Fire audit in India: what it means, which states require it, how often and who may sign

Updated By Flamekite Editorial DeskFacts checked against official sources on

Free fire NOC checkDo I need a fire NOC?

Quick answer

A fire audit (fire audit kya hota hai: a check of a building's fire safety) is an inspection of its fire prevention and life safety measures by someone the state recognises, usually a licensed or empanelled auditor independent of the owner. The auditor tests the systems, looks for hazards, lists the fixes and signs a certificate in the state's form.

It is not the fire NOC, which the fire service issues, and not Maharashtra's Form B, which the maintenance agency signs. India has no national audit cycle: Maharashtra's section 45 buildings are audited every 2 years, Madhya Pradesh wants Form-S by 30 June each year, Telangana asks for a third-party certificate every January or every January and July by height and use, and Chhattisgarh and Odisha every January and July.

Maharashtra section 45 buildings
Every 2 years
Licensed Fire and Life Safety Auditor, Form V
10 facts
Telangana hospitals above 15 m
January and July
Third-party certificate, 2020 circular
Duty finder
Bihar fire audit fee
Rs 1 to Rs 5 per m²
Schedule C, by building category
Official fees
Delhi auditor route starts
20 May 2027
Deferred by the gazette of 16 October 2026
Timeline

Fire audit in India at a glance: 10 facts

What a fire audit is and who requires it, in 10 facts with their sources. Last verified 25 October 2026.
WhatThe ruleSource
What it isAn unbiased assessment of a building's fire and life safety measures by an independent auditor, who identifies hazards and recommends corrective measures against the National Building Code and BIS standards (Telangana's definition)G.O.Ms.No.15
Who sets the ruleEach state or municipal law: fire services are item 7 of the Twelfth Schedule to the ConstitutionLegislative Department, Ministry of Law and Justice
The Union's templateThe 2019 Model Bill asks for a qualified agency's compliance certificate, then maintenance certificates every January and July (section 24)DGFS, MHA
Maharashtra, section 45 buildingsEvery 2 years, by a Fire and Life Safety Auditor licensed by the Director (section 45A, inserted in 2023)Amendment Act 2023
Telangana, by height and useA third-party certificate every January, or every January and July for residential buildings of 45 m, malls, multiplexes, hospitals above 15 m and hotels above 30 mTG fire circular 2020
Madhya PradeshAn annual fire audit report on Form-S by 30 June, for buildings under NBC clause 4.10.1 (Bhumi Vikas rule 87(5))MP Town Planning
An audit that replaces a renewal visitOdisha renews premises audited every January and July without a fresh application or inspection (since 4 November 2025)Odisha Home Dept
A fee set in lawBihar's Schedule C prices an annual fire audit at Rs 1 to Rs 5 per m² of all floors, by building categoryBFS fee PDF
Not yet workingDelhi's empanelled Fire Safety Auditor route, deferred to 20 May 2027; Tamil Nadu's audit agencies under an Act not yet commenced; Assam's auditors, not yet notifiedDelhi Gazette
Last verified25 October 2026, against the 36 Flamekite state pages and the rules, circulars and portals they citeNot stated

