Fire NOC for a cold storage: licences, ammonia rules, state lines and steps
Updated By Flamekite Editorial DeskFacts checked against official sources on
Quick answer
A cold storage is NBC Group H storage, kept below 15 m. Delhi wants a fire NOC above 250 m²; UP and West Bengal also license cold stores under their own Acts.
Both national codes list cold storage premises as moderate hazard. Above 250 m² a single-floor store needs a wet riser, yard hydrant, sprinklers, detection and a 50,000 litre tank under NBC 2016 Table 7, and the ammonia plant brings its own rules: detectors, a water curtain round the receiver and drills every quarter in Telangana.
Free, on WhatsApp. Or set a renewal reminder
Fire NOC for a cold storage at a glance: 10 facts
| What | The rule | Source |
|---|---|---|
| Code class | Group H storage: NBC 2016 clause 3.1.9 names cold storages beside warehouses and freight depots; NBCS 2026 keeps the wording | BIS, NBC 2016 Part 4 |
| Hazard class | Cold storage premises are moderate hazard in NBC 2016 Annex B; NBCS 2026 adds cold freezer rooms to its G2 column | BIS, NBC 2016 Part 4 |
| Height cap | No Group H building above 15 m (NBC 2016 Table 7, Note 20); Maharashtra allows up to 24 m, Haryana 21 m | NBC 2016, Part 4 |
| Smallest state line | Tripura's full route above 200 m²; Delhi, Rajasthan, Gujarat, Chhattisgarh, Manipur and Nagaland above 250 m² | Directorate of Fire and Emergency Services, Tripura |
| Uttar Pradesh | Every storage building needs the fire certificate (s.26(3)), for 3 years; the cold store also needs a licence under the 1976 Act | UP Act 16 of 2022 |
| West Bengal | Cold storage licence for 5 years under the 1966 Act; a single-floor store up to 9 m and 500 m² self-certifies fire safety yearly on Form-12 | WB Cold Storage Act |
| Insurance by law | UP s.23: stored produce insured against fire; West Bengal s.15: the building, machinery and produce | WB Cold Storage Act |
| Ammonia | MSIHC Rules 1989: 50 t and 500 t in Schedule 3, 60 t and 600 t in Schedule 2 | MSIHC Rules 1989 |
| Indian Standard | IS 3594:2024, fire safety of general storage and warehousing including cold storages, second revision | BIS |
| Last verified | 25 October 2026, against each instrument named on this page | Not stated |
Cold storage fire NOC lines in 27 states and UTs, from the instruments
| Option | When a storage building is covered | Term or filing | Instrument | Source |
|---|---|---|---|---|
| Delhi | Storage over 250 m² of covered area on all floors, at any height | 3 years until 20 May 2027 | DFS Rules 2010, Rule 27 as substituted on 26 May 2026 | DFS |
| Uttar Pradesh | Every storage building, any size; storage above 15 m not permitted | 3 years (Rule 44) | Act 16 of 2022, s.26(3); Rules 2024; plus the 1976 cold storage licence | UP Rules 2024 |
| West Bengal | Single-floor warehouses and cold storages up to 9 m and 500 m² self-certify instead of an FSR and FSC | Self-certification every year | Notification 1930 of 1 March 2024, Form-12; plus the 1966 cold storage licence | WB notification 1930 |
| Maharashtra | Schedule-I storage rows from below 15 m and under 1,000 m²; storage permitted up to 24 m | No renewal: Form B every January and July | Act of 2006, s.3(1C) and Schedule-I as substituted in 2023 | MH Act 2023 Schedule-I |
| Gujarat | Godowns and warehouses over 250 m² under 15 m | 3 years, then 2 years for each renewal | Fire Regulations 2023, Third Schedule | Gujarat Fire Safety Compliance Portal |
| Rajasthan | Storage over 250 m² | Generally every year, on the fee | UDH joint order of 14 September 2023, Table 1 | Rajasthan UDH |
| Haryana | Storage with more than 500 m² on any floor; storage buildings capped at 21 m | 3 years | Act 14 of 2022, s.18 | Government of Haryana |
| Chandigarh | More than 500 m² on any floor | 5 years since 6 May 2026 | Haryana Act 2022 as extended by S.O. 2264(E) | Gazette of India |
