Fire extinguisher calculator: how many fire extinguishers your floor needs under IS 2190

Updated By Flamekite Editorial DeskFacts checked against official sources on

Free fire extinguisher calculator: enter floor area, floors and hazard class to get the number, rating and walking distance under IS 2190:2024 clause 7.

Light hazard, area per unit
300 m²
150 m² moderate, 100 m² high
Limits table 
Minimum on a floor
2
One where the floor is under 100 m²
Method 
Class A walking distance
20 m
15 m in a high hazard
Limits table 
Hazard class (IS 2190 Annex B examples)
What else could burn?

IS 2190:2024 · Light hazard

4 fire extinguishers of at least 2A

1,200 m² divided by 300 m² a unit is 4 (cl. 7.2).

On each floor
4
Class A rating
2A+
Walk to a unit
20 m
At most, from any point
Area per unit
300 m²
At most (cl. 7.2)
  • Class A units for the building itself: 4, 2A or higher4 on each floor, no point more than 20 m walking distance from one (cl. 7.1.3, 7.2)
  • Units near live electrical equipmentCO2, powder, clean agent or water mist tested and marked for energised equipment; no CO2 with a metal horn (cl. 6.3.7, 7.5.2)

Limits from IS 2190:2024; types and ratings from IS 15683:2018

Flamekite's count from the standard's minimums. Walls and corridors can push it higher; your fire officer's NOC conditions can ask for more.

Quick answer

Under IS 2190:2024 clause 7.2, one extinguisher may cover at most 300 m² of floor in a light hazard, 150 m² in a moderate hazard and 100 m² in a high hazard, with at least two on every floor of 100 m² or more. Divide the floor area by that figure, round up, and never go below two.

Each unit needs a Class A rating of at least 2A, 3A or 4A, and no point of the floor may be more than 20 m (15 m in a high hazard) from one. Flammable liquids, gas, live electrics, cooking oil and metals each add their own type, which the calculator lists with the clause.

Fire extinguisher requirement per area under IS 2190:2024

The clause 7 limits by hazard class: the Class A rating, the walking distance and the floor area one unit may cover, then the Class B and C limits.
OptionClass A minimum ratingClass A maximum travelMaximum floor area per extinguisherClass B and C minimum ratingClass B and C maximum travelSource
Light hazard2A20 m300 m²55B15 mIS 2190:2024
Moderate hazard3A20 m150 m²144B15 mIS 2190:2024
High hazard4A15 m100 m²233B15 mIS 2190:2024

Fire extinguisher requirement calculation in 5 steps

  1. Pick the hazard class

    Annex B of IS 2190:2024 gives example criteria, not hard rules: light hazard is under 15 occupants, under 300 m² and up to 15 m high; high hazard is over 250 occupants, over 3,000 m² or over 15 m; moderate is in between.

  2. Divide each floor by the area per unit

    300 m² a unit for light, 150 m² for moderate and 100 m² for high hazard (cl. 7.2). Round up.

  3. Apply the two-per-floor minimum

    Every floor of 100 m² or more carries at least two units; a floor under 100 m² may have one (cl. 7.2.2).

  4. Check the walking distance

    No point may be more than 20 m from a Class A unit, or 15 m in a high hazard. On a cut-up plan this can need more units than the area count.

  5. Add units for the special risks

    Class B and C units of at least 55B, 144B or 233B within 15 m of liquids and gases; units marked for energised equipment near panels; a Class F unit within 10 m of a fryer; a unit marked for the metal for Class D (cl. 6, 7.3 to 7.7).

Which extinguisher type for which fire class

Clause 6 matches the type to the fire class first, and clause 7 then sizes it. These are the suitability lines IS 15683:2018 sets out.

