key numbers at a glance
| What | The rule | Source |
|---|---|---|
| Gaseous systems, general requirements | IS 15493:2004, withdrawn by BIS on 14 March 2022; a 2021 revision is cited but was not read | BIS standards database |
| Inspection and maintenance of gas systems | IS 15496:2004, Code of Practice | IS 15496:2004 |
| HFC 227ea (heptafluoropropane) systems | IS 15517:2004 | IS 15517:2004 |
| Carbon dioxide systems | IS 15528:2004: total flooding and local application, high and low pressure | IS 15528:2004 |
| Water mist | IS 15519:2004: design, installation and commissioning with potable water | IS 15519:2004 |
| Water spray (e.g. transformers) | IS 15325:2003: automatic high and medium velocity water spray | IS 15325:2003 |
| Commercial kitchens | NBCS 2026 points to IS 18271:2023 and defines a wet chemical system for Class K grease fires (5.2.2.7) | BIS, SP 7:2026 |
| HFC 227ea least design concentration | 7.5 percent by volume, whatever the fuel (IS 15517) | IS 15517:2004 |
| CO2 in occupied rooms | Normally used in unoccupied areas: discharge leaves too little oxygen to breathe (IS 15528 foreword) | IS 15528:2004 |
| Gas system yearly check | Every system inspected and tested yearly by competent persons; no discharge test needed (IS 15496) | IS 15496:2004 |
Types of fire suppression system: clean agent, inert gas, CO2, wet chemical and mist
| Option | How it puts the fire out | People in the room | Indian code read | Where rules point to it | Source |
|---|---|---|---|---|---|
| Halocarbon clean agent (HFC 227ea) | Floods the room to a design concentration | Allowed up to the NOAEL of 9 percent; above 10.5 percent only in unoccupied rooms | IS 15517:2004 | Data halls (NBCS Annex F), special rooms in business buildings (NBC 6.5.2(b)) | IS 15517:2004 |
| Inert gas (IG-541, IG-55, IG-100, IG-01) | Lowers oxygen with nitrogen, argon or a CO2 blend | NOAEL 43 percent, LOAEL 52 percent | IS 15493:2004 (withdrawn) for limits | Electrical panels, as inert gas flooding (NBC 6.5.2(b)) | IS 15493:2004 (withdrawn) |
| Carbon dioxide (CO2) | Total flooding or local application on the hazard | Normally unoccupied areas only, with lock-off valve | IS 15528:2004 | Electrical panels (NBC 6.5.2(b)); MV and lift panels in Gujarat's inspection sheet | IS 15528:2004 |
| Wet chemical (kitchen hood) | Liquid reacts with hot fat to a soapy layer that cools and smothers | Over the cooking line, manual release too | IS 18271:2023 by reference (not read) | Starred hotel kitchens (NBC Annex G), mall food courts (DGFS items 27, 31) | BIS, SP 7:2026 |
| Water mist and water spray | Fine droplets cool and smother; spray drenches a transformer or tank | Safe for people | IS 15519:2004, IS 15325:2003 | Server rooms (NBCS Table 9 for mist); transformers (Gujarat IN2.3) | IS 15519:2004 |
Fire suppression system installation in 8 steps, from risk to handover
Name the hazard
Room, panel, kitchen line or battery container, its fuel (Class A surface, Class B liquid, cooking fat, live electrics) and whether people work in it.
Check which rule asks for it
NBC 2016 or NBCS 2026 clause, the DGFS checklist, CEA regulations or your state's order, and what the fire officer's NOC conditions say.
Choose the agent
Within its safety limit for an occupied room: HFC 227ea up to 9 percent, inert gases up to 43 percent; CO2 only where the room is normally empty (IS 15493 Table 2; IS 15528).
Seal the enclosure
The room must be strong and tight enough to hold the agent; openings are kept to the minimum, and ceiling tiles are anchored within 1.5 m of each nozzle (IS 15493 cl. 7, 8).
Fit detection, alarms and delay
Detectors to IS 2189, audible and visual pre-discharge alarms inside, a time delay to let people out, and lock-off valves where the concentration could harm them (cl. 6, 9).
