Fire audit checklist: 38 checks, each traced to the rule that requires it
Updated By Flamekite Editorial DeskFacts checked against official sources on
Quick answer
A fire audit checklist of 38 checks, each traced to NBC Part 4, an IS code or a state circular, with test intervals and the official hospital and hotel lists.
India has no single statutory checklist. The auditor works from the code your approval cites, usually NBC 2016 Part 4, the IS code for each system, and the state's own format: Telangana's 13-point certificate, Maharashtra's rule 33 duties and its Form B site checklist. For hospitals the Directorate General Fire Services published a 4-category advisory list of up to 64 items.
- DGCD hospital checklist, tallest category
- 64 items
- Category D: hospitals above 24 m up to 45 m
- Checklist finder
- Travel distance in a sprinklered block of flats
- 60 m
- NBCS 2026 Table 4; 30 m without sprinklers
- Egress table
Free, on WhatsApp. Or check if you need one
The fire audit checklist at a glance: what it checks and against which rule
| What | The rule | Source |
|---|---|---|
| One national checklist? | None in law. The nearest is the Directorate General Fire Services' hospital advisory, which says state fire services may keep their own practice | DGCD, MHA |
| The code most checklists cite | NBC 2016 Part 4, which BIS withdrew on 30 April 2026; approvals issued under it are still audited against it | Gazette of India |
| The newer code | NBCS 2026 Part F, voluntary: only Assam had written it into its fire law by 24 October 2026 | Assam Act XIII of 2026 |
| Where NBCS 2026 binds workplaces | Uttar Pradesh OSH rule 12: buildings of 5 or more floors or 20 m or more must meet Part F | UP Gazette |
| The fullest official test schedule | MFS Form B guidelines of 7 July 2026: daily to 5-yearly tests for extinguishers, hose reels, hydrants, sprinklers, pumps and detection | MFS Form B guidelines |
| The shortest official certificate | Telangana's 13 measures, each marked working or not working by a third-party auditor | TG fire circular 2020 |
| The auditor's duties in law | Maharashtra rule 33: 12 duties, ending in a Fire Audit Report and a Form V certificate | Amendment Rules 2025 |
| Hospitals | DGCD checklist: 48 general items, then Categories A to D by height and plot area | DGCD, MHA |
| Detection code | IS 2189:2026 from 17 March 2026; the 2008 edition was withdrawn on 17 September 2026 | BIS standards database |
| Last verified | 25 October 2026, against the DGCD checklist, the MFS circulars, NBC 2016 Part 4, NBCS 2026 Part F and the BIS standards database | Not stated |
Fire audit checklist system by system: the code, its edition and the test
| Option | Code, current edition | What is required | The official test | Named in | Source |
|---|---|---|---|---|---|
| Portable extinguishers | IS 2190:2024 for selection and upkeep; IS 15683:2018 for construction | The right type and number for the hazard, placed and serviced | Recharge a gas cartridge that has lost more than 10% of its mass; discharge-test water stored-pressure units every 2 years | DGCD item 6; MFS clause 8 A; Telangana item 1 | MFS Form B guidelines |
| First-aid hose reels | IS 884:2025 for the reel; installed under IS 3844:1989 | A reel fed from the riser on each floor the occupancy table names, hose of at least 19 mm (NBCS 2026 clause 5.1.1(d)) | Once a year: hose run out fully, at least 30 L/min at the highest reel (IS 3844 cl. 9.7); Maharashtra's guidelines add a jet of at least 6 m | DGCD item 8; MFS clause 8 B; Telangana item 2 | MFS Form B guidelines |
| Internal hydrants, wet riser, down-comer | IS 3844:1989, current and valid to 20 June 2030 | A riser main of at least 100 mm, 3.5 to 7 bar at the hydrants (NBCS 2026 clause 5.1.1(f)) | Each quarter: 3 adjacent hydrants open together, at least 1,125 L/min at 5.25 kgf/cm² (Maharashtra guidelines); IS 3844 itself asks valves and boxes inspected every 6 months | DGCD items 9 to 11; MFS clause 8 C; Telangana item 3 | MFS Form B guidelines |
| Yard hydrants | IS 13039:2014 | An external hydrant system around the building | Monthly: open each outlet and check washers; every 6 months: landing, drain and isolation valves and the fire service inlet | DGCD Categories B to D; Telangana item 4 | DGCD, MHA |
| Automatic sprinklers | IS 15105:2021 | Sprinklers where NBC 2016 Table 7 asks for them by occupancy and height | Daily: installation valve and gauges; every 6 months: discharge test; yearly: pipework examined and the system flushed | DGCD item 7; MFS clause 8 D; Telangana item 5 | MFS Form B guidelines |
| Fire pumps | IS 15301:2003 | An electric main pump, an equal standby and a jockey pump (NBCS 2026 Table 7M) | Main pump run at least 5 minutes daily; diesel engine started weekly for 10 minutes with fuel for 4 hours | MFS clauses 8 E and 9 B; Telangana item 10 | MFS Form B guidelines |
| Fire water storage | IS 9668:1990 | Underground and terrace tanks in 2 or more interconnected compartments (NBCS 2026 clause 5.1.2.1) | Weekly: tanks full and clean; cleaned once in 1 or 2 years | DGCD item 12; Telangana items 8 and 9 | BIS, SP 7:2026 |
| Detection and alarm | IS 2189:2026; the 2008 edition was withdrawn on 17 September 2026 | Detectors, manual call points, the panel and sounders | IS 2189:2026: daily panel check, quarterly user test, yearly functional test of every smoke detector (Maharashtra's guidelines instead ask 20% a year, every device within 5 years) | DGCD; MFS clause 8 F; Telangana items 6 and 7 | BIS standards database |
| Fire doors | IS 3614:2021 | 120 min doors into exit stairs and in openings of fire walls (NBC 2016 clauses 3.4.5.2 and 4.4.2.4.3.2) | A label giving the rating, maker, batch and month of manufacture (NBC 2016 clause 4.4.2.4.1(f)) | DGCD Category C item 27 (fire compartmentation) | BIS, NBC 2016 Part 4 |
| Exit signs | IS 12349:1988 for safety signs | Green signs, with no point more than 30 m from a visible directional sign (NBC 2016 clause 3.4.7.4) | Lit, on an independent circuit with an alternative supply | MFS clause 9 D; Telangana item 11 | BIS, NBC 2016 Part 4 |
| Emergency lighting | NBC 2016 clause 3.4.7.1; NBCS 2026 clause 3.5.6.1 | A source independent of normal lighting, on within 5 s | Holds the required light for at least 90 minutes; Telangana asks battery backup of at least 90 minutes | Telangana item 12; DGCD Category C item 24 | BIS, NBC 2016 Part 4 |
| Stair and lobby pressurisation | NBC 2016 Table 6 | By height: lift lobbies with 120 min doors at 25 to 30 Pa, or the lift shaft at 50 Pa where there is no lobby | Run on the alternate power supply at the Maharashtra Form B test | Telangana item 13; MFS covering letter | BIS, NBC 2016 Part 4 |
How to walk a building with this fire audit checklist, in Flamekite's order
Collect the papers before the walk
The fire certificate on display, the approved plans, the maintenance contract, the log books and the last audit or Form B. The DGCD hospital list asks for each of these before any system is tested.
