Fire NOC for a hospital: state lines, fire codes, audits and fees
Updated By Flamekite Editorial DeskFacts checked against official sources on
Quick answer
A hospital is an institutional building in the fire codes: Subdivision C-1, hospitals and sanatoria, in NBC 2016 and C-I in NBCS 2026. Whether it needs a fire NOC depends on the state: every hospital in Assam, Uttar Pradesh, Puducherry and Goa, almost every one in Rajasthan, from 9 m in Delhi, Haryana and Bihar, above 15 m in Telangana and from 21 m in Karnataka.
National rules sit on top. The Supreme Court ordered monthly fire audits of COVID hospitals on 18 December 2020; the Health Ministry and NDMA asked hospitals on 23 March 2024 to renew the NOC every year as state rules allow; and NABH accepts a 1-year third-party certificate only for accreditation, never in place of the NOC.
- Supreme Court, COVID hospitals
- Every month
- Fire audit by a district committee, 18 December 2020
- National rules
Free, on WhatsApp. Or set a renewal reminder
Fire NOC for a hospital at a glance: 10 facts
| What | The rule | Source |
|---|---|---|
| Occupancy in NBC 2016 | Group C Institutional, Subdivision C-1 Hospitals and sanatoria: hospitals, infirmaries, sanatoria and nursing homes for people who cannot save themselves | BIS, NBC 2016 Part 4 |
| Occupancy in NBCS 2026 | C-I Hospitals and sanatoria; the 2026 standard is voluntary, and only Assam had written it into its fire law by 24 October 2026 | Assam Act XIII of 2026 |
| Outpatient clinics | Business, Subdivision E-2, in NBC 2016, not institutional, when no patient stays overnight | BIS, NBC 2016 Part 4 |
| States that cover every hospital | Assam, Uttar Pradesh, Puducherry and Goa at any size; Rajasthan all but a ground plus 1 building without beds on a plot up to 1,000 m² | Rajasthan UDH |
| Most common low line | 9 m: Delhi (or 3 storeys), Haryana, Chandigarh, Bihar, Himachal, Manipur, Nagaland and Arunachal Pradesh | Government of Haryana |
| Bed-count lines | Chhattisgarh and Odisha bring in any hospital with more than 30 beds or a critical care unit | Home Department, Chhattisgarh |
| Supreme Court, 18 December 2020 | A nodal officer for each COVID hospital, a district fire audit every month, and an immediate NOC application | Supreme Court of India |
| Health Ministry and NDMA, 23 March 2024 | 13 instructions, among them a yearly NOC renewal as per state rules and electrical load audits twice a year | Ministry of Health and Family Welfare and NDMA |
| NABH | A valid NOC, or proof of application with correspondence every 3 months, or a third-party certificate valid at most 1 year | National Accreditation Board for Hospitals and Healthcare Providers |
| National checklist | The DGFS advisory checklist for hospitals and nursing homes: 48 general items, then Categories A to D up to 45 m | DGFS hospital checklist |
Hospital fire NOC lines in 32 states and UTs: height, beds or every building
| Option | When a hospital is caught | Term or periodic duty | Instrument | Source |
|---|---|---|---|---|
| Assam | Every hospital, nursing home and sanatorium, whatever the height or floor area; all are high risk in Schedule I | Certificate valid until cancelled under the 2025 Act | Act LIII of 2025, s.20(1) and Schedule I | Assam Act LIII of 2025 |
| Uttar Pradesh | Every hospital: institutional buildings are special buildings at any height; below 9 m on a plot under 1,000 m² no agency certificate is needed | 1 year (Rule 44) | Act 16 of 2022; Rules 2024, rules 42 and 44 | UP Rules 2024 |
| Puducherry | Every hospital is Category A; clinical establishments up to G+2 are also listed in Category B | A fresh NOC every year, with 2 agency audit certificates and inspections twice a year | G.O.Ms.No.61 (Home), 10 September 2025 | Puducherry G.O. 61 |
| Rajasthan | Every medical building except a ground plus 1 building without beds on a plot up to 1,000 m² | 5, 3 or 1 year by height and plot (Table 3); a yearly inspection and mock drill | UDH and LSG order of 14 September 2023, Tables 1 and 3 | Rajasthan UDH |
| Goa | Every educational and institutional building, any size (service 97) | Rs 10 per m²; the Deputy Director (Fire) decides in 15 days | Notification of 3 November 2022 under the Goa Right to Services Act | Goa Gazette 2022 |
| Andhra Pradesh | All institutional buildings, of any size, under clause (b) | The old 500 m² plot or 6 m floor line is not in the 2026 text | Fire Service Act 1999, s.13(1) as amended in 2026 | Andhra Pradesh Legislative Assembly |
| Delhi | Institutional buildings over 9 m or of 3 storeys or more | 3 years for non-residential buildings until 20 May 2027 | DFS Rules 2010, Rule 27 as amended | DFS |
| Haryana | Every institutional building of 9 m or more, whatever its floor area | Scheme valid 2 years, certificate 3 years | Act 14 of 2022, s.18(2)(b) | Government of Haryana |
| Chandigarh | Hospitals of 9 m or more as special buildings | 5 years since 6 May 2026 (S.O. 2264(E)); Rs 14 per m², at least Rs 6,615 | MC Office Order 23 of 10 February 2025, under the Haryana Act as extended | MCC Office Order 23 |
| Bihar | Institutional buildings from 9 m, or any floor over 500 m² | Hospitals come first in the fire service's audits (rule 22) | Fire Service Rules 2021, rule 15(a) | Bihar Rules 2021 |
| Chhattisgarh | Above 9 m or G+2, more than 30 beds, or any critical care unit | 2 years under 15 m, 1 year above 15 m (order of 16 October 2025) | Section 14(1) notification of 29 November 2022 | Home Department, Chhattisgarh |
| Odisha | 12 m or more, more than 3 floors, more than 30 beds or any critical care unit; smaller clinics are self-regulatory | 2 years | Rules 2017 as amended in 2019; Order 50908 of 19 November 2019 | Order 50908 of 2019 |
| Manipur | Hospital buildings over 9 m or ground plus 2 | Apply on EoDB Manipur to the Director, Manipur Fire Service | Act of 2026, s.21(5) | Government of Manipur |
| Nagaland | Hospital buildings over 9 m or ground plus 2 | A Fire Safety Officer on site at 15 m and above (s.26) | Act, ss.21(1) and 24(3) | Directorate of Fire and Emergency Services, Nagaland |
| Himachal Pradesh | Institutional buildings over 9 m or ground plus 2 upper storeys (class 6) | Building plans above 15 m need the NOC (s.15-A) | Notification of 23 July 2019 under s.9 | HP Home notification |
| Arunachal Pradesh | Hospitals of 9 m and above (bye-law 11.1(b)(3)) | Renewed every year (bye-law 11.3) | Building Bye-Laws 2019, applied by Act 12 of 2026 | AP Building Bye-Laws 2019 |
| Tripura | Institutional buildings above 10 m or above 200 m² | Up to both limits, outside the full route | Fire Safety Rules 2026 | Directorate of Fire and Emergency Services, Tripura |
| Uttarakhand | Plan permission for hospitals above 12 m and above 500 m² (both) | 3 years; a fire safety officer above 250 beds | Act of 2016 as amended in 2022, s.18; notification 342 of 2021 | Uttarakhand Home notification |
| Telangana | Hospitals, sanatoria and nursing homes above 15 m (high risk) | Audit certificate every January and July above 15 m | Circular of 5 March 2016; audit circular of 28 January 2020 | TSDRFS circular 2016 |
| Karnataka | 21 m or more under the Act; Seva Sindhu still lists above 15 m | Rs 60 per m² for non-residential, at least Rs 5,00,000 | Fire Force Act, s.13(3) as amended in 2023 | Government of Karnataka |
| Kerala | Group C buildings over 1,000 m² built-up or over 15 m | 300 to 1,000 m² up to 15 m: an Appendix L self-declaration | Municipality Building Rules, rule 5(4) | KMBR amendment 2025 |
| Tamil Nadu | TNFRS NOC: the District Officer up to 18.3 m, the Director above | Hospital rules: setbacks of 6 m below 18.3 m and 7 m up to 30 m; mock drills every 6 months | Fire Service Act 1985; Building Rules 2019, Annexure IX | TNCDBR 2019 |
| Gujarat | Hospitals and nursing homes are in Table 1 at every height: under 15 m by plot of 1,000 m² and floors with beds, then 15 to 24 m and 24 to 45 m | A Fire Safety Executive on site for institutional buildings above 15 m | Fire Regulations 2023, Table 1 | Gujarat Fire Safety Compliance Portal |
| Maharashtra | Section 3 duties at every height; Flamekite has not proof-read Schedule-I's hospital rows | Form B every January and July; above 30 m a fire officer and a Fire and Life Safety Audit every 2 years | Act of 2006, ss.3, 45 and 45A as amended in 2023 | Amendment Act 2023 |
| West Bengal | One of the 19 notified high-risk occupancies, and any building of 14.5 m | Hospitals under 15 m with up to 50 beds go to the Zonal committees since 9 December 2025 | Act 1950, s.11C; notification 279 of 2003 | West Bengal Fire and Emergency Services |
| Jharkhand | 15.0 m and above | A Fire Safety Officer above 100 beds (s.29(g)) | Act 9 of 2024 | Government of Jharkhand |
| Meghalaya | C-1 hospitals, sanatoria and nursing homes have their own fee row | A qualified Fire Officer on the premises at 15 m and above | Notification HPL.254/2013/65 of 9 May 2018 | Gazette 24 May 2018 |
| Sikkim | All covered; below 15 m and on a plot under 500 m² no third-party agency certificate | 1 year for hospitals (rule 30) | Fire and Emergency Services Rules 2025, rules 28 and 30 | Sikkim F&ES Rules 2025 |
| Jammu and Kashmir | Hospitals (C3) and hospitals of over 20 beds (PSP3) are in the fire NOC list | Sanctioned in 2 stages above 15 m | Unified Building Bye-Laws 2021, clause 2.18(2) | J&K H&UDD |
| Lakshadweep | Institutional buildings over 500 m² | A Fire Safety Officer at 100 hospital beds | Rules 2026, Schedule II | Lakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026 |
| Andaman and Nicobar Islands | Hospitals, sanatoria and nursing homes are among the 9 Fire Clearance Certificate classes | 1 year today | Fire Service portal; Regulation 5 of 2026 not yet in force | A&N Fire Service portal |
| Mizoram | Public buildings; the Director decides the line | A hospital of 15 m to 24 m: wet riser, sprinklers and detection | Fire Service Amendment Rules 2026 | Mizoram Home Dept |
Getting a hospital's fire NOC in 8 steps
Record the building as C-1, not business
A building where patients stay overnight is institutional, C-1 in NBC 2016 and C-I in NBCS 2026. Only a day-care clinic without beds is business. The class decides the line, the systems and the term.