| Bihar | 15 m or more, or any floor over 500 m² | 3 years; 2 if classed hazardous | Fire Service Rules 2021, rule 15; Schedule C | Bihar Rules 2021 |
| Chhattisgarh | Storage above 250 m² on all floors | Moderate risk: 2 years | s.14(1) notification of 29 November 2022; HQ order of 16 October 2025 | Fire and Emergency Services and SDRF, Chhattisgarh |
| Odisha | Warehouses and storage of 500 m² built-up or more | 2 years | Amendment Rules 2019, rule 9(1); Order 50908 of 2019 | Odisha Rules 2019 |
| Manipur | Storage more than 250 m² covered on all floors | 3 years (s.25(2)) | Act 9 of 2026, in force 14 September 2026 | Government of Manipur |
| Nagaland | Storage more than 250 m² covered on all floors | 2 years | Act 5 of 2023, s.21(1) and s.24(3) | Directorate of Fire and Emergency Services, Nagaland |
| Himachal Pradesh | Storage over 250 m² covered, in the precautions list | Not set | Section 9 notification of 23 July 2019 | Department of Fire Services, Himachal Pradesh |
| Tripura | Storage above 10 m or above 200 m² takes the full route | Not read for this page | Fire Safety Rules 2026, rules 6 and 7 | Directorate of Fire and Emergency Services, Tripura |
| Meghalaya | Storage over 500 m² covered, or over 15 m | Renewal fee Rs 2,000 | Building Bye-Laws 2021, A2.59; fee Annex B | Bye-Laws 2021 |
| Arunachal Pradesh | Storage with more than 500 m² on any one floor | Not set | Building Bye-Laws 2019, bye-law 11.1(b) | AP Building Bye-Laws 2019 |
| Andhra Pradesh | Storage with more than 500 m² on any one floor | Set by occupancy; not read for storage | Fire Service Act 1999, s.13(1) as amended in 2026 | Andhra Pradesh Legislative Assembly |
| Kerala | H storage over 1,000 m² or over 15 m; 300 to 1,000 m² file a self-declaration | 5 years for non-hazardous occupancies, 2 for hazardous industry and storage | Municipality Building Rules 2019, rule 5(4); G.O.(Ms)No.143/2025/Home | KMBR 2019 |
| Telangana | Storage above 15 m | Medium risk (R3): random inspection twice in 5 years | Circular of 5 March 2016 | TSDRFS circular 2016 |
| Karnataka | 21 m or more, any use | No official period published | Fire Force Act 1964, s.13(3), from 24 March 2023 | Government of Karnataka |
| Tamil Nadu | Warehouses in the DTCP list at any height; above 18.3 m the Director's NOC | Not read for this page | TNCDBR 2019; DTCP planning permission checklist | TNSWP |
| Goa | Godowns at any size | Not read for this page | Section 13 notification of 17 December 2014 | DFES Goa charter |
| Sikkim | Every storage building | 3 years for buildings other than homes and hotels (rule 30) | Act 4 of 2023, s.24(3); Rules 2025 | Sikkim F&ES Rules 2025 |
| Assam | Storage and godowns at any size; ammonia storage and handling files Form II | Valid until cancelled | Act LIII of 2025, s.20(1); Sewa Setu forms | Assam Act LIII of 2025 |
| Jammu and Kashmir | Cold storage is named in use class C3, which is in the fire NOC list | Not published | Unified Building Bye-Laws 2021, clause 2.18(2) | J&K Gazette |
| Dadra and Nagar Haveli and Daman and Diu | Storage at any size | Not read for this page | Regulation 6 of 2026, s.29(2), in force 7 July 2026 | Gazette of India Extraordinary |
How to get a fire NOC and licence for a cold storage: 9 steps
Settle the class: Group H, moderate hazard
A cold store is Group H. Check the ammonia: NBC 2016 puts buildings storing ammonia under pressure in quantities over 70 m³ in Group J, the hazardous group.
Keep the building under the state's height cap
15 m under NBC 2016 and in Uttar Pradesh, 21 m in Haryana, 24 m in Maharashtra subject to local fire-fighting facilities.
Take the cold storage construction permission
Uttar Pradesh (s.9 of the 1976 Act) and West Bengal (s.2A of the 1966 Act) bar building a new cold store without the Licensing Officer's prior permission.