Fix which code edition applies
Read the fire approval: most cite NBC 2016 Part 4, which BIS withdrew on 30 April 2026. Audit against the edition the approval was issued under, and note where NBCS 2026 now differs.
Walk the exits from the top floor down
Count the staircases, measure stair widths and dead ends, check that every fire door self-closes and that no stair holds panels, ducts or storage.
Check the passive measures on the way
Compartment walls and their 120 min doors, sealed shafts, refuge areas above 24 m and the firefighting shaft's lobby.
Run every active system
Start each pump, open the topmost hydrant and the sprinkler test valve, trigger a detector in each zone, and run the hose reel on the highest floor.
Cut the mains and watch the standby
Pumps, alarm, talk-back, pressurisation fans, lifts and stair lighting should all run on the alternate supply, as Maharashtra's Form B test requires.
Record each item against its clause
Mark it working or not working, as Telangana's certificate does, with a dated photograph and the clause it fails, so every fix can be traced to the rule.
The fire audit checklist: 38 checks the rules require, with the clause for each
Every item below is written in an official document, named in brackets. Flamekite's own practical checks are kept apart, further down the page.
- Exits: at least 2 staircases in every building Part 4 covers (NBC 2016 clause 4.4.2.4.3.1) BIS, NBC 2016 Part 4
- Exits: every point on a floor within the Table 5 travel distance, 30 m for homes, schools, hospitals, offices and shops in Type 1 and 2 construction (clause 4.4.2.2) BIS, NBC 2016 Part 4
- Exits: dead-end corridors no longer than 6 m in schools, hospitals and assembly buildings, and 15 m in other buildings (clause 4.4.2.2(c)) BIS, NBC 2016 Part 4
- Exits: exit doors at least 1,000 mm wide, 2,000 mm in assembly buildings, at least 2,000 mm high, and openable from inside without a key (clause 4.4.2.4.1) BIS, NBC 2016 Part 4
- Stairs: built to 120 min, entered through a 120 min fire door, with no lift, electrical panel, gas pipe or duct opening into them (clause 4.4.2.4.3.2) BIS, NBC 2016 Part 4
- Stairs: no narrower than 1.25 m in flats, 1.50 m in hotels, schools and offices, and 2.00 m in hospitals and assembly halls (clause 4.4.2.4.3.2(e)) BIS, NBC 2016 Part 4
- Stairs: risers of at most 150 mm, 190 mm in A-2 homes, and no more than 12 to a flight (clause 4.4.2.4.3.1) BIS, NBC 2016 Part 4
- Stairs: a floor indication board of at least 300 mm by 200 mm inside each stair, on the wall nearest the fire door BIS, NBC 2016 Part 4
- Signs: green exit signs, lit on an alternative supply, with no point more than 30 m from a visible directional sign (clause 3.4.7.4) BIS, NBC 2016 Part 4
- Lighting: emergency lighting on an independent source, on within 5 s of a failure and lasting at least 90 min; battery packs do not replace a diesel-driven supply (clause 3.4.7.1) BIS, NBC 2016 Part 4
- Lighting: at least 10 lumen/m² on the centreline of escape routes, with luminaires at least 2 m up near exits, stair flights, call points and fire equipment BIS, NBC 2016 Part 4
- Compartments: floors divided into compartments of at most 750 m², or the larger sprinklered limits such as 3,000 m² for offices and 1,800 m² for hospitals, by 120 min barriers (clause 4.5.2) BIS, NBC 2016 Part 4
- Compartments: an opening in a fire wall no larger than 5.6 m² and no more than 2.75 m high or wide, closed by a 120 min door (clause 3.4.5.2) BIS, NBC 2016 Part 4
- Shafts: service shafts enclosed to 120 min with 120 min fire-stop around the cables, and electrical shafts sealed at every floor (clauses 3.4.5.4 and 3.4.6.1) BIS, NBC 2016 Part 4
- Smoke: lift lobbies with 120 min doors pressurised to 25 to 30 Pa where Table 6 asks, or the lift shaft to 50 Pa where there is no lobby BIS, NBC 2016 Part 4
- Power: emergency supply to fire pumps, pressurisation fans, fireman's lifts and all other lifts, exit signs and emergency lighting (clause 3.4.6.2) BIS, NBC 2016 Part 4
- Refuge: a refuge area in buildings over 24 m, at or just above 24 m and then every 15 m or so, unless every flat has a balcony (Annex E-4) BIS, NBC 2016 Part 4
- Refuge: 0.3 m² a person for two floors' occupants plus 0.9 m² per 200 for wheelchairs, never under 15 m², sprinklered, signed in letters of at least 75 mm and kept empty (Annex E-4) BIS, NBC 2016 Part 4
- Refuge: a first-aid box, extinguishers, a PA speaker, fireman's talk-back, emergency lighting and drinking water inside it (Annex E-4(f)) BIS, NBC 2016 Part 4
- Firefighting shaft: one per residential tower and school block, and per compartment of hospitals, offices and shops (Annex E-2) BIS, NBC 2016 Part 4
- Extinguishers: placed and serviced under IS 2190:2024 (DGCD item 6) DGCD, MHA