Pressure-test the pipework
Open-ended pipes held at 3 bar for 10 minutes, with a drop of no more than 20 percent (IS 15493 cl. 10.2.11).
Prove it holds
A full-scale discharge test where the authority insists, otherwise an enclosure integrity test (cl. 10.10).
Hand over with the logbook
Certificate, as-installed drawings and flow calculations to the owner, and a signed site logbook started for IS 15496 maintenance.
Fire suppression system components: 10 parts and their job
IS 15493 defines the parts and safeguards of a gas system. A kitchen or panel system has the same chain on a smaller scale.
- Agent container
- Cylinder marked with the agent, its tare and gross weight and its pressure, mounted so it can be weighed and inspected (IS 15493 cl. 8). IS 15493:2004 (withdrawn)
- Manifold and non-return valves
- Join several containers and stop agent escaping if one is removed for service (cl. 8). IS 15493:2004 (withdrawn)
- Pipework and nozzles
- Non-combustible pipe blown clean before use; flow calculation must predict each nozzle's agent within minus 5 to plus 10 percent (IS 15517). IS 15517:2004
- Detectors
- Smoke or heat detectors to IS 2189 that start the release; in data halls aspirating detection (NBCS Annex F). NBCS 2026 Annex F
- Control panel
- Receives detection, runs the delay and fires the release; status lamps green for Auto, yellow for Manual, red for Discharge (IS 15493 cl. 9). IS 15493:2004 (withdrawn)
- Pre-discharge alarm
- Distinct sound and light inside the room that warns before discharge and keeps going until acknowledged (cl. 9). IS 15493:2004 (withdrawn)
- Time delay
- Pause between alarm and discharge sized to how long people take to leave (cl. 6.2, 9.6). IS 15493:2004 (withdrawn)
- Lock-off valve
- Mechanical valve that stops agent reaching the room while people work in it (cl. 3, 6.1). IS 15493:2004 (withdrawn)
- Abort switch
- Not recommended; if fitted, inside near the exit and only working while held pressed (cl. 9). IS 15493:2004 (withdrawn)
- Manual release
- Hand release for the hood's extinguishing medium in a large kitchen (NBCS 2026 cl. 4.7.2). BIS, SP 7:2026
How a gas fire suppression system works: detection to discharge
A gas system floods a closed room within seconds of release, so the sequence before release is built round getting people out.
1. Detection
A detector in the room or under the floor senses smoke or heat and signals the suppression panel. NBCS 2026 Annex F
2. Warning
Pre-discharge sounders and lights inside the room start at once, distinct from every other alarm (IS 15493 cl. 9). IS 15493:2004 (withdrawn)
3. Delay
A time delay lets occupants leave; it may be cut only where a fast fire would make a delay more dangerous (cl. 9.6). IS 15493:2004 (withdrawn)
4. Release
The panel opens the container valves; the agent reaches its design concentration, which for CO2 on a surface fire is within 1 minute (IS 15528). IS 15528:2004
5. Hold
The closed room keeps the agent above extinguishing concentration for the holding time; leaks through openings let it escape (IS 15493 cl. 3, 7). IS 15493:2004 (withdrawn)
6. Recharge and reset
Containers are refilled, and a container more than 5 years from its last test is retested first (IS 15496). IS 15496:2004
Fire suppression gas safety limits: NOAEL and LOAEL by agent
Every gas agent has a level with no observed harm (NOAEL) and a level where harm was first seen (LOAEL). The design concentration must respect them where people may be present.
| NOAEL (percent by volume) | LOAEL (percent by volume) | In a normally occupied room | |
|---|---|---|---|
| HFC 227ea (heptafluoropropane) IS 15493:2004 (withdrawn) | 9 | 10.5 | Up to NOAEL; above LOAEL never |
| IG-541 (nitrogen, argon, CO2 blend) IS 15493:2004 (withdrawn) | 43 | 52 | Up to NOAEL; above LOAEL never |
| IG-100 (nitrogen) IS 15493:2004 (withdrawn) | 43 | 52 | Up to NOAEL; above LOAEL never |
| Carbon dioxide IS 15528:2004 | Not given | Not given | Normally unoccupied areas only; enter only with the lock-off valve closed |
Values from Table 2 of IS 15493:2004, a withdrawn edition; check the current edition and the agent's listing. HFC 227ea above 10.5 percent is only for normally unoccupied rooms, and not above 10.5 percent where escape takes 30 seconds to 1 minute (IS 15517).