Size the fire systems by floor area and storeys
NBC 2016 Table 7 changes at 250 m² and at each added floor; Maharashtra changes at 1,000 m²; NBCS 2026 at 500, 1,000 and 2,000 m² and for racks.
Choose and detail the insulation
Line both faces of any combustible lining to the required flame spread class, fit pressure relief ports in panel chambers, and keep panel joints sealed as NHB's standard sets out.
Engineer the ammonia plant for a leak and a fire
Detectors in the machine room and chamber vestibules, a water curtain round the receiver, relief valves piped to a scrubber, and automatic isolation of the charge in a fire.
Apply for the fire certificate before you store
Apply on the state portal once the systems are installed and tested; the fire documents list and the online apply page show what each state asks.
Take the cold storage licence and the insurance
UP's s.5 and West Bengal's s.3 bar the business without a licence; UP's s.23 and West Bengal's s.15 make fire insurance a duty of the licensee.
Diary renewals, filings and drills
West Bengal's licence renewal goes in 45 days before expiry; Maharashtra files Form B each January and July; Telangana's alert wants ammonia drills every quarter.
Where a cold storage sits in the fire codes: Group H, G2 and J
Both codes put a cold store in Group H, storage, and their hazard tables call it moderate hazard. The ammonia that cools it can pull a building into Group J.
- Group H, NBC 2016 clause 3.1.9
- Buildings used mainly to store goods, vehicles or animals, with cold storages named among the examples. A new use that brings many more people in, such as offices, changes the class. BIS, NBC 2016 Part 4
- Group H, NBCS 2026
- The 2026 standard repeats the definition and the cold storage example word for word in substance. It is voluntary; only Assam had written NBCS 2026 into its fire law by 24 October 2026. BIS, SP 7:2026
- Moderate hazard, NBC 2016 Annex B
- "Cold Storage Premises" sit in the moderate hazard column, beside cork, coir and dry cleaning, read off the page image. BIS, NBC 2016 Part 4
- G2, NBCS 2026 Annex B
- "Cold storage premises" and "Cold Freezer Room" both sit in the G2 moderate hazard column of the 2026 table. BIS, SP 7:2026
- Group J, clause 3.1.10(a)
- Hazardous buildings include those storing gases such as ammonia under a pressure above 0.1 N/mm² in quantities over 70 m³. The clause does not say how a refrigeration charge is counted. BIS, NBC 2016 Part 4
- Fire Zone No. 3
- NBC 2016 groups storage buildings with high hazard industry and hazardous uses in the third fire zone of a planned city. BIS, NBC 2016 Part 4
- Cold storage, UP Act 1976
- An enclosed chamber insulated and cooled by refrigeration machinery for farm produce; cabinets and chilling plants under 100 m³ are left out. LawGistnews report
- Industrial building, Maharashtra Schedule II
- The fee schedule counts Group H storage, Group G industry and Group J hazardous buildings as industrial, at 0.75% of the Annual Statement of Rates up to 45 m. MH Act 2023 Schedule II
Cold storage fire systems by size: NBC 2016, NBCS 2026 and Maharashtra
A cold store's plant grows with its covered area and storeys. The NBC 2016 and Maharashtra rows were read off their page images; the NBCS rows are its protection levels HL-4 to CL-7.