Fire audit rules in all 36 states and UTs: what, how often, who signs

For each state and UT: the periodic fire audit, certificate or declaration its law asks for, how often, who signs it, and whether it works yet. "Not found" means Flamekite found no such duty in the instruments it read.
OptionWhat is audited or filedHow oftenWho signsStatus on 25 October 2026Source
Andhra PradeshA third-party fire audit for the renewal of the fire NOCAt each renewalA Third-party Fire Audit Agency (Qualified Agency) empanelled by the departmentApplications closed 15 July 2026; no list publishedAP audit empanelment
Arunachal PradeshNo periodic audit; section 32(2) lets the Government empanel third-party agencies for low-risk buildingsNot setNone notifiedNot in useGovernment of Arunachal Pradesh
AssamThe owner's self-declaration with a Third Party Fire Safety Auditor's maintenance report, uploaded (rules 18A to 18D)As the Government notifiesA Third Party Fire Safety Auditor empanelled by the DirectorNot started: no notificationAssam Rules 2025
BiharA fire audit under rule 22, opened by a Form C-1 notice, hospitals first and then educational institutions; filed and paid on the Fire NOC and Audit portalSchedule C prices it as an annual auditBihar Fire Service officers, or a registered Fire Consultant at a fixed rate (rule 22(k))In useBihar Rules 2021
ChhattisgarhA licensed auditor's certificate on upkeep (rule 37A(2)(c)), plus a yearly self-declaration with a third-party audit reportCertificate each January and July; report yearlyA fire service officer or a licensed Third Party Auditor, Grades A to DIn force since 24 November 2025CG Home Dept
GoaA licensed agency's certificate, and the owner's Annexure A self-declaration on Rs 100 stamp paperAgency: January and July; owner: yearlyAn agency licensed by the DFES DirectorIn force since 3 July 2025Goa Gazette 2025
GujaratForm B-2 in years 1 and 2; after renewal, the Form B-15 declaration-cum-inspection reportB-2 within 15 days of each anniversary; B-15 every 6 monthsThe Licensed Agency (B-2); the owner or occupier with an enrolled Fire Safety Officer (B-15, rule 26(2) as amended in 2021)In forceGujarat Fire Safety Compliance Portal
HaryanaThe owner's self-declaration that the systems work and nothing changed (sections 19(6) and 20(4)); an empanelled agency audits at issue and renewal under the December 2025 policy, as reportedSelf-declaration yearlyOwner; an empanelled agency picked at randomPolicy text not publishedGovernment of Haryana
Himachal PradeshNot found: the fire station inspects before a NOC issuesNot foundNot foundNot foundEmerging Himachal single window
JharkhandAn annual fire audit before a yearly NOC expires, as the High Court directed in W.P.(PIL) No. 497 of 2023 (reported)YearlyNot specifiedCourt direction, known from a reportLiveLawnews report
KarnatakaBengaluru high-rises: an inspection with a residents' representative under the 7 July 2011 notification, known from a 2011 reportEvery 2 yearsAn officer of District Fire Officer rank or aboveOfficial text not onlineCitizen Mattersnews report
KeralaNot found in the building rules or KFRS pages readNot foundNot foundNot foundKMBR amendment 2025
Madhya PradeshAn annual fire audit report on Form-S (Bhumi Vikas rule 87(5), since 4 September 2020)Yearly, by 30 JuneA Fire Engineer licensed by UADDIn forceMP Town Planning
MaharashtraForm B maintenance certificate; for section 45 buildings, a Fire and Life Safety Audit certified on Form V (section 45A)Form B: January and July; audit: every 2 yearsLicensed agency (Form B); licensed Fire and Life Safety Auditor (Form V)In forceAmendment Act 2023
ManipurThe owner's Form C maintenance declaration to the Fire Officer (section 24(5))January and JulyThe owner, countersigned by the Fire Safety OfficerAct 9 of 2026; rules not foundGovernment of Manipur
MeghalayaMock drills and fire safety audits in all types of establishments, by order of 9 August 2016Not fixedMeghalaya Fire and Emergency ServicesIn useOrder HPL/31/2002/138
MizoramA periodic fire safety audit for high-rise and critical buildings (2026 amendment, item 11); renewal certification still to be notifiedNot fixedSelf or third-party certification, as notifiedNot notifiedMizoram Home Dept
NagalandA licensed agency's Form C2 maintenance certificate (section 24(5)), and a fire service inspection (section 27(A)(6))Form C2: January and July; inspection at least yearlyLicensed agency; the fire serviceIn forceDirectorate of Fire and Emergency Services, Nagaland
OdishaAn audit certificate on Forms IV and IV(B), uploaded (rule 9(14))January and JulyAn auditor empanelled by the Director; rule 9(15)(a) holders for the biggest buildingsIn force; no upload service or auditor list onlineOdisha Home Dept
PunjabPeriodic returns that the building complies (section 23(5)) and audits by qualified auditors (section 23(6))As prescribed; no rule foundQualified auditorsRules not foundPunjab Gazette
RajasthanNot found in the orders readNot foundNot foundNot foundLocal Self Government Department, Rajasthan
SikkimThe owner's Form A6 declaration with the Fire Safety Officer's compliance report (rule 41)January and JulyOwner and Fire Safety Officer; a Qualified Third Party Agency certifies larger buildings at issue on Form A2In force since 17 December 2025Sikkim F&ES Rules 2025
Tamil NaduCategory B buildings: a 3-year fire safety certificate from an empanelled Fire Safety Audit Agency (2025 Act)Every 3 yearsA Fire Safety Audit Agency empanelled under section 32Act not commencedGovernment of Tamil Nadu, Gazette Extraordinary No. 263, 6 June 2025
TelanganaA third-party fire safety auditor's certificate uploaded on the fire service website (2020 circular); an owner's certificate under G.O.Ms.No.15 of 2026Every January, or every January and July, by height and useA third-party fire safety auditor or consultant, with a licence numberIn use; the Fire Audit module needs a loginTG fire circular 2020
TripuraAn empanelled agency's Form B, or the owner's self-certification, for the yearly renewalYearly, after the first 3 yearsAn empanelled inspection agencyNo agency list publishedDirectorate of Fire and Emergency Services, Tripura
Uttar PradeshThe owner's Form A-8 declaration, countersigned by the qualified agency (section 26(5), Rule 56)January and JulyOwner, with a licensed qualified agencyIn forceUP Rules 2024
UttarakhandA self-declaration or Self Audit Report uploaded by the NOC holderEvery 6 monthsOwnerIn force since November 2021Uttarakhand Home notification
West BengalA mock fire drill with a licensed agency, certified on Form G (rule 20 of the 2003 Rules)YearlyLicensed agency, Classes A to CIn forceWB Rules 2003
Andaman and Nicobar IslandsA maintenance certificate under section 26(6) of Regulation 5 of 2026Every JulyNot set: Qualified Agencies to be selected as prescribedRegulation's start not notifiedGazette of India Extraordinary, Part II Section 1, No. 19, 25 May 2026
ChandigarhA licensed agency's certificate that the systems work and nothing changed (section 19(6) as extended)Every JulyLicensed agency (new section 55A)Act extended 6 May 2026; no agency listGazette of India
Dadra and Nagar Haveli and Daman and DiuA maintenance declaration (section 29(6)) and a self-declaration of operational fitness (section 29(4))Every July; once after 30 monthsOwner; a qualified agency certifies at application (section 29(5))In force since 7 July 2026Gazette of India Extraordinary
DelhiA yearly Form K declaration with Rs 1,000; an empanelled Fire Safety Auditor may issue the certificateYearly, from 20 May 2027Fire Safety Auditor (levels L-1 to L-3), Fire Safety Officer, owner or occupierDeferred to 20 May 2027DFS
Jammu and KashmirFire safety audits by the department; no owner filing cycle foundNot fixedFire and Emergency ServicesIn use (reported)Kashmir Readernews report
LadakhCategory III buildings (hotels above 30 rooms, buildings above 15 m) get the fire NOC through empanelled third-party auditorsAt issueEmpanelled third-party auditors, then the Director, Fire and RescueDraft Bye-Laws 2025Ladakh H&UDD
LakshadweepA Form I declaration (rule 12(4)) and a self-declaration of operational fitness after 30 monthsEvery JulyOwner; Qualified Agency inspections await a notification (rule 13)Rules in forceLakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026
PuducherryAudit certificates from any two licensed agencies on display (Categories A and B), with department inspectionsInspections twice a year for Category A, yearly for BLicensed agencies; 6 on the department's listIn force since G.O.Ms.No.61 of 10 September 2025Puducherry G.O. 61

How a fire audit runs: 7 steps from booking to filing

  1. Read your state's fire audit duty

    Find your row in the 36-state table: the form, the month it falls due and who may sign. In Telangana the cycle depends on height and use; in Maharashtra only section 45 buildings need the 2-yearly audit.

  2. Engage a signatory the state recognises

    A licensed or empanelled auditor for audits, a licensed agency for maintenance certificates. Check the state's published list, the auditor's licence number and, in Chhattisgarh and Odisha, the grade or class that covers your building.

  3. Put the records together

    Approved fire drawings, the last NOC or approval, the annual maintenance contract, service and test reports and the last mock drill's attendance sheet.

  4. Host the site visit and the tests

    The auditor walks the exits and refuge areas, runs every pump and alarm and photographs the tests. Maharashtra's rule 33 asks for date- and time-stamped photos or videos signed by the owner's representative.

  5. Receive the report and the certificate

    A report listing each deficiency and its fix, and a certificate in the state's form: Form V in Maharashtra, Forms IV and IV(B) in Odisha, Form-S in Madhya Pradesh.

  6. File it by the deadline

    Upload on the state's portal or submit to the fire officer: each January in Telangana, by 30 June in Madhya Pradesh, every January and July in Chhattisgarh and Odisha.

  7. Close the gaps and diary the next audit

    Fix what the report lists within the notice period, keep the evidence with the certificate, and note the next due date.

Fire audit meaning: what fire audit kya hota hai says in law

A fire audit is a check of the whole building, not of one system, by someone the state allows to sign. Two official texts define it plainly.

Telangana's G.O.Ms.No.15 of 20 January 2026 calls third-party fire and life safety auditors independent organisations or individuals, not affiliated with the owners or occupants, who give an unbiased assessment of the fire and life safety measures, identify hazards and recommend corrective measures under the National Building Code and the relevant BIS standards.

Maharashtra's Fire Adviser drew the line in a circular of 16 September 2015. The licensed agency installs the Schedule I systems and certifies their upkeep in January and July; a Fire Risk Audit looks at what those certificates do not: basement installations, lifts and escalators, exits, electrical fittings, ventilation and air conditioning, fire doors and windows, fire load and venting.

So the word covers three different things in Indian law: an audit by a licensed or empanelled third party (Maharashtra, Chhattisgarh, Odisha, Telangana, Delhi from 2027), an audit by the fire service itself (Bihar's rule 22, Jammu and Kashmir, Meghalaya), and an owner's self-audit or declaration (Uttarakhand's Self Audit Report every 6 months). The table above says which one your state means.

