Fire safety equipment list for buildings in India: what each building type needs by height, from extinguishers to sprinklers

Updated By Flamekite Editorial DeskFacts checked against official sources on

Fire safety equipment list for Indian buildings from NBC 2016 Table 7: extinguishers, hose reels, risers, hydrants, sprinklers, alarms and tanks by height.

Building types with no extinguisher rule
1
A-2 houses; every other row needs them
Baseline list 
Flats: sprinklers throughout from
45 m
Below that, only basements over 200 m²
Sprinkler test 
Five-star hotel underground tank
250,000
Litres, the largest in Table 7
Equipment table 
Floor area per extinguisher, light hazard
300 m²
150 m² moderate, 100 m² high
Extinguisher count 

Quick answer

The fire safety equipment a building in India must have is set by Table 7 of NBC 2016 Part 4, which state fire rules adopt: up to 12 kinds of installation, from extinguishers and hose reels through down-comers, wet risers, yard hydrants, sprinklers, manual and automatic alarms, underground and terrace water tanks and fire pumps, rising with height and occupancy. Extinguishers are needed in every building type except one- or two-family houses.

A block of flats under 15 m needs extinguishers, a first-aid hose reel and a 5,000-litre terrace tank; at 45 m to 60 m it needs a wet riser, a yard hydrant, sprinklers throughout and a 150,000-litre underground tank. Hospitals, malls, five-star hotels and big factories need nearly everything at any height. Add exit signs and 90 minutes of escape lighting in every building Part 4 covers.

Fire safety equipment list at a glance: 10 items and their codes

The installations Table 7 names, and the Indian Standard each is built and kept to.
WhatThe ruleSource
Fire extinguishersEvery row of Table 7 except A-2 houses; sized and counted under IS 2190:2024NBC 2016, Table 7
First-aid hose reelThe lowest water installation, alone in small flats, lodges, schools and shopsNBC 2016, Table 7
Down-comerA dry-at-the-bottom riser fed from the terrace tank, in mid-height flats, schools, small assembly halls and low officesNBC 2016, Table 7
Wet riserA charged riser with landing valves on each floor, from 35 m in flats and in most hotels, hospitals, malls and factoriesNBC 2016, Table 7
Yard hydrantAn external hydrant ring round the building, from 45 m in flats and in larger non-residential rowsNBC 2016, Table 7
Automatic sprinklersIn basements over 200 m² in most rows, and throughout taller and higher-risk buildingsNBC 2016, Table 7
Manual fire alarmCall points from 15 m in flats and in most other rows; automatic detection added in hotels, hospitals and tall buildingsNBC 2016, Table 7
Underground tankFrom 75,000 litres for flats of 35 m to 45 m up to 250,000 litres for five-star hotelsNBC 2016, Table 7
Terrace tank and pump5,000 to 25,000 litres, with a 450 or 900 litre a minute pump in smaller rowsNBC 2016, Table 7
Exit signs and escape lightingGreen lit signs within 30 m, lighting lasting 90 minutes, in every Part 4 building (3.4.7)BIS, NBC 2016 Part 4

Fire safety equipment by building type and height (NBC 2016 Table 7)

The equipment each proof-read Table 7 row asks for on top of extinguishers, and its water storage.
OptionRiser or hose reelYard hydrantSprinklersAlarmWater: underground / terrace (litres)Source
Flats under 15 mHose reelNoBasement over 200 m²NoneNone / 5,000NBC 2016, Table 7
Flats 15 m to 35 mDown-comerNoBasement over 200 m²ManualNone / 25,000NBC 2016, Table 7
Flats 45 m to 60 mWet riserYesThroughoutManual150,000 / 10,000NBC 2016, Table 7
Hotel under 15 m, floors over 1,000 m²Wet riser above one storeyYesThroughoutManual and automatic100,000 / 10,000NBC 2016, Table 7
Five-star hotel, any heightWet riserYesThroughoutManual and automatic250,000 / 20,000NBC 2016, Table 7
School under 15 mHose reelNoBasement over 200 m²NoneNone / 10,000NBC 2016, Table 7
Hospital 15 m to 24 mWet riserYesThroughoutManual and automatic150,000 / 20,000NBC 2016, Table 7
Mall with cinemas or food courtsWet riserYesThroughoutManual and automatic200,000 / 20,000NBC 2016, Table 7
Office under 10 mDown-comerNoBasement over 200 m²ManualNone / 10,000NBC 2016, Table 7
Office above 30 mWet riserYesThroughoutManual and automatic200,000 / 20,000NBC 2016, Table 7
Shops, ground plus one, up to 500 m²Hose reelNoBasement over 200 m²NoneNone / 5,000NBC 2016, Table 7
Moderate hazard factory over 1,000 m²Wet riserYesThroughoutManual and automatic150,000 / 20,000NBC 2016, Table 7
Warehouse under 15 m, over 250 m², ground onlyWet riserYesThroughoutManual and automatic50,000 / 10,000NBC 2016, Table 7

How to work out your building's fire equipment list in 6 steps

  1. Find the occupancy group

    Residential, educational, institutional, assembly, business, mercantile, industrial, storage or hazardous, with the subdivision (A-4 flats, C-1 hospitals, D-6 malls and so on).