| Wet riser | Yard hydrant | Sprinklers | Detection | Underground tank | Pumps | |
|---|---|---|---|---|---|---|
| NBC 2016, below 15 m, under 250 m² NBC 2016, Part 4 | No | No | Yes | No | None; 25,000 litre terrace tank | 900 litres a minute at the terrace |
| NBC 2016, over 250 m², ground floor only NBC 2016, Part 4 | Yes | Yes | Yes | Yes, with manual alarm | 50,000 litres | 1,620 litre a minute set (Note 14) |
| NBC 2016, over 250 m², ground plus one NBC 2016, Part 4 | Yes | Yes | Yes | Yes, with manual alarm | 75,000 litres | 2,280 litre a minute set (Note 10) |
| NBC 2016, over 250 m², more floors NBC 2016, Part 4 | Yes | Yes | Yes | Yes, with manual alarm | 1,00,000 litres | 2,280 litre a minute set (Note 10) |
| NBCS 2026, up to 500 m² (HL-4) BIS, SP 7:2026 | Yes | No | No | Yes | By hydraulic calculation | By hydraulic calculation |
| NBCS 2026, 501 to 1,000 m² (HL-5) BIS, SP 7:2026 | Yes | Yes | No | Yes | By hydraulic calculation | By hydraulic calculation |
| NBCS 2026, 1,001 to 2,000 m² (CL-6) BIS, SP 7:2026 | Down-comer instead | Yes | Yes | Yes | By hydraulic calculation | By hydraulic calculation |
| NBCS 2026, over 2,001 m², ridge to 9 m, or racks (CL-7) BIS, SP 7:2026 | Yes | Yes | Yes | Yes, with voice evacuation | By hydraulic calculation | By hydraulic calculation |
| Maharashtra, below 15 m, under 1,000 m² MH Act 2023 Schedule-I | Yes | No | Basement over 200 m² only (Note 4) | No | 50,000 litres | 1,620 litre a minute set (Note 14) |
| Maharashtra, over 1,000 m², or 15 m to 24 m MH Act 2023 Schedule-I | By Note 18 | By Note 18 | By Note 18 | By Note 18 | By Indian Standard design | By Indian Standard design |
Every row also asks for extinguishers and first-aid hose reels. Maharashtra's Note 18 asks the whole occupancy to be protected by hydrants, sprinklers, spray, mist, gas, foam and alarms as the Indian Standards apply, and Note 21(b) asks another agent where water is unsuitable. NBCS 2026 Remark 1 recommends a dry riser where the ambient temperature is below 4 °C, which fits a freezer block. The general warehouse grid, with multi-level car parks, is on the warehouse page.
Cold storage height, exit and water limits in 12 numbers
These are the figures the codes and state Acts set for storage buildings, read off the page images where marked in the sources.
15 m
Highest Group H building NBC 2016 permits (Table 7, Note 20); Uttar Pradesh repeats it NBC 2016, Part 4
21 m
Highest storage building Haryana's 2022 Act permits Government of Haryana
24 m
Highest storage building Maharashtra permits, subject to local fire-fighting facilities (Notes 3(c) and 3(g)) MH Act 2023 Schedule-I
30 m²
Floor area per person used to work out a storage building's occupant load (NBC 2016 Table 3) BIS, NBC 2016 Part 4
30 m
Longest travel to an exit in a storage building of construction Types 1 and 2 (NBC 2016 Table 5); 50% more if fully sprinklered BIS, NBC 2016 Part 4
90 m
Travel distance NBCS 2026 allows in a sprinklered storage building BIS, SP 7:2026
1,400 m²
Gross area above which a storage space needs 2 exit doors, unlocked while anyone is inside (clause 6.8.1.2) BIS, NBC 2016 Part 4
10 persons
Normally present: the other trigger for those 2 exit doors BIS, NBC 2016 Part 4
150 mm
Size of the fire mains for storage buildings up to 15 m (NBC 2016 Table 8) BIS, NBC 2016 Part 4
4 °C
Ambient temperature below which NBCS 2026 recommends a dry riser BIS, SP 7:2026
41.8 MJ/kg
Calorific value of polystyrene in NBCS 2026 Table 12; polyurethane 35.2 BIS, SP 7:2026
100 m³
Chilling plants smaller than this are not a cold storage under the UP Act LawGistnews report
The cold storage licence beside the fire NOC: 6 regimes
A cold store answers to a licensing officer as well as the fire service. These are the regimes Flamekite read, with what each asks about fire.