Measure height, plot area, floors and beds
Test the hospital against your state's row above: 9 m in Delhi, Haryana and Bihar, 30 beds or an ICU in Chhattisgarh and Odisha, plot area in Rajasthan's Table 3, every hospital in Assam and Uttar Pradesh.
Design to the hospital rules, not only the general table
Plan horizontal evacuation into a neighbouring compartment, 2.4 m patient corridors and 2.0 m exits, ICUs and theatres behind 120-minute walls, and a sprinkler over oxygen and medical gas stores.
File the plan-stage application where your state has one
Upload the fire drawings for the provisional or plan approval. In Telangana a high-rise hospital also engages a third-party reviewer of the fire and life safety design under rule 24.0.
Install, test and get the agency's certificate
Extinguishers, hose reels, risers, sprinklers, detection and pumps as the code and the approval list; the licensed agency certifies them where the state requires it.
Pass the fire officer's inspection and display the NOC
The officer checks exits, compartments, the oxygen store, the electrical panel and every system. Keep the NOC on display: the DGFS checklist asks for it.
Run the periodic duties
Form B every January and July in Maharashtra, the audit upload every January and July in Telangana above 15 m, the yearly inspection and mock drill in Rajasthan, and drills at least twice a year under the 2024 advisory.
Diary the renewal by your state's term
1 year in Uttar Pradesh, Puducherry, Sikkim and Arunachal; 5, 3 or 1 in Rajasthan; 2 or 1 in Chhattisgarh. The 2024 advisory asks for a yearly renewal as state rules allow.
Hospital, nursing home and sanatorium: the occupancy words fire officers use
The class an officer writes on the file decides the line and the table. These 8 terms come from the 2 national codes, NDMA and NABH.
- Group C Institutional (NBC 2016, 3.1.4)
- Buildings used for treating or caring for people with illness, disease or infirmity, for infants, convalescents or the aged, and for custody; they ordinarily provide sleeping accommodation. BIS, NBC 2016 Part 4
- C-1 Hospitals and sanatoria
- A building or group under single management housing people with physical limitations from health or age who cannot save themselves: hospitals, infirmaries, sanatoria and nursing homes. BIS, NBC 2016 Part 4
- C-I (NBCS 2026)
- The same subdivision in the 2026 standard, with its own Table 7C of firefighting installations and clause 6.3 on hospital exits. BIS, SP 7:2026
- E-2 outpatient clinic
- NBC 2016 files outpatient clinics, laboratories and research establishments as business, Subdivision E-2, not institutional. BIS, NBC 2016 Part 4
- Progressive horizontal evacuation
- Moving patients through a fire-resisting wall into the next compartment on the same floor, which NBCS 2026 calls of paramount consideration for hospitals. BIS, SP 7:2026
- Comparative and ultimate safety
- NDMA's 2 levels for hospitals: protection in place against heat and smoke, and complete removal of occupants to an assembly point outside. NDMA
- Smoke compartment (Telangana)
- On every storey where patients sleep or are treated, or with 50 or more occupants: compartments of at most 500 m² in 2-hour construction. G.O.Ms.No.162
- Third-party inspection certificate (NABH)
- A fire and life safety certificate from a NABCB-accredited Type A inspection body, valid at most 1 year, accepted for accreditation only. National Accreditation Board for Hospitals and Healthcare Providers
NABH on hospital fire NOC: a third-party certificate counts for accreditation only
Hospitals often read NABH's 2022 advisory as a way round the fire NOC. Its own words close that door.
Word for word
Such Fire & Life Safety Inspection Certificates shall be accepted in lieu of statutory Fire NOC, only for consideration for the purpose of NABH accreditation. This does not absolve the hospitals/health care providers from complying to Fire NOC requirements/any other extant applicable statutes. It shall be sole responsibility of hospitals/health care providers to obtain Fire NOC, as applicable.
Without a NOC, NABH asks for proof of the application with acknowledged correspondence with the fire department at least once in 3 months, or that third-party certificate, valid for a maximum of 1 year, plus an undertaking from the head of the hospital. Its 10 accreditation requirements add a central fire alarm at a place staffed 24 hours, detectors on all floors, an exit plan per floor, emergency lighting and drill records. NABH's notice of 2 January 2026 made January its Fire Safety Month.
Fire systems a hospital needs by height: NBC 2016 and NBCS 2026
NABH's table, adapted from NBC 2016, and NBCS 2026 Table 7C set the 4 big systems for a hospital. R is required, NR not required.
| Wet riser | Automatic sprinkler | Automatic detection and alarm | Manual alarm or voice evacuation | |
|---|---|---|---|---|
| NBC 2016: under 15 m, plot up to 1,000 m², up to G+1 National Accreditation Board for Hospitals and Healthcare Providers | NR | R | NR | Manual alarm R |
| NBC 2016: under 15 m, plot up to 1,000 m², G+2 National Accreditation Board for Hospitals and Healthcare Providers | R | R | R | Manual alarm R |
| NBC 2016: under 15 m, plot over 1,000 m² National Accreditation Board for Hospitals and Healthcare Providers | R | R | R | Manual alarm R |
| NBC 2016: 15 m to 24 m, and above 24 m to 45 m National Accreditation Board for Hospitals and Healthcare Providers | R | R | R | Manual alarm R |
| NBCS 2026: up to 500 m² and up to 24 m BIS, SP 7:2026 | Self-certification by a certified, state-approved professional | Same | Same | Same |
| NBCS 2026 CL-3: 501 to 1,000 m², up to 45 m BIS, SP 7:2026 | R, with a yard hydrant | R | R | Voice evacuation NR |
| NBCS 2026 CL-4: 1,001 m² and above, up to 45 m BIS, SP 7:2026 | R, with a yard hydrant | R | R | Voice evacuation R |
| NBCS 2026 CL-5: above 45 m to 60 m BIS, SP 7:2026 | R, with a yard hydrant | R | R | Voice evacuation R |
Every row needs extinguishers and hose reels. NBCS 2026 Note 1 sprinklers any basement, oxygen or medical gas store, laundry, linen or waste room and transformer room to the CL-3 level whatever the hospital's size; above 60 m it asks for multi-level pumping with pumps of no more than 12 bar. NABH's key prints "NR= Required", a slip for not required. Delhi's nursing-home sheet adds a 75,000 to 1,50,000 litre underground tank, a 10,000 litre terrace tank and 1,620 l/min pumps below 15 m.