  2. Measure the height

    Table 7 rows step at 10, 15, 24, 30, 35, 45 and 60 m depending on the group; use the height your fire officer uses, usually to the top floor's level.

  3. Note floor area and basements

    Some rows turn on floor area (hotels at 300 and 1,000 m²) and most add sprinklers for a basement over 200 m².

  4. Read across the row

    Riser, hydrant, sprinklers, alarm, tanks and pumps. Extinguishers come on top, counted by floor area under IS 2190.

  5. Add the Part 4 baseline

    Exit signs, escape lighting, fire doors to stairs, and in high-rise buildings the extra rules of Annex E.

  6. Check your state's schedule

    Some states publish their own list, such as Maharashtra's Schedule-I; it prevails where it differs.

Fire safety equipment every covered building needs

Whatever the row, a building that Part 4 covers ends up with these 7 items. Only A-2 houses are left out of Table 7 altogether.

  • Portable extinguishers on every floor, at least 2 per floor (1 if the floor is under 100 m²), chosen for the fire classes present (IS 2190 cl. 7.2). IS 2190:2024
  • Green exit signs, lit on an independent circuit, within 30 m of every point (NBC 2016 clause 3.4.7.4). BIS, NBC 2016 Part 4
  • Escape lighting that comes on within 5 seconds and lasts 90 minutes (clause 3.4.7.1). BIS, NBC 2016 Part 4
  • Fire doors of 120 minutes into exit staircases, closing by themselves (clause 4.4.2.4.3). NBC 2016, Part 4
  • At least a first-aid hose reel, or a riser, in every proof-read row except houses. NBC 2016, Table 7
  • Sprinklers in any basement over 200 m², even where the floors above need none. NBC 2016, Table 7
  • 5,000 litres more in the terrace tank where a basement exceeds 200 m² (Note 6). NBC 2016, Table 7

How many fire extinguishers per floor, by hazard

IS 2190:2024 Table 1 sets the rating, floor area and walking distance for each extinguisher. Use the calculator to count your floor.

Least Class A ratingFloor area per unitWalking distance to a Class A unitLeast Class B rating, within 15 m
Light hazard: offices, homes, classrooms2A300 m²20 m55B
Moderate hazard: shops, workshops, stores3A150 m²20 m144B
High hazard: heavy storage, flammable processes4A100 m²15 m233B

At least 2 units on each floor, or 1 where the floor is under 100 m² (cl. 7.2). Class F (cooking oil) units go within 10 m of the hazard (cl. 7.7.2). Electrical rooms need units marked for live equipment (cl. 6.3.7). IS 2190:2024

Does your building need sprinklers? 8 answers from Table 7

Sprinklers are the costliest line on the list, so this is the question owners ask first.

  1. IfFlats or hostels under 45 m

    Only in a basement over 200 m²; from 45 m, throughout the building. Sprinkler systems NBC 2016, Table 7

  2. IfA hotel under 15 m

    Basement only if floors are up to 1,000 m²; throughout once a floor exceeds 1,000 m². Hotels NBC 2016, Table 7

  3. IfA five-star hotel

    Throughout, at any height. NBC 2016, Table 7

  4. IfA school under 24 m

    Only in a basement over 200 m². Schools and colleges NBC 2016, Table 7

  5. IfA hospital with beds on ground plus 2 or more, even under 15 m on a plot up to 1,000 m²

    Throughout. Hospitals NBC 2016, Table 7

  6. IfAn office or shop building of 15 m to 24 m, or an office above 30 m

    Throughout; below 10 m, an office needs them only in a basement over 200 m². Offices NBC 2016, Table 7

  7. IfA mall with cinemas or food courts, or a multi-level car park

    Throughout. Malls and shops NBC 2016, Table 7

  8. IfA warehouse over 250 m², or a moderate hazard factory over 1,000 m²

    Throughout. Warehouses NBC 2016, Table 7

Fire water tanks and pumps in numbers

Table 7's water columns and the pump notes beneath it.