Uttar Pradesh, Act 11 of 1976
Licence from the Director of Horticulture
No cold storage business without a licence (s.5); no new store built without prior permission (s.9); refusal if the store does not meet prescribed specifications (s.6); stored produce insured against fire (s.23). Read from a legal database copy. LawGistnews report
West Bengal, Act VI of 1966
Licence for 5 years from the Director of Agriculture
Valid 5 years, renewed 2 years at a time on a fee of up to Rs 200, applied 45 days before expiry; District Magistrates may be empowered; the building, machinery and produce insured as the Licensing Officer decides. WB Cold Storage Act
Bihar, Act of 1992
Bihar State Regulation of Cold Storages Act
Its section 40(b) lets the officer inspect a cold storage, its machinery and records. Its licence terms were not read for this page. Indian Kanoonnews report
WDRA, circular of 27 April 2017
Warehouse registration for a cold store
A registered cold storage may also insure stock lost to a power failure and plant and machinery damaged by fire; the 2019 procedure asks a basic data sheet and proof of the technical standards it was built to. WDRA circular 1/2017
NHB subsidy
Capital investment subsidy
40% of capital cost, 55% in hilly and scheduled areas, up to 5,000 MT a project, for stores with a safety system against fire and refrigerant leaks built to the notified technical standards. NHB subsidy
Assam, Sewa Setu
A fire form for ammonia
Form II covers the storage and handling of gases including ammonia; Form III covers godowns. Flamekite did not find which of the 2 forms Assam applies to a cold store with an ammonia plant. Sewa Setu Assam
What West Bengal's 1966 Act says about insuring a cold storage
Section 15 of the West Bengal Act makes insurance of the whole cold store a legal duty. Read off the page image of the Act as amended in 1978.
Word for word
Cold storage building, cold storage machinery and the agricultural produce stored in a cold storage shall be insured against such items of risks and with such Insurance Company or Companies as may be determined by the Licensing Officer from time to time
The proviso makes the hirer pay a pro-rata premium on the produce alone. Uttar Pradesh's section 23 is narrower: the licensee insures the stored produce against fire and breakdown, and says nothing of the building. Neither Act names a fire certificate; Flamekite did not find either state's cold storage Rules, where a fire condition could sit.
4 fire rules that tie a cold storage licence to the fire certificate
Four states' fire rules name cold storage among the licences that fall with the fire certificate. In each, a cancelled certificate goes to the licensing authority.
Uttar Pradesh: rule 46 of 2024
After a show-cause notice within 24 hours and 15 days to reply, the fire officer reports to the licensing authority to cancel the licence of a cold storage, among others; sealing under rule 47 follows if it does not act. UP Rules 2024
Odisha: Order 50908 of 2019
An officer who cancels a certificate reports to the licensing authority for cinema, clinic, factory, hotel, warehouse and cold storage licences; prosecution needs sanction. Order 50908 of 2019
Sikkim: rule 32 of 2025
The same show-cause steps, 24 hours and 15 days, then a Form A16 report to the licensing authority of the cold storage. Sikkim F&ES Rules 2025
Chhattisgarh: rule 35 of 2021
No authority may issue or renew a licence for a warehouse or cold store without working fire systems and a valid fire certificate. CG Gazette
Ammonia plant safety in a cold storage: 12 points from the rules
Telangana's Directorate of Factories issued Safety Alert 10/2026 in June 2026 for cold storage units with ammonia chilling plants; NHB's 2010 standard and the MSIHC Rules add the rest.
- Ammonia is a listed hazardous chemical: the MSIHC Rules set 50 t and 500 t in Schedule 3 and 60 t and 600 t in Schedule 2, counting installations of one occupier less than 500 m apart. MSIHC Rules 1989
- Fit fixed ammonia detectors in the machine room, the cold chamber vestibules, the control room and the condenser area, alarming in sound and light outside the room. Telangana Factories
- Calibrate the gas detectors every 6 months and keep the records. Telangana Factories
- Put a water curtain round the ammonia receivers; NHB's standard also asks sprinklers over high-pressure receivers. Telangana Factories
- Pipe relief valve discharge to a water absorption or scrubber tank, never to open air or an occupied area; NHB asks a safety release to a water sump. Telangana Factories
- Test relief valves every 12 months and after any release; pressure or leak test the pipelines at least every 3 years. Telangana Factories
- Provide emergency shut-off valves on the main receivers and suction headers, and automatic isolation of the refrigerant charge in a fire. Telangana Factories
- Keep at least 2 self-contained breathing sets with spare cylinders outside the compressor room, and inspect the PPE every 6 months. Telangana Factories
- Run ammonia mock drills at least once a quarter, announced and unannounced, and record what went wrong. Telangana Factories
- Keep a written on-site emergency plan where MSIHC rule 13 applies, or an emergency response procedure, agreed with the local fire brigade and hospital. Telangana Factories
- Fit fire sensors in the chambers and machine room, emergency ventilation for the machine room, and alarm switches near every cold store door (NHB-CS-Type 01-2010). NHB standards
- Run the self-inspection checklist at least every 3 months: 14 items from vessel certificates to colour-coded piping. Telangana Factories
PUF and EPS insulated panels in a cold storage: 5 dos and 4 don'ts
The codes do not name PUF or EPS panels, so these lines come from the clauses that govern combustible linings and from NHB's cold storage standard. Each line names its source.