Where Indian rules call for a fire suppression system
Suppression is asked room by room, not building by building. These are the rules Flamekite found that name it.
IfA business building in groups E-3 to E-5 with special rooms or electrical panels
NBC 2016 clause 6.5.2(b): clean agents, mist or hypoxic air for special locations, CO2 or inert gas flooding for electrical panels. Offices BIS, NBC 2016 Part 4
IfA data centre
NBCS 2026 Annex F: clean agents such as heptafluoropropane or a fluorinated ketone in data halls, and their own suppression for UPS, transformer and generator rooms. Fire NOC for Data Centre NBCS 2026 Annex F
IfA centrally air-conditioned starred hotel kitchen
NBC 2016 Annex G asks for a kitchen suppression system. Hotels BIS, NBC 2016 Part 4
IfA mall, multiplex or food court
The DGFS checklist (advisory) asks automatic wet chemical suppression over restaurant hoods, items 27 and 31. Malls and shops DGFS mall checklist
IfA battery energy storage system above 650 V
CEA regulation 122F(2): automatic suppression in every battery container from 1 April 2027. CEA Battery Storage (BESS) Fire Safety Rules 2026 CEA
IfA one-floor shop, clinic or coaching centre under 500 m² in Uttarakhand
The 6 June 2025 order asks automatic extinguishers on the electrical panel, UPS and DG set. Fire NOC Uttarakhand Uttarakhand GO 2025
Kitchen hood fire suppression system: what Indian rules ask
Kitchen suppression is written narrowly. Four rules name it; none makes it compulsory for every restaurant.
NBC 2016 Annex G
Starred hotels
A centrally air-conditioned starred hotel's kitchen needs a kitchen suppression system, not just extinguishers. BIS, NBC 2016 Part 4
NBC 4.7.2, NBCS 4.7.2
Hood detectors in high-rise kitchens
Large kitchens in high-rise hotels, hospitals and similar buildings get thermal detectors in the hood that trip the exhaust fan and shut off gas, with a manual release for the hood's extinguishing medium. BIS, SP 7:2026
DGFS items 27, 31
Malls and food courts
Restaurant kitchens compartmented by at least 60 minutes, with automatic wet chemical suppression over the hoods (advisory checklist). DGFS mall checklist
NBCS 2026 5.2.2.7
What the system is
A fixed wet chemical system for Class K cooking-oil fires; NBCS sends commercial kitchens to IS 18271:2023 for detail. BIS, SP 7:2026
Electrical panel and server room suppression: do's and don'ts
Panels and server rooms are where gas and tube systems are most often fitted. The codes set these limits.
Do
- Use CO2 or inert gas flooding for electrical panels where NBC 2016 clause 6.5.2(b) applies. BIS, NBC 2016 Part 4
- Use aspirating smoke detection in server areas to trigger suppression early (NBCS Annex F, F-3.1, F-3.2). NBCS 2026 Annex F
- Fit a lock-off valve and keep the system on manual while anyone is inside a CO2-protected room (IS 15528). IS 15528:2004
- Seal every new cable or duct hole through the protected room's walls, and inspect the enclosure at least every 12 months (IS 15496). IS 15496:2004
Don’t
- Do not use clean agent or water mist in a lithium-ion battery room: NBCS Table 9 marks them not suitable; use pre-action sprinklers or water spray. NBCS 2026 Table 9
- Do not flood a normally occupied room with CO2: it creates a dangerous lack of oxygen (IS 15528 foreword). IS 15528:2004
- Do not design HFC 227ea above 10.5 percent for a room people work in (IS 15517). IS 15517:2004
Fire suppression system numbers from the Indian codes
Six figures that recur in gas system design and upkeep.