Three kinds of fire audit in Indian law
WhatThe ruleSource
Third-party auditMaharashtra section 45A: only a licensed Fire and Life Safety Auditor may carry out a fire auditAmendment Act 2023
Fire service auditBihar rule 22: a Form C-1 notice, then Form D-1 advice to remove deficiencies and a Form E-1 notice with a time to complyBihar Rules 2021
Owner's self-auditUttarakhand: a self-declaration or Self Audit Report uploaded every 6 months (notification of November 2021)Uttarakhand Home notification

Fire audit vs fire NOC, Form B, renewal and self-declaration

Five papers are often called a fire audit. They differ in who signs, what they prove and when they fall due.

Who signsWhat it provesWhenExample in law
Fire NOC or fire safety certificate Amendment Act 2023The fire serviceThe building met the fire code when inspectedBefore occupation, then on the state's renewal termFinal Fire Safety Approval under Maharashtra's 2006 Act, as amended in 2023
Fire audit Amendment Rules 2025A licensed or empanelled auditor, independent of the ownerHazards, systems, records and staff readiness assessed, with the fixes listedOn the state's cycle: 6 months to 2 yearsForm V certificate with a Fire Audit Report, rule 33 of the 2009 Rules as amended in 2025
Form B maintenance certificate MFS Form B guidelinesThe licensed agency that maintains the systemsThe systems were kept in good repair over the periodJanuary and JulySection 3(3) and rule 4(2), Maharashtra; one agency per system group since 7 July 2026
Renewal Gujarat Gazette 2024The fire service, or a private officer it approvesA further term for the certificateBefore expiryForm B-13.3 in Gujarat, issued only after RFO or CFO approval since 24 June 2024
Self-declaration Government of Goa, Official Gazette Series II No. 14, 3 July 2025The owner or occupierThe owner's word that nothing changed and the systems workYearly or every 6 monthsAnnexure A on Rs 100 stamp paper every year in Goa

In Maharashtra a section 45 building needs all three of the NOC, the January and July Form B and the 2-yearly audit; Form B replaces routine renewal there. The full Form B rules are on the Form B page.

Maharashtra's 2015 fire audit circular: what Form B leaves out

Eight years before the law made audits compulsory, the state's Fire Adviser explained why the agency's half-yearly certificate is not an audit.

Word for word

These factors are not covered by the periodical inspections to be carried out and the certificates to be issued by the Licensed Agency. ... These can be ascertained if "Fire-Risk Audit" is carried out in a building at least once in a year, particularly when, high-rise building are coming up in an increasing number where such Fire Risk Audit is necessary.

Fire Adviser, Government of Maharashtra, Circular No. MFS/2015/10/1462, 16 September 2015, paragraph 07 (read from the page image) MFS circular 2015

Paragraph 11 of the same circular said there was then "no obligation" on owners to get the audit; it only advised it. That changed on 11 May 2023, when section 45A made a licensed Fire and Life Safety Audit compulsory every 2 years for section 45 buildings.

Fire audit scope: 15 checks the Maharashtra and Telangana formats require

Maharashtra's rule 33 lists the auditor's duties and Telangana's 2020 certificate lists the systems by name. Together they are the most detailed official scope in India.

  • A 360-degree assessment of the building from the fire hazard risk point of view Amendment Rules 2025
  • The building's construction checked against the fire safety regulations Amendment Rules 2025
  • Ignition sources found and controlled where flammable materials are stored, processed or moved Amendment Rules 2025
  • Stored goods checked for physical and chemical compatibility, with measures to reduce fire damage Amendment Rules 2025
  • Electrical hazards that may cause a fire, with the measures needed Amendment Rules 2025
  • The Building Management System or fire control room evaluated Amendment Rules 2025
  • Staff safety awareness and training, and readiness to handle an incident Amendment Rules 2025
  • Every active fire and life safety measure tested, and photos or videos taken with date and time stamps, signed by the owner's representative Amendment Rules 2025
  • Fire extinguishers, hose reels, wet riser or down-comer and yard hydrants, counted against NBC Part 4 and marked working or not working TG fire circular 2020
  • Automatic sprinklers and the manually operated electric fire alarm in the entire building, and automatic detection TG fire circular 2020
  • Underground static water tank and terrace tank capacities, in litres TG fire circular 2020
  • Fire pumps at the underground tank: electric and diesel pumps of 2,280 LPM and a jockey pump of 180 LPM TG fire circular 2020
  • Exit signs, emergency lighting with at least 90 minutes of battery backup, and fire shaft pressurisation TG fire circular 2020
  • Basement installations, lifts and escalators, the number of exits, ventilation, fire doors and windows MFS circular 2015
  • Fire load and fire load density, and how fire would be vented MFS circular 2015

The fire audit report: from the site visit to the fire service's file

Every state's paper trail has the same 6 stops, though the forms differ.

  1. 1. Report and certificate

    In Maharashtra the auditor gives the owner a Fire Audit Report and a Form V certificate; each building needs its own Form V. Amendment Rules 2025

  2. 2. Telangana's certificate

    The third-party auditor certifies each of 13 measures as working or not, signs with a licence number and owns any deviation found later. TG fire circular 2020

  3. 3. Upload or submit

    Odisha's Forms IV and IV(B) are uploaded by the owner or an authorised auditor or agency, every January and July. Odisha Home Dept

  4. 4. Online filing and fee

    Telangana's Fire Audit application takes the building's floors, staircases, fire systems and plans, uploaded as PDFs under 3 MB, with the fee paid through the Telangana cyber treasury. TG Fire Audit manual

  5. 5. Deficiencies notified

    Sikkim's shortcomings found at the January or July declaration must be fixed within the notice period, at most 30 days. Sikkim F&ES Rules 2025

  6. 6. The next cycle earned

    In Odisha, premises audited every January and July are renewed without a fresh application or inspection. Odisha Home Dept

Fire audit forms by name: Form V, IV(B), B-15, Form-S, Form K

Each state names its audit papers differently. These are the 12 terms owners meet most.