- Hose reels: run out fully once a year, giving at least 30 L/min at the highest reel and a jet of at least 6 m (MFS clause 8 B) MFS Form B guidelines
- Hydrants: isolating valves locked open and checked weekly; each quarter, 3 adjacent hydrants together give at least 1,125 L/min at 5.25 kgf/cm² (MFS clause 8 C) MFS Form B guidelines
- Hydrants: a hose box at every hydrant holding 2 lengths of hose and a branch pipe (DGCD item 11) DGCD, MHA
- Risers: in a hospital of ground plus 2 or more storeys, a wet riser where there are beds and a down-comer where there are none (DGCD items 9 and 10) DGCD, MHA
- Sprinklers: installation valve and gauges read every day, a discharge test every 6 months and the whole system flushed every year (MFS clause 8 D) MFS Form B guidelines
- Pumps: the main pump run for at least 5 minutes every day and the diesel pump started every week for 10 minutes, with fuel for 4 hours (MFS clause 8 E) MFS Form B guidelines
- Pumps: the pump house displays the flow measured at 7 kgf/cm² and at 4.5 kgf/cm² when the pumps were commissioned (MFS clause 8 E) MFS Form B guidelines
- Telangana: the certificate states both tank volumes in litres and confirms pumps of 2,280 LPM, electric and diesel, with a 180 LPM jockey TG fire circular 2020
- Detection: one device per zone triggered each week, at least 20% of devices tested each year, every device within 5 years, and 750 mm kept clear below each detector (MFS clause 8 F) MFS Form B guidelines
- Wireless detection in Maharashtra: only under clause 4.9 of IS 2189:2026, on licence-exempt bands such as 865 to 867 MHz, installed by a licensed agency, and not in high-rise buildings MFS circular 1420
- Electrical: no transformer or switchgear inside the building unless dry type, and an audit of the electrical load including DG sets (DGCD items 42 and 43) DGCD, MHA
- Electrical: lightning protection to IS/IEC 62305 (DGCD item 33) DGCD, MHA
- Records: a valid fire safety certificate on display, approved plans on site and a maintenance contract in force (DGCD items 30, 31 and 34) DGCD, MHA
- Records: maintenance log books up to date and a record of past fires and the action taken (DGCD items 35 and 37) DGCD, MHA
- People: an evacuation plan on every floor, marked assembly areas and a fire control room that holds the floor plans (DGCD items 45, 47 and 48) DGCD, MHA
- People: a mock drill with its attendance sheet, and exits and refuge areas free of obstruction, declared by the owner with each Maharashtra Form B MFS Form B guidelines
- Maharashtra section 45 buildings: the licensed auditor's 12 rule 33 duties, from ignition sources and storage compatibility to staff readiness, ending in a Form V Amendment Rules 2025
Means of egress on a fire audit checklist: NBC 2016 against NBCS 2026
Most buildings were approved under NBC 2016, but auditors now meet NBCS 2026 too. These 12 egress numbers show where the two agree and where the 2026 text is more generous.
| NBC 2016 Part 4 | NBCS 2026 Part F | |
|---|---|---|
| Travel distance, flats and hostels BIS, SP 7:2026 | 30 m; 45 m if fully sprinklered | 30 m; 60 m if sprinklered |
| Travel distance, schools BIS, SP 7:2026 | 30 m; 45 m if fully sprinklered | 30 m; 45 m if sprinklered |
| Travel distance, hospitals BIS, SP 7:2026 | 30 m; 45 m if fully sprinklered | 30 m; 45 m if sprinklered |
| Travel distance, offices BIS, SP 7:2026 | 30 m; 45 m if fully sprinklered | 30 m; 60 m if sprinklered |
| Travel distance, shops and malls BIS, SP 7:2026 | 30 m; 45 m if fully sprinklered | 30 m; 45 m if sprinklered |
| Travel distance, low and moderate hazard industry (G-1, G-2) BIS, NBC 2016 Part 4 | 45 m; 67.5 m if fully sprinklered | 45 m; 60 m if sprinklered |
| Travel distance, high hazard industry (G-3) BIS, SP 7:2026 | 22.5 m | 22.5 m; 45 m if sprinklered |
| Dead-end corridor BIS, SP 7:2026 | 6 m in schools, hospitals and assembly; 15 m elsewhere | The same: 6 m and 15 m |
| Distance to a visible exit sign BIS, SP 7:2026 | 30 m at most | 30 m at most |
| Emergency lighting BIS, SP 7:2026 | On within 5 s; at least 90 min | On within 5 s; at least 90 min |
| Stair width, flats and hospitals BIS, SP 7:2026 | 1.25 m for flats; 2.00 m for hospitals | 1.25 m for flats; 2.00 m for hospitals |
| Stair risers BIS, SP 7:2026 | 150 mm, 190 mm in A-2 homes; 12 to a flight | 150 mm, 175 mm in one or two family homes; up to 15 to a flight |
Type 1 and 2 construction. NBC 2016 has no sprinklered column: note 1 to its Table 5 adds 50% for a fully sprinklered building, which is how the sprinklered figures in the first column are worked out. NBCS 2026 Table 4 gives them in their own column and caps the common path of travel at half the distance. NBCS 2026 is voluntary unless your state adopts it.