Hospital exits and evacuation under NBCS 2026: 12 checks
Clause 6.3 of NBCS 2026 writes hospital-only rules on top of the general exit tables. A fire officer or auditor can test each of these 12 on a walk-round.
- Corridors, aisles and ramps used to move patients are at least 2.4 m wide throughout; others at least 1.5 m. BIS, SP 7:2026
- Every exit from a hospital or infirmary section is at least 2.0 m wide. BIS, SP 7:2026
- Room doors: 1.25 m for 1 or 2 beds, 1.50 m for 3 to 5 beds, 2.0 m for larger wards, ICUs, recovery and delivery rooms (1.5 m where there are 2 doors). BIS, SP 7:2026
- Operation theatres, delivery rooms, ICUs and recovery rooms are fire and smoke separated from neighbouring areas by at least 120 minutes. BIS, SP 7:2026
- Each compartment can take the next compartment's patients too, at 3.5 m² for each bed-ridden patient and 0.6 m² for others. BIS, SP 7:2026
- Compartment doors close by themselves on alarm, with electromagnetic hold-open; corridor doors are double-leaf and at least 2.0 m. BIS, SP 7:2026
- Common path of travel up to 30 m, and no dead-end corridor longer than 6 m. BIS, SP 7:2026
- Patients who cannot save themselves are housed within 45 m where possible; above it, refuge terraces with medical gases on alternate floors. BIS, SP 7:2026
- Any sleeping room or suite over 100 m² has 2 doorways to the exit corridor. BIS, SP 7:2026
- Laboratories stay within 100 m², or get 120-minute separation; basements hold no flammables or flammable-chemical labs. BIS, SP 7:2026
- A stretcher lift in each lift bank doubles as the fireman's lift. BIS, SP 7:2026
- No combustible material is stored beyond what normal use needs. BIS, SP 7:2026
The national layer for hospitals, from the Health Ministry to NABH: 8 instruments
Fire is a state subject, but 8 national instruments speak to hospitals. Only the Supreme Court's directions bind; the rest advise or set accreditation terms.
1. NDMA Hospital Safety guidelines, February 2016
Chapter 6 sets comparative and ultimate safety levels and asks every hospital for an ICU evacuation drill and a ward evacuation drill once a year, judged by third-party evaluators. NDMA
2. MoHFW Fire and Life Safety guidelines, 28 September 2020
Framed for government hospitals and sent to all states, as the Ministry told the Lok Sabha on 13 December 2024. Flamekite did not find the text. Lok Sabha answer
3. Supreme Court, 18 December 2020
Every month a district committee fire-audits each COVID hospital; each has a nodal officer; any without a NOC applies at once. Directions after the Rajkot COVID hospital fire, restated on 19 July 2021. Supreme Court of India
4. District committees under Collectors
The Health Ministry urged states to form committees of health, fire and public works officers, headed by District Collectors, to inspect health facilities and act against defaulters. Lok Sabha answer
5. NABH advisory, 20 September 2022
A valid NOC, or 3-monthly correspondence on the application, or a 1-year third-party certificate, for accreditation only. National Accreditation Board for Hospitals and Healthcare Providers
6. MoHFW and NDMA advisory, 23 March 2024
13 instructions to states for accredited hospitals: monthly extinguisher checks, quarterly alarm and hydrant tests, electrical load audits twice a year, sprinklers in ICUs and theatres, yearly NOC renewal as state rules allow. Ministry of Health and Family Welfare and NDMA
7. DGFS hospital audit checklist (F. No. VI-14022/09/2024-DGCD (F))
48 general items, then Categories A to D by height and plot, up to 45 m. Advisory: state fire services may keep their own practice. DGFS hospital checklist
8. MoHFW national guidelines, 2026
Reported in the press as issued on 24 April 2026 to replace the 2020 guidelines. Flamekite found no official copy on 25 October 2026, so the page does not rely on their contents. TeamLease RegTechnews report
The 2024 hospital fire advisory as 7 dos and 4 don'ts
The Health Ministry and NDMA advisory of 23 March 2024 is the most detailed national text a hospital can follow today. Here it is as daily practice.
Do
- Check extinguishers every month, test alarms and hydrants every quarter, and have a professional inspection every year. Ministry of Health and Family Welfare and NDMA
- Audit the electrical load twice a year, and again whenever new equipment arrives or a space becomes an ICU. Ministry of Health and Family Welfare and NDMA
- Fit sprinklers and hosepipes in ICUs and operation theatres, linked to the fire alarm. Ministry of Health and Family Welfare and NDMA
- Test smoke detectors and alarms every month, as the MoHFW and NDMA guidance asks, in patient rooms, halls and common areas; IS 2189:2026 itself sets a yearly functional test of every smoke detector. Ministry of Health and Family Welfare and NDMA
- Seal electrical ducts with intumescent firestop so fire and smoke cannot travel through them. Ministry of Health and Family Welfare and NDMA
- Hold fire and evacuation drills twice a year for staff, doctors and patients, and write an SOP for a fire. Ministry of Health and Family Welfare and NDMA
- Renew the fire NOC every year as state fire rules allow, with up-to-date plans and maintenance and training records. Ministry of Health and Family Welfare and NDMA
Don’t
- Don't allow smoking or open heat sources where oxygen tanks or piped oxygen are in use. Ministry of Health and Family Welfare and NDMA
- Don't connect several high-power devices to one circuit. Ministry of Health and Family Welfare and NDMA
- Don't leave combustible furnishings and finishes in patient care areas; replace them with fire-resistant ones. Ministry of Health and Family Welfare and NDMA
- Don't block escape routes or exits; keep them marked and the assembly areas clear. Ministry of Health and Family Welfare and NDMA
State rulebooks written for hospitals: 6 instruments
Most states treat a hospital as one more institutional building. These 6 instruments were written for hospitals or name them by size.
Rajasthan, Table 3
Every year above 15 m; 5 or 3 years below, or none
A ground plus 1 building without beds on a plot up to 1,000 m² needs no NOC; with beds, or a plot up to 1,000 m² and up to 15 m, 5 years; up to 15 m on 1,000 to 3,000 m², 3 years; on a plot over 3,000 m² or above 15 m, every year. Rajasthan UDH
Telangana, G.O.Ms.No.162 of 2023
High-rise hospital rules amended
Maximum hospital height raised from 60 m to 130 m; a 7 m drive-way with a 9 m turning radius up to 54 m, 11 m and 14 m above; refuge areas above 24 m and about every 15 m, at least 15 m²; fire drills every 3 months for 2 years, then every 6 months. G.O.Ms.No.162
Andhra Pradesh, G.O.Ms.No.2 of 2011
High-rise hospital buildings above 30 m
The rules Telangana amended began here: open spaces of 11 m for 30 to 35 m rising to 16 m for 55 to 60 m, and a 60 m height cap. G.O.Ms.No.2 of 2011
Maharashtra, ss.45 and 45A
Hospitals above 30 m
A fire officer or fire supervisor appointed by the owner, and a Fire and Life Safety Audit by a licensed auditor every 2 years, on top of Form B each January and July. Amendment Act 2023
Delhi, DFS sheet
Nursing homes under 15 m of ground plus 2 or more
A 6 m access road, 2 staircases with a 2.0 m main stair, 2.4 m corridors and 45 m travel (fully sprinklered) for buildings after 1 July 2010; wet riser, sprinklers and detection all required. DFS
Tamil Nadu, Annexure IX
Hospital setbacks and drills
A 6 m setback all round below 18.3 m and 7 m from 18.3 m to 30 m, fire lifts with alternate power, staff trained by the fire service and mock drills every 6 months. TNCDBR 2019
Does your hospital need a fire NOC? 12 cases by state
Match your hospital's state, height, plot and beds to one line. Where an instrument does not name hospitals, the line is Flamekite's reading of its institutional row.