Fire Risk Audit
Maharashtra's 2015 term for an audit of the factors a licensed agency's certificate does not cover, advised at least once a year. MFS circular 2015
Form V (Maharashtra)
The licensed Fire and Life Safety Auditor's certificate under section 45A, with the audit report attached; one per building. Amendment Rules 2025
Forms W and X (Maharashtra)
The auditor's licence application, with Rs 25,000 and a Rs 20 court-fee stamp, and the 2-year licence itself. Amendment Rules 2025
Forms IV and IV(B) (Odisha)
The audit certificates uploaded every January and July under the 2025 amendment; their wording is in the 2017 Rules, not yet read. Odisha Home Dept
Form B-15 (Gujarat)
The declaration-cum-inspection report every 6 months after renewal, by the owner or occupier and the Fire Safety Officer (rule 26(2) as amended in 2021). Gujarat Fire Safety Compliance Portal
Form-S (Madhya Pradesh)
The annual fire audit report under Bhumi Vikas rule 87(5), due by 30 June. MP Town Planning
Form K (Delhi)
The yearly online declaration with a Rs 1,000 fee that keeps a certificate valid once rule 36 starts on 20 May 2027. DFS
Form A-8 (Uttar Pradesh)
The owner's January and July declaration, countersigned by the qualified agency, naming the electrical and lift audits. UP Rules 2024
Form A6 (Sikkim)
The owner's January and July declaration that the measures are intact, with the Fire Safety Officer's compliance report. Sikkim F&ES Rules 2025
Self Audit Report (Uttarakhand)
The NOC holder's six-monthly declaration that fire arrangements and equipment are working. Uttarakhand Home notification
Forms C-1, D-1 and E-1 (Bihar)
The fire audit notice, the advice to remove deficiencies and the Director's notice with a time to comply. Bihar Rules 2021
Annexure IV (Telangana)
The certificate the owner or occupier gives every January and July under G.O.Ms.No.15 of 2026; the annexure itself is not in the published copy. G.O.Ms.No.15

Fire audit duties in India, dated: 2015 to 2027

From advice in 2015 to fixed cycles in Maharashtra, Madhya Pradesh, Telangana, Chhattisgarh and Odisha, with Delhi due in 2027.

  1. 16 September 2015

    Maharashtra's Fire Adviser advises a Fire Risk Audit at least once a year, while saying owners are under no obligation. MFS circular 2015

  2. 9 August 2016

    Meghalaya orders mock drills and fire safety audits in all types of establishments. Order HPL/31/2002/138

  3. 28 January 2020

    Telangana's Director General tells owners of high-rises with an occupancy NOC to upload a third-party certificate every January, or every January and July. TG fire circular 2020

  4. 4 September 2020

    Madhya Pradesh inserts rule 87(5): an annual Form-S fire audit by 30 June. MP Town Planning

  5. 18 December 2020

    The Supreme Court directs a district committee to fire-audit each COVID hospital at least once a month. Supreme Court of India

  6. 11 May 2023

    Maharashtra's section 45A makes a licensed fire audit compulsory every 2 years for section 45 buildings. Amendment Act 2023

  7. 24 June 2023

    Telangana's G.O.Ms.No.44 issues the first guidelines to empanel third-party fire and life safety auditors. G.O.Ms.No.15

  8. 12 June 2025

    Maharashtra's amendment rules create the auditor's licence (Forms W and X), the Form V certificate and the 12 duties of rule 33. Amendment Rules 2025

  9. 4 November 2025

    Odisha's Second Amendment Rules bring January and July audit uploads and audit-based renewal. Odisha Home Dept

  10. 24 November 2025

    Chhattisgarh's rule 37A: a licensed third-party auditor's certificate each January and July. CG Home Dept

  11. 20 January 2026

    Telangana's G.O.Ms.No.15 replaces the 2023 guidelines and adds the owner's January and July certificate. G.O.Ms.No.15

  12. 1 April 2027

    Due: a third-party fire audit for battery energy storage systems under CEA Chapter XA. CEA

  13. 20 May 2027

    Due: Delhi's empanelled Fire Safety Auditor route and the yearly Form K, after a 270-day deferral. Delhi Gazette

Fire audit fees that an official source sets

Few states put a price on a fire audit. These are the only charges Flamekite found in an Act, rule, notification or official portal.

As published

  • Bihar, annual fire audit fee (Schedule C)Rs 1 to Rs 5 per m²Of all floors, basement included: Rs 1 residential, Rs 2 assembly and institutional, Rs 3 academic, Rs 4 commercial, Rs 5 storage, industrial and hazardous BFS fee PDF
  • Bihar, appeal against a fire audit orderRs 1,000By bank draft or treasury challan (rule 22(f)) Bihar Rules 2021
  • Delhi, yearly Form K, from 20 May 2027Rs 1,000Paid with each online declaration (rule 38(2)) DFS
  • Delhi, the auditor's charge per certification, from 20 May 2027Rs 10,000 to Rs 5,00,000Ranges by auditor level in the Seventh Schedule; the full table is on the third-party fire audit page DFS
  • Tripura, empanelled agency's yearly inspection for Form BRs 200 or 20% of the first charge, whichever is higherFrom the October 2025 empanelment terms; no agency listed yet Tripura Home (F&ES)
  • Telangana, Fire Audit applicationNot shownThe manual says the fee is paid online through the Telangana cyber treasury, without the amount TG Fire Audit manual
  • Maharashtra, the auditor's own licenceRs 25,000Paid by the auditor on Form W; what an auditor charges an owner is not published Amendment Rules 2025

Chhattisgarh leaves the audit fee to the owner and the auditor (agree it before selecting on the portal, which locks the choice); Puducherry's licensed agencies set their own fees. Private auditors' and consultants' quotes are not fire service fees and are not listed.

Fire audit duty finder: 8 buildings, 8 different rules

Find the line closest to your building; the state table has the rest.

  1. If A residential tower above 70 m in Maharashtra

    Form B every January and July from a licensed agency, and a licensed Fire and Life Safety Audit on Form V every 2 years. Amendment Act 2023

  2. If A hospital above 15 m, a mall or multiplex, or a hotel above 30 m in Telangana

    A third-party fire safety auditor's certificate uploaded every January and July. TG fire circular 2020

  3. If A residential building above 30 m and below 45 m in Telangana

    A third-party certificate uploaded once a year, in January. TG fire circular 2020

  4. If A Madhya Pradesh building under NBC clause 4.10.1

    Form-S by 30 June every financial year, from a Fire Engineer licensed by UADD. MP Town Planning

  5. If A non-residential building above 15 m in Odisha

    A January and July audit by an auditor with the rule 9(15)(a)(i) or (ii) qualification; then renewal without a fresh application. Odisha Home Dept

  6. If A hospital seeking NABH accreditation

    Your state's rule, plus a 1-year third-party Type A inspection certificate, which counts only for accreditation, not as the NOC. National Accreditation Board for Hospitals and Healthcare Providers

  7. If A battery energy storage system above 650 V, from 1 April 2027

    A third-party fire audit under CEA Chapter XA, with detection and suppression in every container. CEA

  8. If Any building in Delhi

    No auditor-issued certificate before 20 May 2027; the fire service still certifies. Delhi Gazette

Who may sign a fire audit: 6 kinds of signatory

The signature makes the paper valid. India uses 6 kinds of signatory, and a state may use more than one.

Fire audit in numbers: 8 official and reported figures

The few published counts show how many audits the states run and how many buildings fail.

  • 3,728

    Fire safety audits Jammu and Kashmir Fire and Emergency Services reported for 2025 Kashmir Readernews report

  • 462

    Private hospitals audited in Patna a year before June 2026; 384 were compliant (reported) Patna Pressnews report

  • 356

    Fire safety audits on Meghalaya's list for 2022 and 2023 Meghalaya F&ES

  • 861

    Rows on Maharashtra's licensed-agency list valid to 03.07.2028 (serials to 847); agencies sign Form B but not the audit MFS agency list

  • 12

    Duties rule 33 gives a Maharashtra Fire and Life Safety Auditor, from a 360-degree assessment to dated photos of every test Amendment Rules 2025

  • 13

    Measures on Telangana's 2020 third-party certificate, each marked working or not working TG fire circular 2020

  • 10 %

    Self-certified Maharashtra industrial approvals the online system picks for a fire service inspection (order of 10 December 2025) MFS office order 2025

  • 90 minutes

    Battery backup for emergency lighting that Telangana's certificate checks TG fire circular 2020

Fire audit mistakes that leave a building non-compliant

Each of these leaves an owner holding a paper the state does not accept.