7.5 percent
Least design concentration of HFC 227ea for any fuel (IS 15517) IS 15517:2004
30 percent
Factor added to the theoretical CO2 concentration to get the design figure (IS 15528) IS 15528:2004
20 min
Least time a 30 percent CO2 concentration is held round enclosed rotating electrical machines (IS 15528) IS 15528:2004
40 percent
Extra CO2 stored in high-pressure cylinders, since only the liquid part is effective (IS 15528) IS 15528:2004
1.5 m
Radius round each nozzle within which ceiling tiles are anchored (IS 15493) IS 15493:2004 (withdrawn)
3 bar
Pneumatic test of open-ended pipework for 10 minutes, drop at most 20 percent (IS 15493 cl. 10.2.11) IS 15493:2004 (withdrawn)
What a fire inspector checks on a fire suppression system
Gujarat's inspection sheet is the one state form Flamekite read that names suppression items. The rest come from the codes an inspector applies.
- Water spray or nitrogen systems on transformers and gas flooding on MV and lift panels (Gujarat Regulations 2023, Annexure 12, IN2.3 to IN2.7). Gujarat Fire Safety Compliance Portal
- Signed, dated logbook on site, produced to the authority on demand (IS 15496 cl. 4.2). IS 15496:2004
- Containers weighed and tagged with date, weight, agent and inspector's name (IS 15496). IS 15496:2004
- Pre-discharge alarm inside the room, warning signs and the status lamps showing Auto (IS 15493 cl. 6, 9). IS 15493:2004 (withdrawn)
- Lock-off valve where the design concentration can harm occupants (cl. 6.1). IS 15493:2004 (withdrawn)
- Room unchanged since design: no new openings, no added volume or contents (cl. 6.1 warning; IS 15496). IS 15493:2004 (withdrawn)
- In Maharashtra, suppression kept by the same agency as detection and alarm for the whole building (MFS guidelines clause 6.1). MFS Form B guidelines
Fire suppression system maintenance: monthly to every 5 years
IS 15496 sets the cycle for gas systems, with a signed logbook entry for each visit.
Weekly
Only where the authority deems it necessary: switches and indicators checked and the alarm to the fire control station confirmed. IS 15496:2004
Monthly
Simulated alarm on each zone to the fire control station; alarm bell and indicators checked, with the agent isolated first. IS 15496:2004
Every 6 months
Agent quantity and pressure checked and logged. Halocarbon: refill at more than 5 percent loss of agent or 10 percent of pressure. Inert gas: at more than 5 percent pressure loss. IS 15496:2004
Every 6 months (CO2)
High-pressure CO2 cylinders weighed; refill or replace at a net loss of more than 10 percent (IS 15528). IS 15528:2004
Yearly
Whole system inspected and tested by competent persons; detectors checked for sensitivity; hoses examined; enclosure checked for new openings. IS 15496:2004
Every 5 years
Containers visually inspected and retested before recharge; system hoses pressure-tested. IS 15496:2004
CEA rule that makes battery container suppression compulsory
The one Indian regulation Flamekite found that makes automatic suppression compulsory in so many words, for every battery container from 1 April 2027.
Word for word
Every battery container shall be provided with automatic fire suppression system as per relevant standard.
It applies to battery energy storage connected above 650 V and names no agent: the CEA's list of relevant standards was still to be issued on 26 October 2026. NBCS 2026 separately marks clean agent and water mist not suitable for lithium-ion battery rooms in buildings.
Fire suppression faults that fail an inspection
Each fault breaks a clause of IS 15493, IS 15496 or IS 15528, or a rule above.