If Any hospital or nursing home in Assam
Yes, whatever its height or floor area: Schedule I files every hospital as high risk. Fire NOC Assam 2026 Assam Act LIII of 2025
If Any hospital in Uttar Pradesh
Yes: institutional buildings are special buildings at any height, and the certificate lasts 1 year under Rule 44. Fire NOC UP UP Rules 2024
If A ground plus 1 clinic without beds in Rajasthan on a plot up to 1,000 m²
No fire NOC under Table 3, item 1. Add beds and it renews every 5 years. Fire NOC Rajasthan Rajasthan UDH
If A hospital in Delhi over 9 m or of 3 storeys
Rule 27's institutional row. NABH's Delhi note reads a 9 to 15 m building as exempt only where the hospital uses the basement, ground and first floor and the floors above are not hospital. Fire NOC Delhi NABH notice 2026
If A hospital in Haryana or Chandigarh of 9 m or more
A special building whatever its floor area; Chandigarh charges Rs 14 per m², at least Rs 6,615. Fire NOC Haryana Government of Haryana
If A 25-bed nursing home in Chhattisgarh with an ICU
Yes: any critical care unit brings it in, whatever the beds; 2 years under 15 m. Fire NOC Chhattisgarh Home Department, Chhattisgarh
If A 20-bed clinic in Odisha below 12 m with no ICU
Self-regulatory under Order 50908; over 30 beds or any critical care unit needs the certificate. Fire NOC Odisha Order 50908 of 2019
If A hospital in Telangana above 15 m
Yes, as high risk, with an audit certificate every January and July; high-rise hospitals also follow the 2011 rules as amended in 2023. Fire Audit Telangana TG fire circular 2020
If A hospital in Karnataka between 15 m and 21 m
The Act's line is 21 m, but Seva Sindhu still lists above 15 m: ask KSFES in writing before you build. Fire NOC Karnataka Government of Karnataka
If A hospital in Kerala over 1,000 m² or 15 m
Fire approval under rule 5(4); 300 to 1,000 m² up to 15 m files an Appendix L self-declaration. Fire NOC Kerala KMBR amendment 2025
If A hospital in Maharashtra above 30 m
Appoint a fire officer or supervisor (s.45) and book a section 45A audit every 2 years, besides Form B twice a year. Fire Audit Maharashtra Amendment Act 2023
If Your state's line leaves the hospital out
Fire equipment is still owed, and NABH asks a hospital without a NOC to justify why it does not apply. Do I need a fire NOC? National Accreditation Board for Hospitals and Healthcare Providers
Hospital fire NOC fees in the official schedules
These are the hospital lines that an Act, rule or order prints. A consultant's or agency's quote is a private price.
As published
- Punjab, hospital or nursing home up to 30 bedsRs 5,000Above 100 beds Rs 30,000 plus Rs 5,000 per 25 beds, up to Rs 1 lakh (2021 letter) Local Govt Punjab
- Assam, hospitals and nursing homes under 15 mRs 1,000 or Rs 1,500 a stageUp to or over 1,000 m²; Rs 2,000 or Rs 2,500 at 15 m and above Assam fee Annexure A
- Meghalaya, C-1 hospitals, sanatoria and nursing homesRs 4 per m²Renewal Rs 1,500 Meghalaya F&ES
- Chandigarh, Group C institutionalRs 14 per m², at least Rs 6,615Certificate valid 5 years since 6 May 2026 MCC Office Order 23
- Kerala, hospitals up to 16 m on plots up to 1,000 m²Rs 20 per m², at least Rs 26,000Larger or taller hospitals Rs 40 per m² Kerala Fire and Rescue Services
- Gujarat, hospitals of 24 m to 45 mRs 15 per m²The band also carries 2 charges of Rs 5,000; 15 to 24 m pays Rs 10 per m² Gujarat Fire Safety Compliance Portal
- Karnataka, non-residential high-riseRs 60 per m², at least Rs 5,00,000A 15,000 m² hospital pays Rs 9,00,000 Seva Sindhu
- West Bengal, Group B: hospitals and nursing homesRs 6.52 per m² WBFES
- Goa, educational and institutional buildingsRs 10 per m² Goa Gazette 2022
- Rajasthan, Nagar Nigam areaRs 2 per sq ftRs 1.50 in a Nagar Parishad, Rs 1 in a Nagar Palika; renewal Rs 10,000, Rs 7,500 or Rs 5,000 Rajasthan UDH
- Andhra Pradesh, government hospital buildingsRs 0Exempt from the Rs 10 per m² fee for all NOCs since 30 December 2021 G.O.Ms.No.146
- Uttar Pradesh, portal feeNilProvisional, final and renewal UP Fire dashboard
Tamil Nadu, Jharkhand, Arunachal Pradesh, Puducherry, Himachal and Lakshadweep also charge nothing. Every state's schedule is on the fire NOC fees page.
Penalties for running a hospital without a fire NOC
Fire Acts punish the owner; some states also pull the hospital's licence. These are the amounts and sanctions the instruments set.
| Offence | Penalty | Law |
|---|---|---|
| No fire NOC or missing equipment, Rajasthan | Rs 5,000 on the owner or user | Section 291, Rajasthan Municipalities Act 2009, applied by the 2023 order Rajasthan UDH |
| Letting fire systems fall out of repair, Maharashtra | Rigorous imprisonment of 6 months to 3 years and a fine of Rs 20,000 to Rs 50,000 | Section 36(1), Act of 2006 MFS Act 2006 copy |
| Breaking the fire Act, Assam | Fines of Rs 10,000 to Rs 5 lakh | Act LIII of 2025 Assam Act LIII of 2025 |
| No Fire Safety Officer in a hospital of over 100 beds, Jharkhand | Rs 10 to Rs 50 per m² a month after 30 days' notice | Sections 29 and 31, Act 9 of 2024 Government of Jharkhand |
| Certificate cancelled, Uttar Pradesh | Reported to the licensing authority to cancel the hospital's licence | Rule 46, Rules 2024 LegitQueststudy |
| Licence issued without a valid certificate, Chhattisgarh | No authority may issue or renew a hospital licence without working fire systems and a valid certificate | Rule 35, Rules 2021 CG Gazette |
| COVID hospital without a NOC or renewal, 2020 to 2021 | Appropriate action by the state, as the Supreme Court directed | SMW(C) 7/2020, directions of 18 December 2020 Supreme Court of India |
| Using a forged fire NOC, Chhattisgarh, October 2026 | Criminal case registered against the hospital operator, as reported | Bharatiya Nyaya Sanhita, section 318(4) Medical Dialoguesnews report |
Every state's fire NOC penalties are on the penalties page.
Where hospitals fail fire inspections, and the fix
Hospital fires in India repeat a few failures: overloaded wiring in critical care, oxygen, switched-off systems and lapsed papers. These 7 come from the advisories and the inquiries reported.
If An ICU added to an old floor without checking the electrical load
Audit the load whenever equipment is added or a space becomes an ICU, as the 2024 advisory asks; the Jhansi inquiry team named a short circuit as the primary cause in November 2024. Ministry of Health and Family Welfare and NDMA
If Oxygen cylinders and medical gases stored inside the building footprint
Sprinkler every oxygen or medical gas store to the CL-3 level under NBCS 2026, and keep heat sources out. BIS, SP 7:2026
If A sprinkler control valve left closed and the alarm switched off
Keep systems live around the clock; at SCB Cuttack in March 2026 officials were suspended over exactly this, as reported. Medical Dialoguesnews report
If A NOC that lapsed or was refused, with the hospital still running
Treat a refusal as a stop: the Jhansi college was reported to have been denied a NOC in February 2024 for missing equipment, 9 months before its NICU fire. ThePrintnews report
If A neonatal unit holding more babies than its capacity
Size each compartment to take the neighbouring compartment's patients at 3.5 m² each, and keep bed numbers within the approval. BIS, SP 7:2026
If No reply from the fire department for months
For NABH, keep the acknowledged correspondence at least once every 3 months; it counts only for accreditation. National Accreditation Board for Hospitals and Healthcare Providers
If A NOC bought from a middleman
Verify it on the fire service's portal; an Arang hospital's NOC gave a different date on its QR code, as reported in October 2026. Medical Dialoguesnews report
Hospital fire NOC worked cases: 8 buildings in 8 states
Flamekite's reading of the rules for 8 example hospitals; the buildings are illustrations, the figures are the instruments'.
Case 1
A ground plus 3, 14 m hospital in Jaipur on a 2,000 m² plot
60 beds, Nagar Nigam area, 3,000 m² built-up.
What applies Table 3 item 3: up to 15 m on 1,000 to 3,000 m², so it renews every 3 years. Fee at Rs 2 per sq ft on about 32,292 sq ft is about Rs 64,584, by Flamekite's arithmetic. Rajasthan UDH
Case 2
A 30-bed nursing home in Lucknow, 10 m
Ground plus 2 on a 900 m² plot.