  • If One Form V for a whole Maharashtra campus

    Rule 31 and the note to Form V need a separate certificate for each building. Amendment Rules 2025

  • If Treating a Telangana hospital or mall like any other building

    Hospitals above 15 m, malls, multiplexes, hotels above 30 m and commercial buildings above 30 m upload every January and July, not once a year. TG fire circular 2020

  • If An ordinary empanelled auditor for a big Odisha building

    Non-residential buildings above 15 m, homes above 30 m and premises needing 75,000 litres of underground water need an auditor qualified under rule 9(15)(a)(i) or (ii), not (iii). Odisha Home Dept

  • If A Grade B, C or D auditor for a high-risk Chhattisgarh building

    Only Grade A may audit high-risk buildings. CG Fire NOC

  • If Missing Madhya Pradesh's 30 June deadline twice

    The first default brings a warning and 3 months; the second a show-cause notice on cancelling the fire NOC. MP Town Planning

  • If Letting the installer sign Gujarat's Form B-15

    Regulation 6.6 bars an officer who installed the measures, and 6.7 the building's own Licensed Agency. Gujarat Fire Safety Compliance Portal

Fire audit for a housing society: 4 dos and 4 don'ts

Societies and apartment owners' associations carry the duty once the builder hands over. These rules come from the states' own texts.

Do

  • Take over the fire systems in working order at handover: Bihar's rule 22(g) makes the builder answerable until then, and the owners' association maintains them after. Bihar Rules 2021
  • In Uttarakhand, upload the society's self-declaration or Self Audit Report every 6 months. Uttarakhand Home notification
  • In Telangana, check the society's height: residential buildings of 45 m upload twice a year, those above 30 m and below 45 m once a year in January. TG fire circular 2020
  • Keep the auditor's dated photos and test records with the Maharashtra Form V for the next 2-yearly audit. Amendment Rules 2025

Don’t

Fire audit myths, checked against the law: 5 claims

Vendor pages repeat these. The official texts say otherwise.

  • You may have read

    A fire audit and a fire NOC are the same paper.

    Myth

    What the sources say

    The fire service issues the NOC; a licensed auditor audits. Maharashtra's section 45 buildings need both, every 2 years for the audit. Amendment Act 2023

  • You may have read

    Form B is a fire audit.

    Myth

    What the sources say

    Maharashtra's 2015 circular says the licensed agency's certificates do not cover exits, lifts, electrical fittings, ventilation, fire doors or fire load; that is the audit's job. MFS circular 2015

  • You may have read

    Indian law requires a fire audit every year, everywhere.

    Myth

    What the sources say

    Fire services are a state subject (Twelfth Schedule, item 7). Cycles run from 6 months to 2 years, and in 4 states Flamekite found no periodic audit duty at all. Legislative Department, Ministry of Law and Justice

  • You may have read

    A self-certified approval means no one checks.

    Myth

    What the sources say

    Maharashtra's December 2025 order sends 10% of self-certified industrial approvals to a fire service inspection, and cancels non-compliant ones. MFS office order 2025

  • You may have read

    Telangana wants a fire audit every 6 months from every building.

    Myth

    What the sources say

    The 2020 circular splits buildings: some upload once a year in January, the higher-risk ones every January and July. TG fire circular 2020

Fire audit penalties: missed filings and false certificates

The law punishes both sides: the owner who does not file and the signatory who certifies falsely.

OffencePenaltyLaw
A licensed agency gives a Form A or Form B without actual compliance or maintenanceRigorous imprisonment of 6 months to 3 years and a fine of Rs 20,000 to Rs 50,000Maharashtra Act 2006, section 36(1)(f)(ii) MFS Act 2006 copy
A licensed agency's person knowingly furnishes a false Fire Safety CertificateImprisonment of 3 years extendable to 5, or a fine of Rs 20,000 extendable to Rs 5 lakh, or bothWest Bengal Fire Services Act, section 11K Indian Kanoonnews report
A Delhi Fire Safety Auditor's unsatisfactory certification, after notice (from 20 May 2027)Rs 2 lakh at L-1, Rs 5 lakh at L-2, Rs 10 lakh at L-3; blacklisting on a second defaultDelhi Fire Service Rules, Seventh Schedule DFS
An audit agency issues a certificate fraudulently (Act not yet in force)Fine up to Rs 1 lakh; up to 1 year in jail if a fire it caused leads to grievous hurt or deathTamil Nadu Act 37 of 2025, section 32(8) Government of Tamil Nadu, Gazette Extraordinary No. 263, 6 June 2025
A Gujarat Form B-15 filed late100% of the renewal fee for each 90-day block of delayGujarat Regulations 2023, Table 3 Gujarat Fire Safety Compliance Portal
Form-S not filed by 30 June, a second timeShow-cause notice on cancelling the fire NOCMadhya Pradesh Bhumi Vikas Rules, rule 87(5) MP Town Planning
A multistorey building fails to provide the measures a Bihar audit requiresA collective fine of double the provisional NOC fee on owners and occupantsBihar Fire Service Rules 2021, rule 22(j) Bihar Rules 2021
A Puducherry licensed agency gives an audit certificate without real complianceLicence suspended or cancelled after a show-cause noticeG.O.Ms.No.61, Annexure I Puducherry G.O. 61

Maharashtra's section 36(1) punishment cannot fall below 3 months and Rs 10,000 without special reasons recorded in the judgement. The full Form B penalties are on the Form B page; auditors' licence sanctions are on the third-party fire audit page.

Fire audit drives after fires, December 2025 to July 2026

From news reports, not yet an official source.

Drives ordered after fires, reported in the press and in a district press release; none is a notified rule, and each lasted weeks, not years.

  • After the Goa nightclub fire, Haryana orders fire safety audits of nightclubs, bars, pubs and crowded venues within 7 days. The Tribunenews report

  • The Deputy Commissioner of East Khasi Hills, Meghalaya, orders comprehensive fire safety audits across all establishments after rising fires. DC East Khasi Hills

  • Odisha reports a statewide audit of over 2,215 hospitals and clinics the year before and a hospital fire safety budget raised to Rs 400 crore, after the SCB Cuttack fire. Kalinga TVnews report

  • Delhi's Chief Minister orders a special fire safety audit of hotels, commercial establishments and public buildings after the Malviya Nagar fire. Deccan Chroniclenews report

  • Thane's Municipal Commissioner announces a citywide fire audit and 601 fire service recruitments after a fatal fire. Free Press Journalnews report

  • Bokaro's administration orders a safety audit of commercial and residential buildings across the city. Legal Suvidhanews report

  • Patna City: more than 200 establishments audited in 10 days after the 28 June warehouse fire; notices give 7 to 15 days to add tanks, pipelines and extinguishers. Patna Pressnews report

Fire audit portals where owners file, state by state

Bihar, Chhattisgarh and Telangana run a named fire audit service on their fire portals, and Maharashtra lists its 2 auditor lists online. These are the addresses.