Do
- Make both faces of a combustible lining meet the flame spread class the location needs: the codes warn that fire spreads unseen in a concealed cavity (NBCS 2026, 3.5.10.5). BIS, SP 7:2026
- Fit enough pressure relief ports on every insulated panel chamber (NHB-CS-Type 01-2010). NHB standards
- Seal panel joints with cam locks or tongue and groove, and flash every concrete and wall to ceiling joint inside and out (NHB). NHB standards
- Count the insulation in the fire load: polystyrene carries 41.8 and polyurethane 35.2 thousand kJ per kg, 2.38 and 2.00 times wood (NBCS 2026, Table 12). BIS, SP 7:2026
- Protect any combustible storage, packing, fuel or boiler area in a storage building to level CL-6 (NBCS 2026, Table 7H Note 1). BIS, SP 7:2026
Don’t
- Don't use Class 2 surfaces on walls, staircases or corridors; only Class 1 may go anywhere (NBCS 2026, 3.5.10.3). BIS, SP 7:2026
- Don't wrap duct insulation in combustible material; insulation for ducts should be non-combustible (NBCS 2026, 3.5.7.3.5). BIS, SP 7:2026
- Don't treat the 150 mm EPS or 100 mm PUF wall in NHB's table as a fire rating: it is a thermal thickness for a U value of 0.27 W/m²K. NHB standards
- Don't rely on sprinklers alone where the stored goods react with water: Maharashtra's Note 21(b) asks a suitable other agent. MH Act 2023 Schedule-I
Does your cold storage need a fire NOC? 11 cases
Find the first line that fits your store. Crossing any one test in your state is enough, and the cold storage licence is a separate question.
If Uttar Pradesh, any cold store
Yes: s.26(3) lists every storage building without a size line, and the 1976 Act needs a licence too. Fire NOC UP UP Act 16 of 2022
If Delhi, over 250 m² across all floors
Yes, at any height, under Rule 27. Fire NOC Delhi DFS
If Gujarat, over 250 m² and under 15 m
Yes: godowns and warehouses over 250 m² are in the Third Schedule. Fire NOC Gujarat Gujarat Fire Safety Compliance Portal
If Rajasthan, Chhattisgarh, Manipur or Nagaland, over 250 m²
Yes; Chhattisgarh counts all floors and gives a 2-year certificate. Fire NOC Chhattisgarh Fire and Emergency Services and SDRF, Chhattisgarh
If Tripura, above 10 m or 200 m²
Yes, by the full route under the 2026 Rules. Fire NOC Tripura 2026 Directorate of Fire and Emergency Services, Tripura
If Haryana, Bihar, Arunachal or Andhra Pradesh, a floor over 500 m²
Yes as a special building, at any height; Bihar also at 15 m. Fire NOC Haryana Government of Haryana
If Odisha, 500 m² built-up
Yes, with a 2-year certificate under Order 50908 of 2019. Fire NOC Odisha Order 50908 of 2019
If West Bengal, one floor up to 9 m and 500 m²
No FSR or FSC: a yearly Form-12 self-certification on e-District, plus the cold storage licence. Fire NOC West Bengal WB notification 1930
If Kerala, 300 to 1,000 m² and up to 15 m
An Appendix L self-declaration with a copy to the fire station; above 1,000 m² a fire NOC. Fire NOC Kerala KMBR 2019
If Telangana, up to 15 m
No fire NOC under the 2016 line, but a factory's ammonia plant still answers to the 2026 factories alert. Fire NOC Telangana TSDRFS circular 2016
If Below every line in your state
No certificate, but NBC 2016 still asks a store under 250 m² for extinguishers, hose reels, sprinklers and a 25,000 litre terrace tank. Do I need a fire NOC? NBC 2016, Part 4
Cold storage fire NOC fees in 8 official schedules
Storage pays by floor area where a state publishes a rate. Each line is from an official schedule; consultants' charges and the cold storage licence fee are separate.