Compartments, shafts, refuge areas and fire lifts: the passive part of a fire audit
Passive measures fail quietly: a wedged door or an unsealed shaft shows up only in a fire. These 9 stops follow a high-rise from the floor plate up to the refuge area.
1. The compartment wall
NBC 2016 clause 4.5.2 caps a compartment at 750 m², or more where sprinklered (3,000 m² for offices, 2,000 m² for shops), divided by 120 min barriers. BIS, NBC 2016 Part 4
2. The same wall in NBCS 2026
Table 6 allows 2,000 m² for sprinklered hospitals with beds, 3,000 m² for sprinklered hotels and offices, and 10,000 m² for sprinklered industrial sheds under 6.7 m; states may set their own. BIS, SP 7:2026
3. Doors in the wall
An opening of at most 5.6 m², closed by a 120 min fire door that carries a label with its rating, maker and month of manufacture. BIS, NBC 2016 Part 4
4. Service shafts
Cables and pipes run in shafts of 120 min; the electrical shaft is sealed at every floor with fire-stop of the floor's own rating, because an open shaft carries smoke between floors. BIS, NBC 2016 Part 4
5. The exit stair
A 120 min enclosure entered through a 120 min self-closing door, kept free of panels, ducts and stores, continuous to the ground. BIS, NBC 2016 Part 4
6. The lift lobby
Pressurised to 25 to 30 Pa behind 120 min doors where Table 6 asks; in a firefighting shaft the lobby must be pressurised unless naturally ventilated. BIS, NBC 2016 Part 4
7. The fireman's lift
On emergency power with the other lifts (clause 3.4.6.2), and in NBCS 2026 running down to the basements; Maharashtra's site checklist also asks whether every lift holds a valid licence to operate. MFS Form B guidelines
8. The refuge area
Above 24 m: on the outer edge, open to air on one side, sprinklered, with a sign in letters of at least 75 mm naming the refuge areas above and below. BIS, NBC 2016 Part 4
9. The way on from refuge
The refuge area opens into the firefighting shaft of stair, lobby and fireman's lift, so no one walks back through the floor they escaped. BIS, NBC 2016 Part 4
Fire audit checklist pass marks: 12 numbers from the official schedules
A checklist item is only testable if it has a number. These are the figures the official documents set, which the auditor measures against.
90 min
The least time emergency lighting must hold its light after mains failure (NBC 2016 clause 3.4.7.1(f)) BIS, NBC 2016 Part 4
5 s
The longest emergency lighting may take to come on BIS, NBC 2016 Part 4
30 L/min
Least flow at the highest hose reel in the yearly test, with a 6 m jet MFS Form B guidelines
1,125 L/min
Least quarterly output with 3 adjacent hydrants open, at 5.25 kgf/cm² MFS Form B guidelines
3.2 bar
Pressure the Maharashtra site checklist asks at the remotest hydrant point MFS Form B guidelines
3.5 bar
Least pressure NBCS 2026 sets at the highest and remotest hydrant, with 7 bar the most anywhere BIS, SP 7:2026
10 %
Loss of extinguisher cartridge mass or stored pressure that triggers a recharge MFS Form B guidelines
4 hours
Diesel fire pump running time the fuel tank must hold MFS Form B guidelines
750 mm
Clear radius to keep below every detector MFS Form B guidelines
2,280 LPM
Electric and diesel fire pump ratings on Telangana's certificate; the jockey is 180 LPM TG fire circular 2020
15 m²
Smallest refuge area allowed, however few people it serves BIS, NBC 2016 Part 4
25 to 30 Pa
Pressurisation of a lift lobby behind 120 min doors BIS, NBC 2016 Part 4
Fire audit checklist by frequency: from daily to every 5 years
An audit checks that the routine tests were done. Maharashtra's Form B guidelines of 7 July 2026 set the fullest official calendar, system by system.
Every day
Fire alarm panel shows normal, faults logged; sprinkler installation valve and gauges read; jockey pump cut-in tested; main pump run at least 5 minutes. MFS Form B guidelines
Every week
One detector or call point per zone triggered; hydrants looked over and isolating valves locked open; sprinkler gauges recorded and tanks full; diesel pump run 10 minutes. MFS Form B guidelines
Every month
Each hydrant valve opened to see clean water flow, washers checked and every hydrant kept reachable. MFS Form B guidelines
Every 3 months
Three adjacent hydrants flow-tested; sprinkler heads and alarm gong checked; detection batteries, sounders and panel functions tested; detectors cleaned. MFS Form B guidelines
Every 6 months
Sprinkler discharge test; landing, drain and isolation valves and the fire service inlet serviced; and in Maharashtra, Form B in January and July. MFS Form B guidelines
Every year
Hose reels run out and flow-tested; sprinkler pipework examined and flushed; at least 20% of detectors and sounders tested. MFS Form B guidelines
Every year, in January
Telangana's third-party certificate for flats over 30 m and under 45 m, offices, shops, schools and industry of 15 m to 30 m, and hotels up to 30 m. TG fire circular 2020
Every 2 years
Water stored-pressure extinguishers discharge-tested, and fire tanks cleaned at the latest, depending on the water. MFS Form B guidelines
Every 3 years
The detection system's electrical installation tested. MFS Form B guidelines
Every 5 years
Every detector and alarm device tested at least once. MFS Form B guidelines
IS codes on a fire audit checklist, and their current editions on 25 October 2026
An auditor checks against the current edition of each standard; Maharashtra's guidelines say so in terms. These 12 records were read on the BIS database on 25 October 2026.