Fire audit cases: a hospital, a tower, a society, a factory and a Bhopal block

Five buildings, each under a different state's audit rule.

  1. Case 1

    A 120-bed hospital in Hyderabad, 18 m

    Institutional, above 15 m, holding an occupancy NOC.

    What applies A third-party fire safety auditor certifies the 13 measures and the owner uploads the certificate every January and July. TG fire circular 2020

  2. Case 2

    An 80 m residential tower in Navi Mumbai

    Above 70 m, so a section 45 building.

    What applies Form B from its licensed agency every January and July, and a Fire and Life Safety Audit on Form V every 2 years from a separately licensed auditor. Amendment Act 2023

  3. Case 3

    A 14 m apartment society in Dehradun

    Flats on 5 floors, NOC valid 5 years.

    What applies No third-party audit cycle; the society uploads a self-declaration or Self Audit Report every 6 months. Uttarakhand Home notification

  4. Case 4

    An 18 m factory building in Cuttack

    Non-residential, above 15 m.

    What applies Audited every January and July by an auditor with the rule 9(15)(a) qualification; with the uploads kept up, renewal needs no fresh application or inspection. Odisha Home Dept

  5. Case 5

    A Bhopal building under NBC clause 4.10.1

    Holding a 3-year Fire Safety Certificate.

    What applies Form-S by 30 June each financial year from a UADD-licensed Fire Engineer; a second missed year brings a show-cause notice on cancelling the NOC. MP Town Planning

Questions about fire audits

What is a fire audit?

An inspection of a building's whole fire safety, its systems, exits, hazards, records and staff readiness, by someone the state recognises, who lists the fixes and signs a certificate in the state's form. In most states that is a licensed or empanelled auditor independent of the owner.

Fire audit kya hota hai?

Fire audit ek building ki poori fire safety ki jaanch hai: pumps, alarms, sprinklers, exits, wiring aur staff ki taiyari. A licensed or empanelled auditor does it and signs a certificate, such as Form V in Maharashtra or Forms IV and IV(B) in Odisha.

Is a fire audit mandatory in India?

It depends on the state. It is compulsory for Maharashtra's section 45 buildings every 2 years, yearly in Madhya Pradesh for NBC clause 4.10.1 buildings, every January and July in Chhattisgarh and Odisha, and yearly or six-monthly in Telangana. No national law sets one cycle for every building.

How often is a fire audit required?

From every 6 months to every 2 years: January and July in Chhattisgarh, Odisha and for Telangana's hospitals, malls and tall buildings; yearly in Madhya Pradesh and for Telangana's mid-rise buildings; every 2 years in Maharashtra's section 45 buildings.

What is the difference between a fire audit and a fire NOC?

The fire service issues the NOC after inspecting a building before occupation; a licensed auditor carries out the audit afterwards, on a cycle, to show the systems still work and to find new hazards. Many states need both.

Is Form B a fire audit?

No. Maharashtra's Form B is the maintenance agency's January and July certificate that the systems were kept in good repair. The section 45A fire audit is a separate check by a separately licensed Fire and Life Safety Auditor, every 2 years.

Who can do a fire audit?

Only the signatory your state names: a licensed Fire and Life Safety Auditor in Maharashtra, a Grade A to D Third Party Auditor in Chhattisgarh, an empanelled auditor in Odisha and Telangana, an enrolled Fire Safety Officer for Gujarat's Form B-15, or the fire service itself in Bihar.

How much does a fire audit cost?

Bihar's fire service charges Rs 1 to Rs 5 per m² of all floors. Delhi has set auditors' charges of Rs 10,000 to Rs 5,00,000 per certification from 20 May 2027. Elsewhere the fee is agreed with the auditor and no official rate is published.

Does a housing society need a fire audit?

Where the state's rule covers its building, yes: a Maharashtra society above 70 m needs the 2-yearly audit, a Telangana society above 30 m uploads a third-party certificate every January (twice a year at 45 m), and an Uttarakhand society files a Self Audit Report every 6 months.