As published
- Bihar, storage, industrial and hazardousRs 10 per m²Provisional NOC; Rs 5 per m² for the final NOC and each renewal (Schedule C) BFS fee PDF
- Meghalaya, H: warehouses, cold storage, depotsRs 6 per m²Renewal Rs 2,000 Meghalaya F&ES
- Chandigarh, industrial and storageRs 12 per m²Or Rs 6,615, whichever is more (Office Order 23) MCC Office Order 23
- TelanganaRs 10 per m²Of total built-up area (G.O.Ms.No.142 of 2016) G.O.Ms.No.142
- Rajasthan, Nagar Nigam areaRs 2 per sq ftRs 1.50 in a Nagar Parishad, Rs 1 in a Nagar Palika Rajasthan UDH
- Maharashtra, industrial including Group H, up to 45 m0.75% of the ASR per m²1.00% above 45 m MH Act 2023 Schedule II
- Assam, storage: warehouses and godownsRs 1,500 to Rs 3,000By height (under or over 15 m) and area (to 250, to 500, over 500 m²) Assam fee Annexure A
- Uttar PradeshNilThe UP fire service dashboard lists no fee UP Fire dashboard
West Bengal's cold storage licence fee is capped by the 1966 Act at Rs 500 to apply and Rs 200 to renew. Every state's fire NOC rate is on the fees page.
What a cold storage risks without its licence or fire certificate: 9 penalties
Two sets of law apply: the cold storage Act and the fire Act. Each line names the law that sets it.
| Offence | Penalty | Law |
|---|---|---|
| Breaking the UP cold storage Act, its rules or an order | Up to 2 years or a fine up to Rs 10,000 or both; cognizable | UP Act 11 of 1976, ss.37 and 39 (legal database copy) LawGistnews report |
| Running a West Bengal cold store without a valid licence | Up to 6 months or a fine up to Rs 1,000 or both, plus Rs 50 a day | West Bengal Act VI of 1966, s.21(1) WB Cold Storage Act |
| Violations left unremedied (Uttar Pradesh fire rules) | Report to the licensing authority to cancel the cold storage licence; then sealing | UP Rules 2024, rules 46 and 47 UP Rules 2024 |
| A cold store without fire systems or a certificate (Chhattisgarh) | No licence issued or renewed | Chhattisgarh Rules 2021, rule 35 CG Gazette |
| Breaching the fire safety chapter (Delhi) | Up to 6 months or Rs 50,000 or both, and up to Rs 3,000 a day | Delhi Fire Service Act 2007, section 37 Caseminestudy |
| Letting fire systems lapse (Maharashtra) | Rigorous imprisonment of 6 months to 3 years and a fine of Rs 20,000 to Rs 50,000 | Maharashtra Act 2006, section 36(1) MFS Act 2006 copy |
| Not maintaining fire equipment (Gujarat) | Rs 10,000 to Rs 1 lakh or 1 month to 2 years or both, plus up to Rs 3,000 a day | Gujarat Act 2013, section 39(1) Gujarat Gazette |
| No fire NOC, or equipment missing (Rajasthan) | Rs 5,000 on the owner or user | Rajasthan Municipalities Act 2009, section 291, applied by the 2023 order Rajasthan UDH |
| Breaking the fire law (Assam) | Fines from Rs 10,000 to Rs 5 lakh | Assam Act LIII of 2025 Assam Act LIII of 2025 |
Every state's fire penalty ladder is on the fire NOC penalties page.
Cold storage fire NOC worked cases: 8 stores
Each case applies one instrument to a described cold store. They are Flamekite's worked examples, not decisions of any fire service or licensing officer.
Case 1
A single-storey cold store in Narela, Delhi, 600 m²
One floor of chambers, 9 m to the ridge.
What applies Over 250 m², so a DFS certificate. NBC 2016's ground-floor row asks a wet riser, yard hydrant, sprinklers, detection, a 50,000 litre underground tank and a 1,620 litre a minute pump set. NBC 2016, Part 4
Case 2
A ground plus 2 potato store in Nalanda, Bihar, 1,200 m² a floor
3,600 m² in all, 13 m high.
What applies A floor over 500 m², so covered. Provisional fee 3,600 x Rs 10 = Rs 36,000, final Rs 18,000. NBC asks a 1,00,000 litre tank and 2,280 litre a minute pumps. BFS fee PDF
Case 3
A 5,000 MT store in Agra, Uttar Pradesh
Multi-chamber, 14 m, ammonia plant.