  • 2,50,000 litres

    Underground tank for a five-star hotel, the largest in Table 7 NBC 2016, Table 7

  • 2,00,000 litres

    Underground tank for malls, offices above 30 m and flats above 60 m NBC 2016, Table 7

  • 75,000 litres

    Underground tank for flats of 35 m to 45 m and small hospitals NBC 2016, Table 7

  • 5,000 litres

    Smallest terrace tank, and the extra amount Note 6 adds for a basement over 200 m² NBC 2016, Table 7

  • 2,850 l/min

    Largest main pump in the notes; others are 1,620 and 2,280 l/min NBC 2016, Table 7

  • 180 l/min

    Jockey pump that keeps the system pressurised NBC 2016, Table 7

  • 900 l/min

    Terrace pump in mid-size rows; 450 l/min in the smallest NBC 2016, Table 7

Fire safety equipment names and what each one does

The systems on your fire NOC drawing, each with the page that covers it in depth.

State fire equipment lists that differ from Table 7

Most states point to Table 7. Some publish their own schedules; where they do, follow them.

Maharashtra, Schedule-I (2023)
Its apartment row starts below 15 m: extinguishers, a first-aid hose reel, a 5,000-litre terrace tank and a 450 l/min terrace pump; talk-back and public address from 24 m. MH Act 2023 Schedule-I
Kerala, KMBR rule 5(4)
A fire NOC is needed above 1,000 m² or 15 m, assembly buildings over 200 m² and hazardous and multiplex buildings at any size, so the equipment list is checked from those sizes. KMBR amendment 2025
Ladakh, Fire Rules 2025
Its own schedule by class, with glow-in-the-dark exit signs and emergency lights on a second power source in every column. Gazette notification S.O. 140
Gujarat, Regulations 2023, Annexure 12
The inspector's checklist that each certified building's equipment is tested against, including extinguisher hydro test intervals. Gujarat Fire Safety Compliance Portal

Fire equipment mistakes that fail an inspection

Equipment bought is not equipment that works. Five findings and the fix.

  • If Sprinklers fitted on the floors but not in the 300 m² basement car park.

    Table 7 asks for basement sprinklers over 200 m² in almost every row; extend the system. NBC 2016, Table 7

  • If Terrace tank sized without the basement.

    Add the 5,000 litres Note 6 requires where a basement exceeds 200 m². NBC 2016, Table 7

  • If Only CO2 extinguishers throughout an office.

    Class A fires need A-rated units; CO2 is for electrical and B risks. Match type to the fire (IS 2190 cl. 6). IS 2190:2024

  • If Extinguishers past 10 years from manufacture.

    Replace them: service life is 10 years, 15 for CO2, whatever the refill dates (Annex G). IS 2190:2024

  • If Exit signs that go dark in a power cut.

    Wire them to the alternative supply on an independent circuit (clause 3.4.7.4). BIS, NBC 2016 Part 4

Fire safety equipment myths

Four beliefs that cost money or leave a gap.

  • You may have read

    Sprinklers mean you can drop the extinguishers.

    Myth

    What the sources say

    Table 7 lists extinguishers alongside every system; IS 2190 says fixed systems never replace them (cl. 1.1). IS 2190:2024

  • You may have read

    Every building over 15 m needs sprinklers throughout.

    Myth

    What the sources say

    Not flats: under Table 7 they need sprinklers throughout only from 45 m. Offices and shops of 15 m to 24 m and hospitals of 15 m to 24 m do. NBC 2016, Table 7

  • You may have read

    A small house needs fire equipment by law.

    Myth

    What the sources say

    Table 7 sets nothing for A-2 one- or two-family houses; extinguishers are still sensible. NBC 2016, Table 7

  • You may have read

    Any red cylinder is a legal extinguisher.

    Myth

    What the sources say

    Extinguishers sold in India must carry the BIS mark under the Fire Extinguishers (Quality Control) Order, 2023. Gazette of India

Fire equipment lists for 4 real-world buildings

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's reading of Table 7 rows for example buildings. Your fire officer confirms the final list.

  1. Case 1

    A 12 m apartment block, no basement

    Ground plus 3 flats.

    What applies Extinguishers, a first-aid hose reel and a 5,000-litre terrace tank; no riser, hydrant, sprinklers or alarm under the under-15 m row. NBC 2016, Table 7

  2. Case 2

    A 50 m residential tower with a 2,000 m² basement

    Flats, 45 m to 60 m row.

    What applies Wet riser, yard hydrant, sprinklers throughout, manual alarm, 150,000 litres underground and 10,000 on the terrace, plus 5,000 for the basement. NBC 2016, Table 7

  3. Case 3

    A 20 m hospital

    C-1, 15 m to 24 m row.

    What applies Wet riser, yard hydrant, sprinklers throughout, manual and automatic alarm, 150,000 litres underground and 20,000 on the terrace. NBC 2016, Table 7

  4. Case 4

    A 600 m² ground-floor warehouse

    Storage under 15 m, over 250 m².