What applies Covered as institutional at any height; at 10 m it misses the below-9 m exemption from the agency certificate, and the certificate lasts 1 year. UP Rules 2024
Case 3
A 70 m hospital tower in Hyderabad
Wards on 16 floors.
What applies Under the 130 m cap of G.O.Ms.No.162; an 11 m drive-way with a 14 m turning radius above 54 m, refuge areas above 24 m and about every 15 m, a third-party design review, and audit uploads every January and July. G.O.Ms.No.162
Case 4
A 32 m hospital in Pune
Institutional, 9 floors.
What applies Above 30 m, so section 45 asks for a fire officer or supervisor and section 45A a licensed audit every 2 years, besides Form B every January and July. Amendment Act 2023
Case 5
A 60-bed hospital in Puducherry town
Institutional, G+3.
What applies Category A whatever its height: 2 agency audit certificates, inspections twice a year and a fresh NOC every year. Puducherry G.O. 61
Case 6
A 12 m nursing home in Delhi built in 2015
Ground plus 3, beds on every floor.
What applies Over 9 m and 3 storeys, so Rule 27 applies; the DFS sheet asks for 2 staircases, 2.4 m corridors, sprinklers and a 75,000 to 1,50,000 litre underground tank. DFS
Case 7
A 40-bed nursing home in Raipur, 8 m, with no ICU
Ground plus 1.
What applies Under 9 m, but more than 30 beds brings it in under the 2022 notification; a moderate-risk 2-year certificate. Home Department, Chhattisgarh
Case 8
A 2,400 m² hospital planned to NBCS 2026, 20 m
Ground plus 5 with an oxygen manifold room.
What applies CL-4 under Table 7C: wet riser, yard hydrant, sprinklers, detection and voice evacuation; the oxygen room sprinklered to CL-3 at least. BIS, SP 7:2026
Hospital fire rules in numbers
2.4 m
Minimum width of a corridor or ramp used to move patients (NBCS 2026) BIS, SP 7:2026
120 min
Fire separation around ICUs, theatres, delivery and recovery rooms BIS, SP 7:2026
3.5 m²
Space per bed-ridden patient a compartment must hold for its neighbours BIS, SP 7:2026
500 m²
Largest smoke compartment on a Telangana hospital floor with patients G.O.Ms.No.162
130 m
Telangana's maximum hospital height since 2023, up from 60 m G.O.Ms.No.162
30 beds
Above this, a Chhattisgarh or Odisha hospital needs the certificate at any height Home Department, Chhattisgarh
13
Instructions in the Health Ministry and NDMA advisory of 23 March 2024 Ministry of Health and Family Welfare and NDMA
64
Items for hospitals above 24 m to 45 m in the DGFS audit checklist DGFS hospital checklist
Hospital fire rules, dated: 2011 to 2026
Fifteen dated steps that shaped what a hospital owes today.
3 January 2011
Andhra Pradesh issues its Fire Prevention and Safety Measures in High-rise Hospital Buildings Rules for hospitals above 30 m. G.O.Ms.No.2 of 2011
February 2016
NDMA's Hospital Safety guidelines ask for a yearly ICU and ward evacuation drill. NDMA
28 September 2020
The Health Ministry sends its Fire and Life Safety guidelines to all states and government hospitals. Lok Sabha answer
9 December 2020
The Supreme Court records that every state was told to form a fire safety audit committee after the Rajkot COVID hospital fire. Supreme Court order
18 December 2020
The Supreme Court directs monthly fire audits of COVID hospitals and immediate NOC applications. Supreme Court of India
12 April 2021
Maharashtra's fire directorate orders audits of vulnerable buildings, citing the Bhandara hospital fire. MFS order 417
8 June 2021
Maharashtra asks every municipal body for an action-taken report on the inspection of all hospitals and nursing homes, in the Home Ministry's proforma. MFS hospital letter
20 September 2022
NABH revises its minimum fire safety measures and the third-party certificate route. National Accreditation Board for Hospitals and Healthcare Providers
27 December 2022
West Bengal sets up fire safety committees in every government hospital down to sub-divisional level. WB H&FW notification 215
16 August 2023
Telangana amends its high-rise hospital rules: 130 m cap, third-party design review, drills every 3 months for 2 years. G.O.Ms.No.162
14 September 2023
Rajasthan's order sets hospital terms of 5, 3 or 1 year by size in Table 3. Rajasthan UDH
23 March 2024
The Health Ministry and NDMA issue their 13-point advisory to prevent hospital fires. Ministry of Health and Family Welfare and NDMA
22 July 2025
Maharashtra cancels the 2021 audit orders 417 and 591 and moves audits to licensed section 45A auditors. MFS order 1148
2 January 2026
NABH declares January its Fire Safety Month and restates the Delhi applicability rules. NABH notice 2026
4 to 10 May 2026
The Health Ministry and DGFS hold a Fire Safety Week for healthcare facilities, as reported. All India Radionews report
Hospital fires in India, 2011 to 2026, as reported
From news reports, not yet an official source.
No inquiry report on these fires was found published online. The counts below are from news reports, except where an official order is named; where an order and the press differ, both are given.
16 March 2026
All India Radio reports at least 10 killed in a night fire in the Trauma Care department of SCB Medical College and Hospital, Cuttack. AIR Newsnews report
5 October 2025
The Week (PTI) reports a fire in the neuro-ICU of SMS Hospital's trauma centre in Jaipur killing 6, and a probe committee under the Medical Education Commissioner. The Weeknews report
12 December 2024
All India Radio reports 6 dead in a night fire at a private hospital in Dindigul, 5 of them found in a lift. AIR Newsnews report
15 November 2024
Al Jazeera reports newborns killed in a fire in the NICU of the Jhansi medical college; The Tribune reports the state's 4-member team found a short circuit the primary cause and a toll of 12. The Tribunenews report
25 May 2024
The Tribune reports 7 newborns dead at a baby-care hospital in Vivek Vihar, Delhi, whose licence had expired and which had no fire clearance. The Tribunenews report
1 August 2022
The Quint reports 8 dead at a private hospital in Jabalpur reported to be running on an expired fire NOC. The Quintnews report
9 January 2021
Scroll.in reports 10 infants dead in a fire around 2 am in the Sick Newborn Care Unit of Bhandara District General Hospital; Maharashtra's fire directorate order of 12 April 2021 gives 11 newborns. Scroll.innews report
9 December 2011
89 die at AMRI Hospital, Kolkata, in a fire that began in a basement used to store flammables (Wikipedia); NDMA's 2016 guidelines say more than 90. Wikipedianews report
Hospital fire NOC myths, checked against the rules
You may have read
A NABH third-party fire certificate replaces the hospital's fire NOC.
Myth
What the sources say
NABH accepts it in lieu of the NOC only for accreditation; the hospital must still obtain the NOC where it applies. National Accreditation Board for Hospitals and Healthcare Providers
You may have read
A small hospital under 15 m never needs a fire NOC.
Myth
What the sources say
Assam, Uttar Pradesh, Puducherry and Goa cover every hospital, and Delhi, Haryana and Bihar start at 9 m. UP Rules 2024
You may have read
The Health Ministry's 2024 advisory makes every NOC a 1-year NOC.
Myth
What the sources say
It asks for a yearly renewal "as per State Fire Safety Rules"; Rajasthan still gives smaller medical buildings 5 or 3 years. Ministry of Health and Family Welfare and NDMA
You may have read
The Supreme Court ordered monthly fire audits of every hospital.
Myth
What the sources say
The directions of 18 December 2020 were for hospitals earmarked for COVID patients. Supreme Court of India
You may have read
The DGFS checklist is a binding national format.
Myth
What the sources say
It says state fire services may continue their existing practice and use it as advisory input. DGFS hospital checklist
You may have read
Day-care clinics follow the hospital rules.
Myth
What the sources say
NBC 2016 files outpatient clinics as business, E-2; only buildings where patients stay are C-1. BIS, NBC 2016 Part 4
Where a hospital applies for its fire NOC, state by state
These 9 official portals took hospital and institutional fire applications on 25 October 2026.