- IS 2189:2026
- Selection, installation and maintenance of automatic fire detection and alarm systems; published 17 March 2026, the fifth revision. The 2008 edition was withdrawn on 17 September 2026. BIS standards database
- IS 2190:2024
- Selection, installation and maintenance of first-aid fire extinguishers; published 18 October 2024. The 2010 edition was withdrawn on 9 April 2025. BIS standards database
- IS 15683:2018
- Portable extinguishers, performance and construction; the 2006 edition was withdrawn on 20 May 2024. BIS standards database
- IS 16018:2012
- Wheeled fire extinguishers, current since 30 April 2013. BIS standards database
- IS 3844:1989
- Installation and maintenance of internal fire hydrants and hose reels; still current, valid to 20 June 2030. BIS standards database
- IS 13039:2014
- External hydrant systems, provision and maintenance; current. BIS standards database
- IS 15105:2021
- Design and installation of fixed automatic sprinkler systems; the 2002 edition was withdrawn on 14 March 2022. BIS standards database
- IS 15301:2003
- Installation and maintenance of fire fighting pumps; current. BIS standards database
- IS 9668:1990
- Provision and maintenance of water supplies for fire fighting; current. BIS standards database
- IS 3614:2021
- Fire doors and doorsets; its 1966 and 1992 parts were withdrawn on 14 March 2022. BIS standards database
- IS 12349:1988
- Fire protection safety signs; current, valid to 31 January 2027. BIS standards database
- IS 2175 and IS 11360
- The old heat and smoke detector specifications; both withdrawn on 18 July 2025, with no current edition. BIS standards database
Out-of-date standards printed on official fire audit checklists, and what to check instead
Two official lists still cite editions BIS has withdrawn or replaced. These 6 entries are the ones to correct before an audit is signed.
If The MFS Form B guidelines of 7 July 2026 list IS 2189:2008 for detection
BIS withdrew it on 17 September 2026, and MFS circular 1420 of 16 October 2026 tells authorities to hold detection to IS 2189:2026. MFS circular 1420
If The same guidelines list IS 2175 for heat detectors
Withdrawn on 18 July 2025 with IS 11360; there is no current edition to check against. BIS standards database
If The DGCD hospital checklist cites IS 884:1985 for hose reels
IS 884:2025 is the current edition on the BIS database. BIS standards database
If The DGCD hospital checklist lists IS 2189:2008 among its references
Check against IS 2189:2026, current on the BIS database since 17 March 2026. DGCD, MHA
If The MFS guidelines head pump maintenance "IS 13039"
IS 13039:2014 is the external hydrant code; pumps are IS 15301:2003, which the same guidelines also list. MFS Form B guidelines
If Both checklists rest on NBC 2016, withdrawn on 30 April 2026
Keep auditing against NBC 2016 where the approval was issued under it, and note the NBCS 2026 figure beside it. Gazette of India
Official fire audit checklists in India: 8 documents and what each covers
These are the official lists Flamekite found and read. None is a national legal format; each binds only where its issuer's law reaches.
MHA, DGCD
Hospital fire safety audit checklist
48 general items, then Categories A to D by height and plot area, from 23 to 64 items each, every item with its reference. Advisory to state fire services. DGCD, MHA
Maharashtra
Form B site inspection report
Clause 9 of the 7 July 2026 guidelines: extinguishers, tanks and 6 pumps, hydrants and sprinklers, passive measures and detection, ending in Form B to be issued or compliance needed. MFS Form B guidelines
Maharashtra
Form B test schedules
Clause 8: daily to 5-yearly tests for extinguishers, hose reels, hydrants, sprinklers, pumps and detection. MFS Form B guidelines
Maharashtra
Rule 33 auditor duties
12 duties of the licensed Fire and Life Safety Auditor for section 45 buildings, ending in a Fire Audit Report and Form V every 2 years. Amendment Rules 2025
Telangana
13-point third-party certificate
Each measure required as per NBC Part 4, marked working or not working, signed with the auditor's licence number. TG fire circular 2020
Delhi
Nursing home fire requirements sheet
2 staircases, a 6 m access road, sprinklers, a 75,000 to 1,50,000 litre underground tank and 1,620 L/min pumps. DFS
Chhattisgarh
Equipment by building type
The fire NOC portal's list of equipment for 9 occupancies, drawn from NBC Part 4 Table 7. CG Fire NOC
Ministry of Tourism
Hotel classification facilities
A valid fire NOC, trained staff with periodic drills, smoke detectors, visual and audible alarms and exit signs with backup power. Ministry of Tourism
Which fire audit checklist fits your building: hospital, hotel, school, factory or high-rise
Find your building below. The DGCD hospital list grows with height, from 23 items to 64 items.