    What applies Wet riser, yard hydrant, sprinklers throughout, manual and automatic alarm, 50,000 litres underground and 10,000 on the terrace. NBC 2016, Table 7

Questions about fire safety equipment lists

What fire safety equipment is required in a building in India?

NBC 2016 Part 4 Table 7 sets it by occupancy and height: extinguishers in all but houses, then hose reels, down-comers or wet risers, yard hydrants, sprinklers, manual and automatic alarms, tanks and pumps, plus exit signs and 90 minutes of escape lighting.

What is the fire fighting equipment list as per NBC?

Table 7's columns: extinguishers, first-aid hose reels, wet riser, down-comer, yard hydrant, automatic sprinklers, manual fire alarm, automatic detection and alarm, underground tank, terrace tank, and the pumps that serve them.

What fire safety equipment does an apartment building need?

Under 15 m: extinguishers, a hose reel and a 5,000-litre terrace tank. 15 m to 35 m adds a down-comer and manual alarm. From 35 m a wet riser; from 45 m a yard hydrant and sprinklers throughout.

Which buildings need sprinklers in India?

Under Table 7, basements over 200 m² in almost all buildings; throughout in flats from 45 m, offices and shops of 15 m to 24 m, offices above 30 m, hospitals with beds on upper floors, five-star hotels, malls, car parks, warehouses over 250 m² and larger factories.

How many fire extinguishers are required per floor?

At least 2 per floor (1 if under 100 m²), with one unit per 300 m² in light hazard, 150 m² in moderate and 100 m² in high hazard areas (IS 2190:2024).

What fire safety equipment does an office need?

An office under 10 m needs extinguishers, a down-comer, a manual alarm and a 10,000-litre terrace tank. From 15 m to 24 m it needs a wet riser, yard hydrant, sprinklers throughout, manual and automatic alarm and a 100,000-litre underground tank.

What are the names of fire safety equipment?

Fire extinguisher, fire bucket, hose reel, down-comer, wet riser, landing valve, yard hydrant, sprinkler, smoke and heat detector, manual call point, fire alarm panel, fire pump, jockey pump, exit sign and emergency light.

Keep reading

Free tools for this

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)checked 25 October 2026
  2. Bureau of Indian Standards: IS 2190:2024, Selection, Installation and Maintenance of First-Aid Fire Extinguishers (Portable and Mobile), Code of Practice, fifth revision (free download after registration) (opens in a new tab)checked 26 October 2026
  3. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clauses 3.4.5, 3.4.6.2, 3.4.7, 4.4.2 (Tables 4 and 5), 4.4.2.5 (Table 6), 4.5.2 and Annex E (opens in a new tab)checked 25 October 2026
  4. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clauses 2.16 to 2.39 (exit, exit access, exit discharge, fire door notes, fire exit, fire exit hardware), 3.4.7.1 (escape lighting), 4.2 (general exit requirements, door swing) and 4.4.2.4.2 to 4.4.2.4.3.4 (corridors, curved and external stairs) (opens in a new tab)checked 29 October 2026
  5. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clause 4.3 and Table 3 (occupant load), 4.4.2.2 (dead ends), Table 4 (capacity factors), Table 5 (travel distance), 4.4.2.4.1 (doorways) and 4.4.2.4.3 (staircases), printed pages 29 to 34, read off the page images (opens in a new tab)checked 25 October 2026
  6. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: minimum fire fighting installations for apartment houses (A-4) by height, with Notes 1, 4, 6, 10, 11 and 15 (read off the page images, pp. 13 to 15 and 32 to 34) (opens in a new tab)checked 25 October 2026
Show all 10 sourcesShow fewer
  1. Local Self Government Department, Government of Kerala (Kerala Gazette Extraordinary No. 3808): Kerala Municipality Building (Amendment) Rules, 2025 (G.O.(P) No.53/2025/LSGD, S.R.O. No.1240/2025, 29 October 2025) and Kerala Panchayat Building (Amendment) Rules, 2025 (G.O.(P) No.54/2025/LSGD): rule 5(4) restated, rules 35 and 36 (opens in a new tab)checked 25 October 2026
  2. Gazette notification S.O. 140 (copy hosted by Simpliance): Ladakh Fire Prevention and Fire Safety Rules, 2025 (S.O. 140, 28 November 2025) (opens in a new tab)checked 24 October 2026
  3. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 28 October 2026
  4. Department for Promotion of Industry and Internal Trade, Gazette of India Extraordinary No. 3431, 10 August 2023: Fire Extinguishers (Quality Control) Order, 2023, S.O. 3585(E), 9 August 2023: IS 15683:2018 and IS 16018:2012 (opens in a new tab)checked 26 October 2026