If Gas cylinders never weighed, or no logbook
Weigh and log every 6 months and keep the signed logbook on site (IS 15496). IS 15496:2004
If Agent loss above the limit
Refill or replace: halocarbon over 5 percent agent or 10 percent pressure, inert gas over 5 percent pressure, CO2 over 10 percent of mass. IS 15496:2004
If Room altered after design: new cable holes, false ceiling or extra racks
Seal penetrations and have the design concentration rechecked; changes in volume or contents change the concentration (IS 15493 cl. 6.1). IS 15493:2004 (withdrawn)
If CO2 system left on Auto while staff work in the room
Close the lock-off valve before anyone enters (IS 15528). IS 15528:2004
If No pre-discharge alarm or time delay
Fit distinct sounders and lights inside and a delay sized to the escape time (IS 15493 cl. 9.6). IS 15493:2004 (withdrawn)
If Clean agent fitted in a lithium-ion battery room
Replace with pre-action sprinklers or water spray (NBCS 2026 Table 9, Note 15). NBCS 2026 Table 9
Fire suppression system myths the codes contradict
Five claims about suppression that the codes and rules do not support.
You may have read
Every restaurant must fit a wet chemical hood system.
Myth
What the sources say
NBCS 2026 defines the system and asks hood detectors only of large kitchens in high-rise hotels, hospitals and similar buildings; the state and the fire officer decide the rest. BIS, SP 7:2026
You may have read
A gas system must be test-discharged every year.
Myth
What the sources say
IS 15496 asks a yearly inspection and test and says discharge tests are not necessary. IS 15496:2004
You may have read
CO2 is a safe agent for an office server room with staff.
Myth
What the sources say
IS 15528 says CO2 creates a dangerous lack of oxygen and should normally be used in unoccupied areas. IS 15528:2004
You may have read
The CEA has named the gas for battery containers.
Myth
What the sources say
Regulation 122F(2) says automatic suppression as per relevant standard and nothing more. CEA
You may have read
A suppression system replaces the building's sprinklers and extinguishers.
Myth
What the sources say
It protects one room or hazard; NBC 2016 Table 7 still sets the building's sprinklers, hydrants and extinguishers. NBC 2016, Table 7
Fire suppression for 3 rooms: worked examples
Flamekite's reading of the codes and rules above for three common cases. Your fire service's reading prevails.
Case 1
A 40 m² server room in a 20 m office
Staffed during the day, inside a sprinklered office building.
What applies No separate NOC. NBCS Table 9 points to aspirating detection with clean agent or pre-action sprinklers; an HFC 227ea design must stay at or below 9 percent with a pre-discharge alarm and delay, because people work there. NBCS 2026 Table 9
Case 2
The kitchen of a 5-star hotel
Centrally air-conditioned, 30 m tall.
What applies NBC Annex G asks a kitchen suppression system, and clause 4.7.2 thermal detectors in the hoods that trip the exhaust and shut the gas, with a manual release. BIS, NBC 2016 Part 4
Case 3
A containerised BESS beside a substation
Lithium-ion, connected above 650 V, commissioned in 2027.
What applies From 1 April 2027 regulation 122F(2) asks automatic suppression in every container, with smoke, gas, heat and flame detection and a third-party fire safety audit. CEA
What Flamekite could not confirm about fire suppression systems
Six facts a reader would expect here are not stated, because no official text was available to read on 29 October 2026.
- The current edition of IS 15493 (a 2021 revision is cited) and the current BIS status of IS 15496, IS 15517 and IS 15528: the 2004 texts were read instead.
- IS 18271:2023 on commercial kitchens: not read, so no wet chemical design values are given.
- An official rate for a gas, kitchen hood or electrical panel suppression system from CPWD, a state schedule or GeM: none found, so no price is given.
- An Indian Standard for automatic tube or panel suppression units: none read.
- HSN code and GST rate for suppression systems: not confirmed from a CBIC or GST Council notification.
- Design values for fluorinated ketone and aerosol systems: no Indian text read.
Questions about fire suppression systems in India
What is a fire suppression system?
Fire suppression system kya hota hai?
What gases are used in fire suppression systems?
Is a clean agent gas safe for people?
Can CO2 suppression be used where people work?
Which buildings need a fire suppression system in India?
Is a kitchen hood suppression system compulsory?
What suppression is used for electrical panels?
What suppression is used in a server room or data centre?
How often is a gas suppression system checked?
When must a suppression cylinder be refilled?
What does a fire suppression system cost in India?
Keep reading
- Fire fighting systemWhere suppression sits among risers, sprinklers, pumps and alarms.