If A hospital or nursing home under 15 m on a plot up to 1,000 m²
DGCD Category A: 23 items, including no flammable partitions or curtains and safe storage of oxygen cylinders. DGCD, MHA
If A hospital or nursing home under 15 m on a plot over 1,000 m²
DGCD Category B: 31 items, adding yard hydrants, call points, automatic detection and a separated electrical panel. DGCD, MHA
If A hospital or nursing home of 15 m to 24 m
DGCD Category C: 37 items, adding back-up power to fireman's lifts, fire compartmentation, an evacuation coordinator and a fire control room. DGCD, MHA
If A hospital above 24 m and up to 45 m
DGCD Category D: 64 items, adding a fire command centre staffed 24x7, ICU evacuation kits, oxygen leak detection, vertical evacuation drills and a refuge area. DGCD, MHA
If A hotel seeking a star classification
The Ministry of Tourism's facilities list on top of the fire NOC: trained staff, drills, smoke detectors, alarms and exit signs with backup power. Ministry of Tourism
If A school affiliated to CBSE
No CBSE fire list of its own: Circular 01/2022 asks for a valid fire safety certificate while the school operates, so the state's NBC-based items apply, with 6 m dead ends and 1.50 m stairs. CBSE
If A factory or workplace in Uttar Pradesh in a building of 5 floors or 20 m
OSH rule 12 makes NBCS 2026 Part F the checklist for fire emergencies, besides the fire NOC. OSH Code 2020 UP Gazette
If A factory in another state
The Factories Act's section 38 was repealed on 21 November 2025, but the state's factory rules under it continue until its OSH rules are final. OSH Code 2020 PIB
If A Telangana tower of flats of 45 m or more, a mall or a hospital above 15 m
The 13-point third-party certificate every January and July. Fire NOC Telangana TG fire circular 2020
Telangana's 13-point fire audit certificate and the line the auditor signs
Telangana's certificate is the shortest official checklist in India, and the only one that puts the auditor's own liability into the form.
Word for word
If any deviation found in the above report I may be held responsible
The 13 rows run from extinguishers, hose reels, risers and yard hydrants through sprinklers, manual and automatic alarms, both tanks and the pumps, to exit signs, 90-minute emergency lighting and fire shaft pressurisation, each "Required as per Part-4 of NBC" and marked working or not working. The form asks no measurement beyond tank litres and pump ratings: the flow, pressure and coverage tests in the sections above are what make each tick defensible.
Flamekite's practical fire audit checks beyond the rule text
Flamekite’s working from the official rules; no government publishes this figure.
Labelled as Flamekite's practice: each follows from a rule cited on this page, but none is written in an official checklist.
Do
- Test the hydrant on the top floor, not the ground floor: the rules measure pressure at the highest and remotest point. BIS, SP 7:2026
- Time the emergency lighting with a stopwatch from the moment the mains are cut; 5 s on and 90 min held are both testable. BIS, NBC 2016 Part 4
- Read the label on a sample of fire doors in each stair; a door without one cannot show its rating. BIS, NBC 2016 Part 4
- Compare the extinguisher, detector and hydrant counts in the log with what is on the wall, floor by floor. MFS Form B guidelines
- Re-measure travel distances wherever a floor has been partitioned since approval; new cabins lengthen the walk. BIS, NBC 2016 Part 4
- Write the clause beside every item marked not working, so the fix can be checked against the same rule. TG fire circular 2020
Don’t
- Don't accept a detector test done by the panel's test button alone; the schedule asks a device in each zone to be triggered. MFS Form B guidelines
- Don't let the maintenance agency audit the systems it maintains; Maharashtra called that arrangement contradictory in 2021. MFS order 417
- Don't treat stored furniture or a locked grille in a refuge area as minor; the rule says the area is always kept clear. BIS, NBC 2016 Part 4
- Don't sign off a wireless detection system in a high-rise in Maharashtra; the October 2026 circular says it does not suit one. MFS circular 1420
- Don't copy last year's figures into this year's report; every reading should come from this visit, with a dated photo. Amendment Rules 2025
- Don't cite a withdrawn IS edition in the report; check the BIS database on the day. BIS standards database
Fire audit checklist worked examples: 4 buildings and the list each gets
Flamekite's reading of the rules for 4 example buildings; the buildings are illustrations, the figures are the codes' and circulars'.
Case 1
An 80-bed hospital in Pune, 20 m
Institutional, ground plus 5, sprinklered.
What applies DGCD Category C, 37 items. Compartments up to 1,800 m² under NBC 2016 (2,000 m² under NBCS 2026), 2.00 m stairs, dead ends of 6 m at most, and Form B from its licensed agency every January and July. DGCD, MHA
Case 2
A 36 m tower of flats in Hyderabad
12 floors of 600 m², no balconies.
What applies A third-party certificate every January under the 2020 circular. Refuge at or just above 24 m: 600 ÷ 12.5 = 48 people a floor, 96 for two floors, × 0.3 m² = 28.8 m² plus 0.9 m² for wheelchairs, so about 29.7 m². BIS, NBC 2016 Part 4
Case 3
A 2,500 m² engineering shed in Kanpur, 6 m high
One storey, moderate hazard, not sprinklered.
What applies Under NBCS 2026 Table 6 an industrial shed under 6.7 m is split into compartments of 1,500 m² unless sprinklered (then 10,000 m²); NBC 2016 leaves this to the fire department. Travel distance 45 m. UP OSH rule 12 does not reach a 1-storey shed. BIS, SP 7:2026
Case 4
A 60-room hotel in Goa seeking 3 stars
Ground plus 4, about 15 m.
What applies The Ministry of Tourism's list: trained staff, drills, smoke detectors, visual and audible alarms, exit signs with backup power. Under NBC 2016, 1.50 m stairs and 30 m travel; NBCS 2026 compartments of 750 m², or 3,000 m² sprinklered. Ministry of Tourism
Fire audit checklist myths, checked against the documents
You may have read
There is one government fire audit checklist for all of India.
Myth
What the sources say
There is none in law. The DGCD's hospital list is advisory and says states may keep their own practice; each state's form decides. DGCD, MHA
You may have read
A clean Form B means the building passed a fire audit.