Keep reading

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Director General, Telangana State Disaster Response and Fire Services: Circular Memorandum Rc.No.6402/MSB/2019, 28 January 2020: conducting of fire audit in all high-rise and non-high-rise buildings; third-party certificate uploaded every January, or every January and July, by height and use, with the 13-point certificate format (read from the page images) (opens in a new tab)checked 25 October 2026
  2. Fire Adviser, Government of Maharashtra (Maharashtra Fire Services): Circular No. MFS/2015/10/1462, 16 September 2015, "Regarding Fire Audit": the licensed agency's Form B against a Fire Risk Audit, advised at least once a year for high-rise and other special buildings (read from the page images) (opens in a new tab)checked 25 October 2026
  3. Government of Telangana, Home (Services.IV) Department: G.O.Ms.No.15, 20 January 2026: empanelment of Third-Party Fire and Life Safety Auditors and Fire and Life Safety System Integrators (opens in a new tab)checked 25 October 2026
  4. Government of Maharashtra (copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023 (Mah. Act No. XXIV of 2023), first published 11 May 2023 (opens in a new tab)checked 25 October 2026
  5. Government of Uttarakhand, Home Section-4 (copy hosted by Uttarakhand Fire and Emergency Services): Notification No. 342/XX-3/2021-2(39)/2006 of November 2021 under section 26 of the 2016 Act: 5 year validity for residential buildings except hotels, 3 years for other buildings, six-monthly self-declaration, fresh certificate on change of use (opens in a new tab)checked 24 October 2026
  6. Government of Bihar, Home Department notification (English copy hosted by Bihar Fire Service): Bihar Fire Service Rules, 2021: rules 14 to 27, 33, 34 and 38, Schedules C (fees), D (online NOC), E (pandals) and H (existing buildings) (opens in a new tab)checked 25 October 2026
Show all 70 sourcesShow fewer
  1. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
  2. Legislative Department, Ministry of Law and Justice: The Constitution of India (Twelfth Schedule, item 7: Fire services; Article 243W) (opens in a new tab)checked 24 October 2026
  3. Directorate General Fire Services, Civil Defence and Home Guards (MHA): Revised Model Fire and Emergency Service Bill, 2019 (opens in a new tab)checked 26 October 2026
  4. Directorate of Town and Country Planning, Madhya Pradesh: Madhya Pradesh Bhumi Vikas Rules, 2012, English text updated up to 6 March 2025: rules 2(38), 12(2), 26, 42 and 87 (fire audit amendment of 4 September 2020) (opens in a new tab)checked 25 October 2026
  5. Home Department, Government of Odisha: Odisha Fire Prevention and Fire Safety (Second Amendment) Rules, 2025, notification PT1-HOME-FS-RULE-0001-2024, 4 November 2025: January and July audit certificates, renewal without fresh application for audited premises (opens in a new tab)checked 25 October 2026
  6. Bihar Fire Service: Fire NOC and Audit portal: Schedule C, prescribed rate of fee for NOC, renewal, fire audit and fire consultation (opens in a new tab)checked 25 October 2026
  7. Delhi Gazette Extraordinary, Part IV (Home Department, Govt of NCT of Delhi): Notification F. No. 6/DFS/MS/HQ/MISC/2026/01/631, 16 October 2026 (No. 314, SG-DL-E-17102026-277257): commencement of Rules 34 to 38 and the First and Seventh Schedules extended to 20/05/2027 (opens in a new tab)checked 25 October 2026
  8. Urban Development Department, Government of Maharashtra (copy hosted by MFS): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Rules, 2025, Notification No. MFS-2023/C.R.370/UD-14, 12 June 2025 (opens in a new tab)checked 25 October 2026
  9. Gujarat Government Gazette Extraordinary No. 128, Part IV-B, 24 June 2024: Gujarat Fire Prevention and Life Safety Measures (Amendment) Rules, 2024, notification GH/V/80 of 2024: substituted rule 25 and Form B-13.3 (opens in a new tab)checked 25 October 2026
  10. Government of Goa, Official Gazette Series II No. 14, 3 July 2025: Home Department notification 3/14/2024-HD(G)/1652, 23 June 2025: 5-year fire NOC validity (opens in a new tab)checked 25 October 2026
  11. Telangana State Disaster Response and Fire Services Department: Fire Audit user manual (Online TS-Fire application): registration, the Fire Audit Application form, plan uploads in PDF under 3 MB and online payment through the Telangana cyber treasury (opens in a new tab)checked 25 October 2026
  12. Government of Sikkim, Sikkim Government Gazette Extraordinary No. 466, 17 December 2025: The Sikkim Fire and Emergency Services Rules, 2025: Home Department notification No. 99/Home/2025, 17 December 2025, under section 63 of Act 4 of 2023, with Schedules I to V and Forms A1 to A20 (opens in a new tab)checked 25 October 2026
  13. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 25 October 2026
  14. Delhi Fire Service (copy of Delhi Gazette Extraordinary, Part IV): Delhi Fire Service (Amendment) Rules, 2025, notification F.No. DFS/HQ/Misc/2025/01(E-259159)/237, gazetted 26 May 2026 (opens in a new tab)checked 25 October 2026
  15. Uttar Pradesh Gazette Extraordinary, 18 January 2024 (copy hosted by UP Fire and Emergency Services): Uttar Pradesh Fire and Emergency Services Rules, 2024, Notification No. 181/VI-Pu-8-2024-801(1)-2023: rules 40 to 56, 65, 66 and 72, Schedules VI and VII, Forms A-4, A-8 and A-11 to A-13 (opens in a new tab)checked 25 October 2026
  16. Home (Police) Department, Government of Meghalaya: Order No. HPL/31/2002/138 of 9 August 2016 under section 10(k): mock drills and fire safety audits in all types of establishments (opens in a new tab)checked 24 October 2026
  17. Supreme Court of India: SMW(C) 7/2020, In Re: Proper Treatment of COVID-19 Patients, order of 19 July 2021 restating the directions of 18 December 2020 (opens in a new tab)checked 25 October 2026
  18. Home Department, Chhattisgarh (on the CG Fire NOC portal): Chhattisgarh Fire and Emergency Services (Amendment) Rules, 2025, notified 24 November 2025: Rules 37A and 37B, third-party auditor certificate every January and July (Hindi) (opens in a new tab)checked 25 October 2026
  19. Central Electricity Authority (Gazette of India Extraordinary, Part III Section 4, No. 231): CEA (Measures relating to Safety and Electric Supply) Amendment Regulations, 2026, F. No. CEA-PS-16/1/2021-CEI Division, gazetted 30 March 2026, in force 1 April 2027 (scanned copy) (opens in a new tab)checked 26 October 2026
  20. Home (F&ES) Department, Government of Tripura: Notification F.3-8(NOC)/Empanelment-Agency/TFES/2025 of 23 October 2025: expression of interest for empanelled fire inspection agencies, with licence terms and service charges (11 pages, signed scan) (opens in a new tab)checked 24 October 2026
  21. National Accreditation Board for Hospitals and Healthcare Providers (NABH): Revised Advisory for Minimum Essential Fire Safety Measures, 20 September 2022 (opens in a new tab)checked 25 October 2026
  22. Fire and Emergency Services, Meghalaya: Fire safety audits conducted, 2022 and 2023, by building class (356 entries) (opens in a new tab)checked 24 October 2026
  23. Directorate of Maharashtra Fire Services: List of Approved Licensed Agencies Valid Up to 03.07.2028 (847 numbered entries in the copy read) (opens in a new tab)checked 25 October 2026
  24. Directorate of Maharashtra Fire and Emergency Services: Office Order No. MFS-2025/1763, 10 December 2025: self-certified fire approval for low-hazard industries up to 2,000 m² and below 18 m, Form B in January and July where no renewal is due, and 10% of cases picked for inspection (read from the page images) (opens in a new tab)checked 25 October 2026
  25. Fire and Emergency Services and SDRF, Chhattisgarh: Necessary documents and related information for TPA applicants: grades A to D, solvency, bank guarantee, registration fee, risk types each grade may inspect (opens in a new tab)checked 25 October 2026
  26. Government of Tamil Nadu, Gazette Extraordinary No. 263, 6 June 2025: Tamil Nadu Fire and Rescue Services Act, 2025 (TN Act 37 of 2025) (opens in a new tab)checked 25 October 2026