- Fire sprinkler systemPre-action and deluge systems for rooms gas cannot protect.
- Fire alarm systemThe detection that triggers a suppression release.
- Fire extinguishersClean agent and CO2 portable units, classes and IS 2190.
- Fire NOC for data centresNBCS Annex F, Table 9 and lithium-ion rules.
- Fire NOC for restaurantsKitchen rules, LPG, hoods and wet chemical systems.
- CEA battery storage rulesRegulation 122F and the third-party audit.
- Fire AMCKeeping detection, alarm and suppression under one contract.
Words on this page, explained
Keep exploring
The codes and laws behind it
Sources
Each source was opened and read on the date shown. How Flamekite checks its sources
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15493:2004, Gaseous Fire Extinguishing Systems, General Requirements (withdrawn by BIS on 14 March 2022): definitions, safety precautions, Table 2 toxicity values, alarms, time delays, commissioning and enclosure integrity (opens in a new tab)
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15496:2004, Inspection and Maintenance of Gaseous Fire Extinguishing Systems, Code of Practice: yearly inspection, 6-monthly agent checks, 5-year container tests, logbook and monthly to yearly procedures (opens in a new tab)
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15517:2004, Gaseous Fire Extinguishing Systems, HFC 227ea (Heptafluoropropane) Extinguishing Systems: occupancy limits, design concentration and flow verification (opens in a new tab)
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15528:2004, Gaseous Fire Extinguishing Systems, Carbon Dioxide Total Flooding and Local Application (Sub-floor and In-cabinet), High and Low Pressure (Refrigerated) Systems (opens in a new tab)
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15519:2004, Water Mist Fire Protection Systems, System Design, Installation and Commissioning, Code of Practice (scope read) (opens in a new tab)
- Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15325:2003, Design and Installation of Fixed Automatic High and Medium Velocity Water Spray System, Code of Practice (scope read) (opens in a new tab)
Show all 18 sourcesShow fewer
- Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clause 3.1.6 (Group E, E-1 to E-5), 3.4.7.4 exit signs, 3.4.8 air handling and ducts, 3.4.10 glazing, 3.4.11 surface interior finishes, 4.3 and Table 3 occupant load, 4.4 egress, Tables 4 and 5, 6.5 business buildings, Annex D fire drills and Fire Safety Plan, Annex E high-rise (read off the page images, pp. 15, 24 to 26, 29 to 32, 64, 65, 81 to 84, 87 and 88) (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)
- Central Electricity Authority (Gazette of India Extraordinary, Part III Section 4, No. 231): CEA (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026, F. No. CEA-PS-16/1/2021-CEI Division, gazetted 30 March 2026, in force 1 April 2027 (scanned copy) (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards, Part F: Annex F Requirements for data centres (F-1 to F-9, printed pages 152 to 155) and clause 3.1.6 Group E with subdivision E-II, read off the page images (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: Table 7 rows (d) hotels (A-5) and (e) hotels (A-6) with Notes 1 to 15, clause 4.10.1 (Fire Officer for starred hotels) and clause 6.1.1.4 (Subdivision A-5), read off the page images (opens in a new tab)
- Directorate General Fire Services, Civil Defence and Home Guards, MHA (copy on the CG Fire NOC portal): Fire Safety Audit / Inspection Checklist for Mix Occupancy Building (shopping complex, mall, multiplex, restaurants and parking), F. No. VIII-11011/07/2025-DGCD (F), 19 numbered pages, advisory (opens in a new tab)
- Government of Uttarakhand, Home (Adhishthan) Section-3 (copy hosted by Uttarakhand Fire and Emergency Services): Government order No. 304272/XX-3/2025-02(10)/2024, 6 June 2025: amended NBC 2016 Part 4 Table 7 fire installations for low-rise (below 12 m) and mixed occupancy buildings, Annexures A to G (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 Part F, Table 9 Fire detection and suppression systems: rows for UPS rooms, lithium-ion battery rooms, server rooms and data halls, network and electrical rooms, printed page 103, read off the page image (opens in a new tab)
- Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)
- Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)