Myth
What the sources say
Form B certifies maintenance by the agency. Maharashtra's 2015 circular lists exits, ventilation, fire doors and fire load among what agency certificates do not cover. MFS circular 2015
You may have read
Battery emergency lights are enough in any building.
Myth
What the sources say
NBC 2016 clause 3.4.7.1(g) says battery packs may not be used in place of a diesel-driven emergency supply. BIS, NBC 2016 Part 4
You may have read
Wireless smoke detectors are accepted everywhere now.
Myth
What the sources say
Maharashtra accepts them under IS 2189:2026 clause 4.9, but names high-rise buildings and large industrial spaces as unsuitable. MFS circular 1420
You may have read
NBCS 2026 replaced NBC 2016 on every checklist.
Myth
What the sources say
NBCS 2026 is voluntary; only Assam had written it into its fire law by 24 October 2026, and buildings approved under NBC 2016 are audited against it. Assam Act XIII of 2026
Fire audit checklist changes in 2026: new editions and circulars
From news reports, not yet an official source.
Between March and October 2026 the detection code, the national building code and Maharashtra's test schedules all changed, so a checklist written before 2026 needs updating.
16 October 2026
MFS circular 1420 accepts wireless detectors under IS 2189:2026 clause 4.9 on licence-exempt bands, installed by licensed agencies, and not in high-rise buildings. MFS circular 1420
17 September 2026
BIS withdraws IS 2189:2008, leaving IS 2189:2026 as the only detection code. BIS standards database
7 July 2026
MFS issues Form B guidelines with test schedules and a site inspection checklist for licensed agencies. MFS Form B guidelines
30 April 2026
BIS establishes SP 7:2026 and withdraws NBC 2016 in the Gazette of India. Gazette of India
17 March 2026
BIS publishes IS 2189:2026, the fifth revision of the detection and alarm code. BIS standards database
Where to download the official fire audit checklists
These 6 official pages held the checklists and codes on 25 October 2026.
MHA, via MFS
DGCD hospital fire audit checklist
The 26-page hospital and nursing home checklist, Categories A to D DGCD, MHA
mahafireservice.gov.in/firestation/Fire%20Safety%20Audit%20Checklist%20for%20Hoospital%20issued%20by%20DGCD.pdfMaharashtra
MFS Form B guidelines
Test schedules and the site inspection checklist MFS Form B guidelines
mahafireservice.gov.in/circular/Guidelines%20to%20issue%20Form%20B.pdfMaharashtra
MFS circulars page
The wireless detection circular and the fire audit circulars from 2012 to 2026 MFS circular 1420
mahafireservice.gov.in/s-circular.phpTelangana
Telangana fire audit circular
The 13-point certificate and who files it, January or January and July TG fire circular 2020
fire.telangana.gov.in/home/Admin/ViewFileFTP?pdffilename=FireAudit_7.pdf&type=CircularsChhattisgarh
Chhattisgarh equipment checklist
Equipment needed by building type CG Fire NOC
firenoc.cg.gov.in/CheckList.aspxBIS
BIS standards database
Whether an IS edition is current or withdrawn BIS standards database
standards.bis.gov.in
What official fire audit checklists leave out, and what Flamekite could not confirm
No official checklist covers every system, and 4 documents Flamekite looked for were not available online.
The DGCD hospital list stops at 45 m: a taller hospital has no category of its own. It also carries no issue date in the copy hosted by the Maharashtra Fire Service, and it names a MoHFW circular on fire safety audits of 3 January 2020 that Flamekite did not find.
Fire lift specifications sit in NBC 2016 Part 8 and NBCS 2026 Part D, which Flamekite has not read, so this page's lift checks stop at emergency power, pressurisation and the lift licence. The NDMA's School Safety Policy (2016), which CBSE points schools to, is covered on the schools page: quarterly safety audits by the School Management Committee and drills preferably every six months.
The BIS standards themselves are sold, not published: where a clause number appears for an IS code, it is the one an official circular names, not Flamekite's reading of the standard.
| What | The rule | Source |
|---|---|---|
| DGCD hospital checklist date | Not printed in the hosted copy; file number VI-14022/09/2024-DGCD (F) | DGCD, MHA |
| Hospitals above 45 m | No DGCD category | DGCD, MHA |
| Hydrant pressure at the remotest point | Maharashtra's checklist asks over 3.2 bar; NBCS 2026 sets at least 3.5 bar. Both are shown; the approval's code decides | MFS Form B guidelines |
| Telangana Annexure IV | The owner's January and July certificate under G.O.Ms.No.15 of 2026 is not in the published 2-page copy | G.O.Ms.No.15 |
Questions about the fire audit checklist
What is a fire audit checklist?
- A list of every fire and life safety item an auditor checks, each tied to the rule that requires it: exits and stairs, compartments, refuge areas, extinguishers, hydrants, sprinklers, pumps, detection, emergency lighting and records. In India the items come from NBC Part 4, the IS code for each system and the state's own form.
Is there an official fire audit checklist in India?
- Not one national legal format. The Directorate General Fire Services published an advisory checklist for hospitals, Telangana prescribes a 13-point certificate, and Maharashtra's July 2026 guidelines carry a site inspection checklist. Each binds only where its issuer's law applies.
What is on a fire audit checklist for a hospital?
- The DGCD list starts with 48 general items, then grows by height: 23 items for a hospital under 15 m on a small plot, 31 on a larger plot, 37 from 15 m to 24 m and 64 above 24 m up to 45 m, adding oxygen safety, ICU evacuation kits and a 24x7 fire command centre.
How often should fire systems be tested?
- Maharashtra's 2026 schedule runs from daily panel and pump checks, through weekly detector and diesel pump tests and quarterly hydrant flow tests, to yearly hose reel tests, at least 20% of detectors each year and every detector within 5 years.