Class A (solids)Class B (liquids)Class C (gases)Class F (cooking oil)Live electrical
Water basedYes, A ratingNoNoNoNo
FoamAs ratedAs rated, B ratingBy B ratingNoNo
ABC powderYes, A ratingAs ratedBy B ratingNoIf marked suitable
Carbon dioxideNo A ratingAs ratedBy B ratingNoIf marked suitable, no metal horn
Clean agentAs ratedAs ratedBy B ratingNoIf marked suitable
Water mistAs ratedAs ratedBy B ratingOnly if F ratedIf marked suitable

Class D metals need a unit marked for that metal. Class F units are sized by the cooking area: 5F up to 0.03 m², 15F up to 0.05 m², 25F up to 0.08 m², 75F up to 0.25 m² (cl. 7.7). IS 15683:2018

How many fire extinguishers are required: 6 worked floors

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's arithmetic from the clause 7 limits. The number is the larger of the area count and what the walking distance needs.

  1. Case 1

    A small shop

    One floor of 80 m², light hazard

    What applies Under 100 m², so one 2A unit is the minimum (cl. 7.2.2). Two is the safer plan where the floor has two exits. IS 2190:2024

  2. Case 2

    An open-plan office floor

    One floor of 1,200 m², light hazard

    What applies 1,200 divided by 300 is 4 units of at least 2A, no point more than 20 m from one. IS 2190:2024

  3. Case 3

    A 5-floor office building

    5 floors of 450 m², light hazard

    What applies 450 divided by 300 is 1.5, rounded up to 2 per floor: 10 units of at least 2A in all. IS 2190:2024

  4. Case 4

    A workshop with paint and solvents

    600 m², moderate hazard, flammable liquids

    What applies 600 divided by 150 is 4 units of at least 3A, plus Class B units of at least 144B within 15 m of the liquids. IS 2190:2024

  5. Case 5

    A storeroom

    400 m², high hazard

    What applies 400 divided by 100 is 4 units of at least 4A, none more than 15 m away, with 233B units for any flammable liquid. IS 2190:2024

  6. Case 6

    A restaurant fryer

    Cooking area of 0.04 m²

    What applies 15F covers up to 0.05 m², so one 15F unit within 10 m, on top of the Class A units for the dining floor. IS 2190:2024

Where the count needs a closer look

The area count is the floor of the requirement, not the answer for every plan.

  • If Walls and corridors break up the floor

    Walk the plan: if any point is more than 20 m (15 m in a high hazard) from a unit, add one, whatever the area count says. IS 2190:2024

  • If Adding up small Class B units

    Lower-rated units may not be added together to reach the rating, except up to 3 AFFF units whose ratings sum to it (cl. 7.3.2). IS 2190:2024

  • If A metal fire risk

    Class D units are sized by the metal and its particle size, not by area. Ask us with the metal and the quantity. IS 2190:2024

  • If Your state or NOC asks for more

    IS 2190 sets minimums (cl. 1.3). A state rule or the fire officer's NOC conditions can ask for more; Mizoram's draft rule of one per 200 m² is not yet in force. IS 2190:2024

  • If Buckets in place of extinguishers

    The standard does not recommend fire buckets as a replacement, though they may be added on top. IS 2190:2024

Questions about fire extinguisher calculation

How do I calculate how many fire extinguishers a floor needs?

Divide the floor area by 300 m² (light hazard), 150 m² (moderate) or 100 m² (high), round up, and keep at least two on any floor of 100 m² or more (IS 2190:2024 cl. 7.2). Then check that no point is more than 20 m, or 15 m in a high hazard, from a unit.

How many fire extinguishers per square foot are required?

IS 2190 works in square metres: one unit per 300 m² (about 3,230 sq ft) in a light hazard, 150 m² (about 1,615 sq ft) in a moderate hazard and 100 m² (about 1,076 sq ft) in a high hazard, with at least two per floor.

What rating should each fire extinguisher have?

At least 2A in a light hazard, 3A in a moderate hazard and 4A in a high hazard for ordinary combustibles; for flammable liquids and gases at least 55B, 144B or 233B (IS 2190:2024 clause 7).

Does a small room under 100 m² need two extinguishers?

No. Clause 7.2.2 allows one unit on a floor under 100 m². Two is still the safer plan where the floor has two exits.

Which extinguisher goes near an electrical panel?

CO2, powder, clean agent or water mist units tested and marked suitable for energised equipment; a CO2 unit with a metal horn is not safe on live equipment (IS 2190 cl. 6.3.7). Use a clean agent where powder residue would damage electronics.