  27. Government of Goa, Official Gazette Series I No. 14, 3 July 2025: Home Department notification 3/13/2024-HD(G)/1653, 23 June 2025: guidelines for licensed agencies that install, audit and certify fire protection and life safety installations (opens in a new tab)checked 25 October 2026
  28. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures Act, 2006, English gazette of 5 February 2007 (sections 3, 8, 36 to 38 read off the page images) (opens in a new tab)checked 25 October 2026
  29. Government of Puducherry, Home Department (copy hosted by the Fire Service Department): G.O.Ms.No.61, 10 September 2025: Fire Safety Audit and Issue of NOC, Third Party Fire Safety Audit, Categories A, B and C, renewal, temporary licences, and Annexures I to V on licensed agencies and the Category C protocol (opens in a new tab)checked 25 October 2026
  30. Deputy Commissioner and DDMA, East Khasi Hills: Press release DC EKH 73, 20 February 2026: comprehensive fire safety audits across all establishments; apply for a Fire Clearance Certificate or NOC (opens in a new tab)checked 24 October 2026
  31. Bihar Fire Service: Online Fire NOC and Audit Portal: home page (menus, State Fire Office contacts and helpline) (opens in a new tab)checked 24 October 2026
  32. Bihar Fire Service: Citizen User Manual, Fire Audit Application, version 1.0 (Hindi) (opens in a new tab)checked 24 October 2026
  33. Fire and Emergency Services and SDRF, Chhattisgarh: CG Fire NOC portal: New NOC, NOC Renewal, Fire Audit (with helplines) (opens in a new tab)checked 25 October 2026
  34. Telangana Fire, Disaster Response, Emergency and Civil Defence Department: Fire Audit module login (opens in a new tab)checked 25 October 2026
  35. Maharashtra Fire and Emergency Services: Fire auditor: Approved List of Maharashtra Fire and Life Safety Auditors and the Form W application (opens in a new tab)checked 25 October 2026
  36. AP State Disaster Response and Fire Services: Rc.No.5862/Genl/2023, 29 June 2026: empanelment of Third-party Fire Audit Agencies (Qualified Agency) for renewal of Fire NOC, with the application form (opens in a new tab)checked 24 October 2026
  37. Government of Arunachal Pradesh (PRS copy of AP Gazette Extraordinary No. 128, 11 May 2026): Arunachal Pradesh Fire and Emergency Services Act, 2026 (Act 12 of 2026) (opens in a new tab)checked 24 October 2026
  38. Home and Political Department, Government of Assam: Assam Fire and Emergency Services (Amendment) Rules, 2025, notification No. HMB.699902/23 signed 17 October 2025: rules 2(xa), 18, 18A to 18D and Form G (opens in a new tab)checked 24 October 2026
  39. Government of Haryana (PRS copy): Haryana Fire and Emergency Services Act, 2022 (Act 14 of 2022) (opens in a new tab)checked 25 October 2026
  40. Emerging Himachal single window: Fire NOC checklist and procedure (Form A) (opens in a new tab)checked 24 October 2026
  41. Local Self Government Department, Government of Kerala (Kerala Gazette Extraordinary No. 3808): Kerala Municipality Building (Amendment) Rules, 2025 (G.O.(P) No.53/2025/LSGD, S.R.O. No.1240/2025, 29 October 2025) and Kerala Panchayat Building (Amendment) Rules, 2025 (G.O.(P) No.54/2025/LSGD): rule 5(4) restated, rules 35 and 36 (opens in a new tab)checked 25 October 2026
  42. Government of Manipur (PRS copy): Manipur Fire and Emergency Service Act, 2026 (Act 9 of 2026) (opens in a new tab)checked 24 October 2026
  43. Home Department, Government of Mizoram (copy on the Mizoram Fire and Emergency Services site): Notification No. B-20011/2/2026-HM(F&ES), 20 August 2026: Mizoram Fire and Emergency Services (Superintendence and Control of the Fire Force and Fire Safety and Prevention) (Amendment) Rules, 2026, substituting Rule 57 and inserting Rules 57(A) and 57(B) (opens in a new tab)checked 25 October 2026
  44. Directorate of Fire and Emergency Services, Nagaland: Nagaland Fire and Emergency Services Act (Act No. 5 of 2023), Nagaland Gazette, 31 August 2023 (opens in a new tab)checked 24 October 2026
  45. Punjab Government Gazette (Extraordinary), copy hosted by PRS Legislative Research: Punjab Govt. Gazette (Extra), 26 November 2024: the Punjab Fire and Emergency Service Act, 2024 (Punjab Act No. 12 of 2024), Notification No. 12-Leg./2024 of 27 October 2024 (opens in a new tab)checked 25 October 2026
  46. Local Self Government Department, Rajasthan: Fire service: Fire NOC registration and certificate verification (nodal officer and helpline) (opens in a new tab)checked 24 October 2026
  47. Directorate of Fire and Emergency Services, Tripura: Tripura Fire Safety Rules, 2026 (Tripura Gazette, 2 June 2026) (opens in a new tab)checked 24 October 2026
  48. WBXPress (copy of notification 251/DS/FS/O/C-1/F1A-3/96 (Part II), 17 June 2003): West Bengal Fire Services (Fire Prevention and Fire Safety) Rules, 2003 (opens in a new tab)checked 24 October 2026
  49. Gazette of India Extraordinary, Part II Section 1, No. 19, 25 May 2026: Andaman and Nicobar Islands Fire and Emergency Service Regulation, 2026 (No. 5 of 2026) (opens in a new tab)checked 24 October 2026
  50. Gazette of India, Ministry of Home Affairs (copy hosted by TaxHeal): S.O. 2264(E) of 6 May 2026: the Haryana Fire and Emergency Services Act, 2022 extended to the Union territory of Chandigarh, with modifications (opens in a new tab)checked 25 October 2026
  51. Gazette of India Extraordinary (CG-DL-E-02062026-273069): Dadra and Nagar Haveli and Daman and Diu Fire and Emergency Service Regulation, 2026 (No. 6 of 2026) (opens in a new tab)checked 24 October 2026
  52. Housing and Urban Development Department, UT Ladakh: Draft Ladakh Building Bye Laws, 2025, published for objections under section 219 of the J&K Municipal Act 2000 (listed 17 October 2025; clause 8.12 Fire Clearance Criteria read from the page images) (opens in a new tab)checked 24 October 2026
  53. Lakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026: Lakshadweep Fire and Emergency Services Rules, 2026 (Rule 12: 5-year fire safety certificate) (opens in a new tab)checked 24 October 2026
  54. Kashmir Reader: Fire Services records significant safety gains in 2025: 6,039 fire calls, 3,728 fire safety audits (1 January 2026) (opens in a new tab)News report · checked 24 October 2026
  55. Patna Press, 5 June 2026: Patna fire department warns 239 hotels and hospitals of sealing after June 15 (opens in a new tab)News report · checked 24 October 2026
  56. Indian Kanoon (legal database copy of the 1996 text): West Bengal Fire Services Act, 1950: sections 2(ha), 2(hb), 11C to 11K and 38B (copy predates the 2018 and 2022 amendments) (opens in a new tab)News report · checked 24 October 2026
  57. The Tribune: Haryana govt orders fire safety audits of nightclubs, bars (11 December 2025) (opens in a new tab)News report · checked 24 October 2026
  58. Kalinga TV, 18 March 2026: Odisha hikes hospital fire safety budget to Rs 400 crore amid state-wide audit (opens in a new tab)News report · checked 24 October 2026
  59. Deccan Chronicle: Delhi orders fire safety audit after guesthouse tragedy (June 2026) (opens in a new tab)News report · checked 24 October 2026
  60. Free Press Journal: Thane ramps up fire safety: Commissioner Saurabh Rao announces 601 recruitments and a citywide audit after fatal fire (24 June 2026) (opens in a new tab)News report · checked 24 October 2026
  61. Legal Suvidha, 26 June 2026 (summary of a Times of India report): RMC issues 7-day deadline for fire NOC, orders safety audit in Bokaro (opens in a new tab)News report · checked 24 October 2026
  62. Patna Press, 24 July 2026: Fire audits conducted at over 200 locations in Patna City; notices issued over safety lapses (opens in a new tab)News report · checked 24 October 2026
  63. LiveLaw, 19 August 2023: Jharkhand High Court issues directives after the Dhanbad high-rise fire: W.P.(PIL) No. 497 of 2023 (opens in a new tab)News report · checked 24 October 2026
  64. Citizen Matters: New fire safety norms for city high rises (6 September 2011): the 7 July 2011 Bengaluru notification (opens in a new tab)News report · checked 24 October 2026