Should a fire audit in 2026 follow NBC 2016 or NBCS 2026?
- The code your fire approval was issued under, which for most buildings is NBC 2016 Part 4. BIS withdrew it on 30 April 2026, but NBCS 2026 is voluntary unless your state adopts it; Uttar Pradesh's OSH rule 12 already applies it to large workplaces.
Is IS 2189:2008 still valid for fire alarm systems?
- No. BIS withdrew IS 2189:2008 on 17 September 2026; IS 2189:2026, published on 17 March 2026, is the current detection and alarm code, and Maharashtra's October 2026 circular holds detection systems to it.
Can a building owner use this checklist instead of an auditor?
- Only to prepare. Where a state requires an audit, a licensed or empanelled auditor must sign it, such as Maharashtra's Form V or Telangana's licence-numbered certificate; the owner's own declarations, like the Form B covering letter, carry legal liability of their own.
Keep reading
- Fire auditWhat a fire audit is, and which states require one, how often.
- Fire NOC for schoolsCBSE's fire safety certificate, NDMA audits and drills, and the NOC line by state.
- Third-party fire auditWho may sign the audit in each state, and how auditors are chosen.
- Fire audit consultantsHave the audit your state requires arranged with an auditor it accepts.
- National Building Code 2026What NBCS 2026 changed from NBC 2016, and who has adopted it.
- Form B fireMaharashtra's January and July maintenance certificate and its test photographs.
- OSH Code 2020 and fire safetyFire duties in factories after the Factories Act was repealed.
- Free fire NOC checkCheck whether your building needs a fire NOC at all.
Words on this page, explained
Keep exploring
More in Fire Audit
Sources
Each source was opened and read on the date shown. How Flamekite checks its sources
- Directorate General Fire Services, Civil Defence and Home Guards, Ministry of Home Affairs (copy hosted by Maharashtra Fire and Emergency Services): Fire Safety Audit Checklist Advisory for Hospitals / Nursing Homes, F. No. VI-14022/09/2024-DGCD (F): general measures (48 items) and Categories A to D (23, 31, 37 and 64 items), 26 pages (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clauses 3.4.5, 3.4.6.2, 3.4.7, 4.4.2 (Tables 4 and 5), 4.4.2.5 (Table 6), 4.5.2 and Annex E (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)
- Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)
- Director General, Telangana State Disaster Response and Fire Services: Circular Memorandum Rc.No.6402/MSB/2019, 28 January 2020: conducting of fire audit in all high-rise and non-high-rise buildings; third-party certificate uploaded every January, or every January and July, by height and use, with the 13-point certificate format (read from the page images) (opens in a new tab)
- Bureau of Indian Standards, Know Your Standards database: Status records read 25 October 2026 for IS 2189, IS 2190, IS 15683, IS 16018, IS 3844, IS 13039, IS 15105, IS 15301, IS 9668, IS 12349, IS 3614, IS 2175 and IS 11360 (current or withdrawn, with dates) (opens in a new tab)
Show all 20 sourcesShow fewer
- Central Board of Secondary Education: Circular No. 01/2022, 5 January 2022: safety of children in schools (valid building safety and fire safety certificates) (opens in a new tab)
- Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)
- Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)
- Uttar Pradesh Gazette Extraordinary, 27 August 2026, English translation (copy hosted by TeamLease RegTech): Uttar Pradesh Occupational Safety, Health and Working Conditions Rules, 2026, Notification No. 962/XXXVI-03-2026-1903305: rules 12, 16, 43, 45, 46, 47 and 127 (opens in a new tab)
- Urban Development Department, Government of Maharashtra (copy hosted by MFS): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Rules, 2025, Notification No. MFS-2023/C.R.370/UD-14, 12 June 2025 (opens in a new tab)
- Maharashtra Fire and Emergency Services: Circular No. MFS-2026/1420, 16 October 2026: Wireless Detection System, under IS 2189:2026 clause 4.9 (number and date read from the page image) (opens in a new tab)
- Bureau of Indian Standards, Know Your Standards database: Status records for IS 3844:1989, IS 9668:1990, IS 13039:2014, IS 15301:2003, IS 5290:2025, IS 884:2025, IS 636:2018, IS 15105:2021, IS 1641:2013 and IS 8757:2021 (current or withdrawn, publication and validity dates) (opens in a new tab)
- Delhi Fire Service: Fire safety requirements for nursing homes (scanned sheet, page dated 23 January 2025) (opens in a new tab)
- Fire and Emergency Services and SDRF, Chhattisgarh: Equipment needed for a NOC by building type: 9 occupancies, with NBC Part 4 Table 7 (opens in a new tab)
- Ministry of Tourism, Government of India: Revised guidelines for approval of hotels at project stage and star classification, No. 8-TI-I-1(3)/2013-PI-1 (opens in a new tab)
- Press Information Bureau: Four Labour Codes made effective from 21 November 2025, with the transition statement (opens in a new tab)
- Maharashtra Fire and Emergency Services: Office Order No. MFS/51/2021/417, 12 April 2021: fire safety audit of various vulnerable occupancies (read from the page images) (opens in a new tab)
- Fire Adviser, Government of Maharashtra (Maharashtra Fire Services): Circular No. MFS/2015/10/1462, 16 September 2015, "Regarding Fire Audit": the licensed agency's Form B against a Fire Risk Audit, advised at least once a year for high-rise and other special buildings (read from the page images) (opens in a new tab)
- Government of Telangana, Home (Services.IV) Department: G.O.Ms.No.15, 20 January 2026: empanelment of Third-Party Fire and Life Safety Auditors and Fire and Life Safety System Integrators (opens in a new tab)