Uttar Pradesh
UP Fire Service: Apply for NOC
Provisional, final and renewal certificates; no portal fee UP Fire FAQ
upfireservice.gov.in/upfire/user/loginChhattisgarh
CG Fire NOC portal
Online NOC in 7 steps, with the DGFS hospital checklist hosted on the site CG Fire NOC
firenoc.cg.gov.inTamil Nadu
Tamil Nadu Single Window Portal
TNFRS NOC and fire licence; no fees collected TN Single Window
tnswp.com/DIGIGOV/swp-tnswp.jspGujarat
GujFireSafety CoP
Fire Safety Plan and Certificate approval through a Fire Safety Officer Gujarat FSCOP
fscop.gujfiresafetycop.inKerala
Kerala Fire NOC portal
Site and Final Clearance for buildings over the rule 5(4) line Kerala NOC manual
noc.fire.kerala.gov.in/applicant_controller/signupKarnataka
Seva Sindhu: high-rise NOC
Karnataka's high-rise fire NOC application Seva Sindhu
sevasindhu.karnataka.gov.in/category/Application%20for%20No%20Objection%20Certificate%20(High%20rise%20Building)%20-%20Fire%20&%20Emergency.htmlDelhi
Delhi Fire Service
Fire Safety Certificate, its renewal and the nursing-home requirements sheet DFS
dfs.delhi.gov.inTelangana
Telangana Fire Services
Building NOC login and the GOs page with G.O.Ms.No.162 TGFD contact
fire.telangana.gov.inRajasthan
Rajasthan LSG online: fire service
Fire NOC registration, renewal and certificate verification Local Self Government Department, Rajasthan
lsgonline.rajasthan.gov.in/fire_service.aspx
What Flamekite could not confirm about hospital fire rules
Six gaps remain after reading every official copy Flamekite could reach on 25 October 2026. Each is a place to ask the authority in writing.
The Health Ministry's National Guidelines on Fire and Life Safety in Healthcare Facilities, 2026 were reported in the press as issued on 24 April 2026. No copy was found on the Ministry's, DGHS's or PIB's sites, so this page does not repeat the reported figures, such as a Fire Safety Officer for hospitals of 250 beds. The 2020 guidelines they reportedly replace, sent by letter of 28 September 2020, were not found either.
No official inquiry report into the Bhandara (January 2021) or Jhansi (November 2024) fires is online. The Supreme Court's two orders also name the Rajkot inquiry judge differently: Justice D.A. Mehta on 9 December 2020, Justice P M Mehta on 19 July 2021.
NABH's Delhi note and the Delhi Fire Service Rules read differently for hospitals of 9 m to 15 m: Rule 27 brings in institutional buildings over 9 m or of 3 storeys, while NABH treats a 9 to 15 m building as exempt where only the basement, ground and first floor are hospital. Ask DFS before relying on the exemption.
| What | The rule | Source |
|---|---|---|
| MoHFW guidelines 2026 | Reported only; no official copy found | TeamLease RegTechnews report |
| MoHFW guidelines of 28 September 2020 | Named in Lok Sabha answers; text not found | Lok Sabha answer |
| Bhandara toll | 11 newborns in the MFS order; 10 infants in the press | MFS order 417 |
| Maharashtra Schedule-I hospital rows | Not proof-read by Flamekite | Amendment Act 2023 |
| Telangana hospital rules, full text | G.O.Ms.No.162 pages 5 to 11 and the 2011 base rules not read in full | G.O.Ms.No.162 |
| Punjab, Ladakh, Madhya Pradesh, DNH and DD | No hospital-specific line found beyond the general rules | Local Govt Punjab |
Questions about fire NOCs for hospitals
Is a fire NOC mandatory for a hospital?
- In most states, yes once the hospital crosses the state's line, and in Assam, Uttar Pradesh, Puducherry and Goa at any size. Delhi, Haryana and Bihar start at 9 m; Chhattisgarh and Odisha at more than 30 beds or any ICU; Telangana above 15 m; Karnataka at 21 m. Rajasthan exempts only a ground plus 1 building without beds on a small plot.
What are the fire safety norms for hospitals in the NBC?
- Hospitals are C-1 in NBC 2016 and C-I in NBCS 2026. Patient corridors must be 2.4 m wide, exits 2.0 m, ICUs and theatres separated by 120 minutes, and each compartment able to take its neighbour's patients. Sprinklers are required at every height in NABH's NBC 2016 table, and wet risers from G+2.
How often must a hospital renew its fire NOC?
- By the state's term: every year in Uttar Pradesh, Puducherry, Sikkim and Arunachal Pradesh; 5, 3 or 1 year by size in Rajasthan; 2 years under 15 m and 1 above in Chhattisgarh. The Health Ministry and NDMA advisory of 23 March 2024 asks for a yearly renewal as state rules allow.
Can NABH accreditation be done without a fire NOC?
- Only on NABH's own terms: proof of the NOC application with correspondence at least every 3 months, or a third-party inspection certificate from a NABCB-accredited Type A body, valid at most 1 year. NABH says it does not absolve the hospital from obtaining the NOC.
What did the Supreme Court order on hospital fire safety?
- On 18 December 2020, after the Rajkot COVID hospital fire, it directed a nodal officer for each COVID hospital, a district committee to fire-audit each one at least once a month, and an immediate NOC application or renewal, with action against hospitals found without one.
When does a hospital need a Fire Safety Officer?
- It varies: Jharkhand above 100 beds, Lakshadweep at 100 beds, Uttarakhand above 250 beds, Bihar above 500 beds, Uttar Pradesh above 500 beds or from 15 m, Meghalaya and Nagaland from 15 m, Gujarat above 15 m (a Fire Safety Executive), and Maharashtra above 30 m.
How often should a hospital hold fire drills?
- The 2024 national advisory asks for drills twice a year; NDMA asks for a yearly ICU and ward evacuation drill; Tamil Nadu every 6 months; Telangana's high-rise hospitals every 3 months for 2 years, then every 6 months. NHSRC's quality note asks primary health centres for one every quarter.
What is the fire NOC fee for a hospital?
- Punjab charges Rs 5,000 up to 30 beds; Meghalaya Rs 4 per m²; Chandigarh Rs 14 per m² with a Rs 6,615 minimum; Kerala Rs 20 or Rs 40 per m² with a Rs 26,000 minimum; Gujarat Rs 15 per m² for 24 to 45 m. Uttar Pradesh and Tamil Nadu charge nothing, and Andhra Pradesh exempts government hospitals.
Keep reading
- Fire NOCWhat a fire NOC is, who issues it and every state's regime.
- Which buildings require a fire NOCHeight, area and use lines for all 36 states and UTs.
- Fire audit checklistThe DGFS hospital list beside NBC Part 4 and state formats.
- Fire audit report formatThe hospital checklist by category and every state's form.
- Fire NOC feesEvery published state fee schedule compared.
- Fire NOC validityHow long a certificate lasts in each state.
- Fire NOC penaltiesWhat each state's law sets for running without fire compliance.
- Documents required for fire NOCState checklists, with the bed details hospitals add.
Free tools for this
Words on this page, explained
Keep exploring
Fire NOC by building type
- Nursing Homes
- Clinics
- Schools
- Coaching Centres
- Hostels and PGs
- Hotels
- Restaurants
- Banquet Halls
- Cinemas and Theatres
- Gaming Zones
- Residential Buildings
- Apartments
- Commercial Buildings
- Offices
- Shops
- Malls
- Factories
- Industries and MSMEs
- Warehouses
- Cold Storage
- Godowns
- LPG Godowns
- Petrol Pumps
- EV Charging Stations
- Data Centres
- Temples and Places of Worship
Fire NOC: the steps
Sources
Each source was opened and read on the date shown. How Flamekite checks its sources
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016 (SP 7:2016), Part 4: Fire and Life Safety, clauses 1.2, 2.38 and 3.1 (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)
- Supreme Court of India: SMW(C) 7/2020, In Re: Proper Treatment of COVID-19 Patients, order of 19 July 2021 restating the directions of 18 December 2020 (opens in a new tab)
- Supreme Court of India, record of proceedings: SMW(C) 7/2020, In Re: Proper Treatment of COVID-19 Patients, order of 9 December 2020: fire safety audit committees in every state; the Rajkot COVID hospital fire before an inquiry under Justice D.A. Mehta (opens in a new tab)
- Ministry of Health and Family Welfare and NDMA (text reproduced by NABH): Joint advisory to prevent hospital fires, 23 March 2024 (HFW/Advisory to prevent hospital fires/23rdMarch2024/1) (opens in a new tab)
- National Accreditation Board for Hospitals and Healthcare Providers (NABH): Revised Advisory for Minimum Essential Fire Safety Measures, 20 September 2022 (opens in a new tab)
Show all 86 sourcesShow fewer
- National Accreditation Board for Hospitals and Healthcare Providers (NABH): NABH/GEN/2026/00009, 2 January 2026: Fire Safety Advisory for Healthcare Organizations (January as Fire Safety Month), with Annexure 3, Applicability of Fire Safety Compliance Certificates in Delhi (opens in a new tab)
- Lok Sabha (Ministry of Health and Family Welfare): Unstarred Question 3032, 13 December 2024, Fire Accidents in Hospitals: the Fire and Life Safety guidelines of 28 September 2020 and district committees under Collectors (opens in a new tab)
- Lok Sabha (Ministry of Health and Family Welfare): Unstarred Question 704, 7 February 2025, Fire Incident in Jhansi Hospital (15 November 2024): UP's medical education directorate advisories on fire and electrical audits (opens in a new tab)
- National Disaster Management Authority, Government of India: National Disaster Management Guidelines: Hospital Safety, February 2016, chapter 6, Fire Safety in Hospitals, and the yearly ICU and ward evacuation drills (opens in a new tab)
- National Health Systems Resource Centre, Quality and Patient Safety Division (MoHFW's technical body): Guidance Note on Fire Safety Measures in Primary Healthcare Facilities (NQAS; posted in the April 2026 folder; no date printed): quarterly mock drills, a valid fire NOC not waived (opens in a new tab)
- Directorate General Fire Services, Civil Defence and Home Guards, MHA (copy hosted by Maharashtra Fire and Emergency Services): Fire Safety Audit Checklist Advisory for Hospitals / Nursing Homes, F. No. VI-14022/09/2024-DGCD (F), 26 pages: general measures and Categories A to D by height and plot area (opens in a new tab)
- Maharashtra Fire and Emergency Services: Office Order No. MFS/51/2021/417, 12 April 2021: fire safety audit of various vulnerable occupancies (read from the page images) (opens in a new tab)
- Delhi Fire Service (copy of Delhi Gazette Extraordinary, Part IV): Delhi Fire Service (Amendment) Rules, 2025, notification F.No. DFS/HQ/Misc/2025/01(E-259159)/237, gazetted 26 May 2026 (opens in a new tab)
- Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)
- Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)
- Urban Development, Housing and Local Self Government Departments, Rajasthan: Joint order No. P.11(9)UDH/2020 Part, 14 September 2023, on the fire safety certificate and fire NOC (18-page Hindi scan) (opens in a new tab)
- Government of Haryana (PRS copy): Haryana Fire and Emergency Services Act, 2022 (Act 14 of 2022) (opens in a new tab)
- Home Department, Chhattisgarh (on the CG Fire NOC portal): Notification under section 14(1), 29 November 2022: buildings that need a fire NOC (opens in a new tab)
- Government of Telangana, MA&UD (Plg.III) Department (copy on the fire department's GOs page): G.O.Ms.No.162, 16 August 2023: amendments to the Fire Prevention and Safety Measures in High-Rise Hospital Buildings Rules, 2011, including fire drills and new rules 24.0 (third-party review of the fire and life safety design) and 25.0 (existing buildings) (read from the page images) (opens in a new tab)
- Government of Andhra Pradesh, MA&UD (M1) Department (copy hosted by AP Fire Services): G.O.Ms.No.2, 3 January 2011: AP Fire Prevention and Safety Measures in High-rise Hospital Buildings (above 30 m) Rules, 2011 (opens in a new tab)
- Government of Maharashtra (copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023 (Mah. Act No. XXIV of 2023), first published 11 May 2023 (opens in a new tab)
- Delhi Fire Service: Fire safety requirements for nursing homes (scanned sheet, page dated 23 January 2025) (opens in a new tab)
- Chennai Metropolitan Development Authority (copy of Tamil Nadu Government Gazette Extraordinary No. 43): Tamil Nadu Combined Development and Building Rules, 2019 (G.O. Ms. No. 18, MAWS, 4 February 2019): rules 2(58), 7, 20, 39, 64 and Annexure IX (opens in a new tab)
- Assam Gazette Extraordinary No. 811, 24 December 2025 (PRS copy of the gazette): The Assam Fire and Emergency Services Act, 2025 (Assam Act No. LIII of 2025), notification No. LGL.52/2025/3: sections 1 to 67 and Schedule I (opens in a new tab)
- Uttar Pradesh Gazette Extraordinary, 18 January 2024 (copy hosted by UP Fire and Emergency Services): Uttar Pradesh Fire and Emergency Services Rules, 2024, Notification No. 181/VI-Pu-8-2024-801(1)-2023: rules 40 to 56, 65, 66 and 72, Schedules VI and VII, Forms A-4, A-8 and A-11 to A-13 (opens in a new tab)
- Home Department, Government of Odisha: Order No. 50908 of 19 November 2019: procedure for issue and renewal of Fire Safety Certificates and Fire Safety Recommendations (issuing officer, validity, inspecting team and time limit by building type) (opens in a new tab)
- Director General, Telangana State Disaster Response and Fire Services: Circular Memorandum Rc.No.6402/MSB/2019, 28 January 2020: conducting of fire audit in all high-rise and non-high-rise buildings; third-party certificate uploaded every January, or every January and July, by height and use, with the 13-point certificate format (read from the page images) (opens in a new tab)
- Government of Karnataka (PRS copy): Karnataka Fire Force (Amendment) Ordinance, 2023: section 13(3) high-rise NOC (opens in a new tab)
- Local Self Government Department, Government of Kerala (Kerala Gazette Extraordinary No. 3808): Kerala Municipality Building (Amendment) Rules, 2025 (G.O.(P) No.53/2025/LSGD, S.R.O. No.1240/2025, 29 October 2025) and Kerala Panchayat Building (Amendment) Rules, 2025 (G.O.(P) No.54/2025/LSGD): rule 5(4) restated, rules 35 and 36 (opens in a new tab)
- Directorate of Local Government, Punjab (Wayback Machine copy of 21 March 2022 of the portal's fee download): Letter No. S4-DSMS-(Fire)-2021/41343 of 8 October 2021: new fees for online fire NOCs, by NBC zone, with provisional, renewal and 30-day rules (opens in a new tab)
- Fire and Emergency Services, Assam: Annexure A, proposed rates of fee for issuance of No Objection Certificate, renewal NOC etc. (5 image pages, read from the page images) (opens in a new tab)
- Fire and Emergency Services, Meghalaya: Annexure B1 to notification HPL.179/2017/85: institutional, assembly and business buildings (opens in a new tab)
- Municipal Corporation Chandigarh, Fire and Rescue Services: Office Order No. 23 of 10 February 2025: Fire Safety Certificate charges by NBC occupancy group from 1 April 2025, validity 3 years, exemptions (read from the page images) (opens in a new tab)
- Kerala Fire and Rescue Services: Fee structure, G.O.(Ms)No.272/2024/Home (opens in a new tab)
- Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)
- Seva Sindhu, Government of Karnataka: Application for No Objection Certificate (High rise Building) - Fire & Emergency: documents, fee under G.O. of 13-09-2019, 60 working days (opens in a new tab)
- West Bengal Fire and Emergency Services: Issuance of Fire Safety Recommendation: document requirement with drawing scales (opens in a new tab)
- Government of Goa, Official Gazette Series II No. 31 (Extraordinary No. 3), 3 November 2022: Notification 41/1/2022/PG(Notification)/235 under the Goa (Right of Citizens to Time-bound Delivery of Public Services) Act, 2013: DFES services 81 to 116 with designated officers, time limits and appellate authorities (opens in a new tab)
- Government of Andhra Pradesh, Home (Prisons and Fire) Department (copy hosted by AP Fire Services): G.O.Ms.No.146, 30 December 2021: fire precaution fee exempted for government hospital buildings (opens in a new tab)
- Uttar Pradesh Fire and Emergency Services: Dashboard: provisional, final and renewal applications, approvals and days to certificate (printed 24 October 2026) (opens in a new tab)
- Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures Act, 2006, English gazette of 5 February 2007 (sections 3, 8, 36 to 38 read off the page images) (opens in a new tab)
- Government of Jharkhand (PRS copy): Jharkhand Fire Service Act, 2024 (Act 9 of 2024) (opens in a new tab)
- Chhattisgarh Gazette Extraordinary No. 539, 20 October 2021 (on the CG Fire NOC portal): Chhattisgarh Fire and Emergency Service Rules, 2021 (Hindi), Home Department notification of 7 October 2021: rules 33 to 45 (opens in a new tab)
- Government of Puducherry, Home Department (copy hosted by the Fire Service Department): G.O.Ms.No.61, 10 September 2025: Fire Safety Audit and Issue of NOC, Third Party Fire Safety Audit, Categories A, B and C, renewal, temporary licences, and Annexures I to V on licensed agencies and the Category C protocol (opens in a new tab)
- Directorate of Maharashtra Fire Service, with the MHA Fire Adviser's letter of 31 May 2021: Letter No. MFS-2021/37, 8 June 2021 (Marathi): fire incidents in hospitals and nursing homes; action-taken report on the inspection of all hospitals ordered on 9 January 2021, in the MHA proforma (read from the page images) (opens in a new tab)
- WBXPress (copy of Health and Family Welfare notification 215/HF/O/HS(MS)/W-17/2022, 27 December 2022): Hospital Level Fire Safety Committee in every health facility down to sub-divisional hospitals (opens in a new tab)
- Directorate of Maharashtra Fire Service: Office Order No. MFS/51/2025/1148, 22 July 2025: orders 417 and 591 of 2021 on fire-risk inspections by licence agencies and retired fire officers cancelled; Fire and Life Safety Auditors to be appointed under section 45A (read from the page image) (opens in a new tab)
- Uttar Pradesh Fire and Emergency Services: Frequently asked questions (Hindi): Nivesh Mitra categories, free online application, SMS updates, helplines (opens in a new tab)
- Fire and Emergency Services and SDRF, Chhattisgarh: Process to obtain Online NOC: 7 steps, Director review 5 days, inspection 20 days, decision 5 days, maximum 30 days (opens in a new tab)
- Guidance Tamil Nadu (Tamil Nadu Single Window Portal): TNSWP home: TNFRS services, citizen registration, Verify Certificate, NSWS integration, toll-free helpline (opens in a new tab)
- Gujarat State Fire Prevention Services: FSCOP citizen login: FSPA, FSCA, FSCR, inspections and mock drills (opens in a new tab)
- Kerala Fire and Rescue Services (manual by KELTRON): User manual, public side NOC portal (28 February 2020): sign-up, application tabs, e-treasury payment, dashboard (opens in a new tab)
- Delhi Fire Service: Department of Delhi Fire Service, Govt of NCT of Delhi (home page and portal links) (opens in a new tab)
- Telangana Fire, Disaster Response, Emergency and Civil Defence Department: Contact us: Director General's office, control room and portal support (opens in a new tab)
- Local Self Government Department, Rajasthan: Fire service: Fire NOC registration and certificate verification (nodal officer and helpline) (opens in a new tab)
- Andhra Pradesh Legislative Assembly (PRS copy of AP Gazette Part IV-A No. 12, 4 March 2026): Andhra Pradesh Fire Service (Amendment) Bill, 2026 (L.A. Bill No. 12 of 2026): new section 13 thresholds, 21-day and 30-day timelines (opens in a new tab)
- Government of Bihar, Home Department notification (English copy hosted by Bihar Fire Service): Bihar Fire Service Rules, 2021: rules 14 to 27, 33, 34 and 38, Schedules C (fees), D (online NOC), E (pandals) and H (existing buildings) (opens in a new tab)
- Government of Manipur (PRS copy): Manipur Fire and Emergency Service Act, 2026 (Act 9 of 2026) (opens in a new tab)
- Directorate of Fire and Emergency Services, Nagaland: Nagaland Fire and Emergency Services Act (Act No. 5 of 2023), Nagaland Gazette, 31 August 2023 (opens in a new tab)
- Government of Himachal Pradesh, Department of Home (copy hosted by the Department of Fire Services): Notification No. Home-F(A)3-1/2019-I, 23 July 2019, under section 9(1) of the HP Fire Fighting Services Act, 1984: 17 classes of premises and 20 fire precautions, English and Hindi texts (opens in a new tab)
- Department of Town Planning and ULBs, Arunachal Pradesh (Gazette No. 347, 4 September 2019; copy on EoDB Arunachal): Arunachal Pradesh Building Bye-Laws, 2019 (notification No. DTP/BBL-03/2011-12/2592-601, 30 August 2019): definitions, bye-laws 2.9 to 2.17, chapter 11, Annexures C and D, and 13.5 (opens in a new tab)
- Directorate of Fire and Emergency Services, Tripura: Tripura Fire Safety Rules, 2026 (Tripura Gazette, 2 June 2026) (opens in a new tab)
- Government of Uttarakhand, Home Section-4 (copy hosted by Uttarakhand Fire and Emergency Services): Notification No. 342/XX-3/2021-2(39)/2006 of November 2021 under section 26 of the 2016 Act: 5 year validity for residential buildings except hotels, 3 years for other buildings, six-monthly self-declaration, fresh certificate on change of use (opens in a new tab)
- Telangana State Disaster Response and Fire Services Department: Circular Memorandum Rc.No.4039-2/EODB/2015, 5 March 2016: revision of the period of renewal of NOC, risk categories and random inspections (quotes section 13 of the Fire Service Act, 1999) (opens in a new tab)
- West Bengal Fire and Emergency Services: FAQ: fire safety certificate, 14.5 m line, compounding under section 38B (opens in a new tab)
- Gazette of Meghalaya No. 19, Part IIA, 24 May 2018: Notification No. HPL.254/2013/65 of 9 May 2018: qualified Fire Officer in institutional buildings of 15 m and above within 90 days (opens in a new tab)
- Government of Sikkim, Sikkim Government Gazette Extraordinary No. 466, 17 December 2025: The Sikkim Fire and Emergency Services Rules, 2025: Home Department notification No. 99/Home/2025, 17 December 2025, under section 63 of Act 4 of 2023, with Schedules I to V and Forms A1 to A20 (opens in a new tab)
- Housing and Urban Development Department, J&K (copy hosted by NITI for States): Jammu and Kashmir Unified Building Byelaws 2021 (February 2021): use classes, high-rise and tall buildings, fire access and Fire Consultant on Record (opens in a new tab)
- Lakshadweep Gazette Extraordinary Vol. LXII No. 42, 3 September 2026: Lakshadweep Fire and Emergency Services Rules, 2026 (Rule 12: 5-year fire safety certificate) (opens in a new tab)
- Fire Service Department, Andaman and Nicobar Administration (NIC portal): Online Service Portal of Fire Service Department: new and renewal Fire Clearance Certificates, inspections, incident certificates, the 9 premises classes, critical-activity checklists and the Aberdeen Bazar contact (last modified 28 July 2025) (opens in a new tab)
- Home Department, Government of Mizoram (copy on the Mizoram Fire and Emergency Services site): Notification No. B-20011/2/2026-HM(F&ES), 20 August 2026: Mizoram Fire and Emergency Services (Superintendence and Control of the Fire Force and Fire Safety and Prevention) (Amendment) Rules, 2026, substituting Rule 57 and inserting Rules 57(A) and 57(B) (opens in a new tab)
- LegitQuest (legal database): Uttar Pradesh Fire and Emergency Services Rules, 2024: Rule 44 validity, Rule 46 cancellation (opens in a new tab)
- TeamLease RegTech: MoHFW issued the National Guidelines on Fire and Life Safety in Healthcare Facilities, 2026 (opens in a new tab)
- Medical Dialogues: Chhattisgarh hospital operator booked over suspected forgery of fire safety NOC (18 October 2026) (opens in a new tab)
- Medical Dialogues, 19 March 2026: Odisha suspends four officials over SCB hospital fire (opens in a new tab)
- ThePrint, 21 November 2024: Jhansi hospital where blaze killed 10 newborns was denied fire NOC in February (opens in a new tab)
- All India Radio (News on AIR): Health Ministry to observe Fire Safety Week, focus on healthcare facility preparedness (28 April 2026) (opens in a new tab)
- All India Radio News, 16 March 2026: Ten killed in fire at SCB Medical College trauma care centre in Cuttack, Odisha (opens in a new tab)
- The Week (PTI): Fire at SMS Hospital trauma centre ICU in Jaipur kills six; probe committee under Iqbal Khan (6 October 2025) (opens in a new tab)
- All India Radio News: Tamil Nadu: 6 burnt to death in Dindigul hospital fire (13 December 2024) (opens in a new tab)
- The Tribune, 19 November 2024: Primary reason of fire was short circuit: inquiry team on Jhansi medical college fire incident (opens in a new tab)
- The Tribune: 7 newborns killed in Delhi hospital fire (May 2024) (opens in a new tab)
- The Quint: Jabalpur hospital fire: inadequate fire safety systems, 8 deaths (2 August 2022) (opens in a new tab)
- Scroll.in, 9 January 2021: 10 infants die in fire at Maharashtra district hospital (Sick Newborn Care Unit, Bhandara District General Hospital) (opens in a new tab)
- Wikipedia (secondary): 2011 Kolkata hospital fire (AMRI Hospital, Dhakuria, 9 December 2011) (opens in a new tab)