What applies A fire certificate for 3 years whatever its size, the Director of Horticulture's permission before building and a licence before storing, and fire insurance on the produce. LawGistnews report
Case 4
A cold chain warehouse near Pune, 20 m
4 floors, 2,500 m² a floor.
What applies Allowed in Maharashtra up to 24 m if local fire-fighting can serve it. Over 1,000 m², Note 18 asks full protection to the Indian Standards; fee 0.75% of ASR per m². MH Act 2023 Schedule-I
Case 5
The same store planned at 22 m in Faridabad
What applies Above Haryana's 21 m cap for storage buildings: redesign before applying. Government of Haryana
Case 6
A 450 m² single-floor cold store in Hooghly, West Bengal
8 m high.
What applies Inside the 9 m and 500 m² limits: a yearly Form-12 self-certification, and a cold storage licence for 5 years, renewed for 2. WB notification 1930
Case 7
An 800 m² cold store near Shillong
Single storey.
What applies Over 500 m², so a fire clearance. At Rs 6 per m² the fee is Rs 4,800; renewal Rs 2,000. Meghalaya F&ES
Case 8
A 12 m seafood cold store in Medchal, Telangana
Ammonia chilling plant, 40 workers.
What applies Below Telangana's 15 m storage line, so no fire NOC, but as a factory it falls under Safety Alert 10/2026: detectors, a receiver water curtain and quarterly drills. Telangana Factories
Where cold storages fail, and the fix: 7 cases
These are the failures the instruments and the post-incident reports point to for cold stores.
If Building up or adding a floor without permission
Take the Licensing Officer's permission and a revised fire approval first. Police said the Chandausi roof that fell in 2023 had been built 3 months earlier without permission, as reported. National Heraldnews report
If Loading beyond the licensed capacity
Store within the capacity the licence and design allow; the same report said the Chandausi store held more potatoes than its capacity. National Heraldnews report
If Workers housed beside the ammonia plant
Keep living quarters well away: after Tiruvallur, Tamil Nadu served 28 units notices for housing workers within 300 m of ammonia, as reported. DT Nextnews report
If No fixed gas detection in the machine room
Telangana's alert lists the absence of continuous gas detection among the 8 root causes of ammonia incidents; fit fixed detectors with outside alarms. Telangana Factories
If Relief valves venting into the plant room
Pipe them to a scrubber or water tank, and test them every year. Telangana Factories
If Offices or a packing hall added inside the store
A new use that raises the number of occupants changes the class from Group H; get the class and the fire approval reviewed. BIS, NBC 2016 Part 4
If Insurance taken on the produce only
In West Bengal section 15 covers the building and machinery too; WDRA lets a cold store add cover for power failure and plant damaged by fire. WB Cold Storage Act
Cold storage fire NOC myths, checked against the rules
5 claims repeated online, and what the instruments say.
You may have read
A cold store is too cold to burn.
Myth
What the sources say
BIS's note on IS 3594:2024 says cold stores face significant fire hazards from insulation, wooden pallets and packaging, and NBC 2016 rates cold storage premises moderate hazard. BIS
You may have read
Every state needs a fire NOC for cold storage only above 500 m².
Myth
You may have read
The cold storage licence covers fire safety.
Myth
What the sources say
The licence comes from the horticulture or agriculture side; the fire certificate is a separate document from the fire service, and four states' fire rules can cancel the licence when the certificate goes. UP Rules 2024
You may have read
A cold storage can go as high as the plot allows.
Myth
What the sources say
NBC 2016 permits no Group H building above 15 m; Maharashtra stops at 24 m and Haryana at 21 m. NBC 2016, Part 4
You may have read
Ammonia only poisons; it cannot burn.
Myth
What the sources say
Telangana's 2026 alert classes ammonia as toxic and flammable, with a flammable range of 15 to 28% in air, and asks the charge to isolate automatically in a fire. Telangana Factories
Cold storage fire and licensing rules, dated: 1966 to 2026
The instruments that set or changed a cold store's fire and licence duties, in order.
1966
West Bengal's Cold Storage (Licensing and Regulation) Act; amended in 1978 to 5-year licences renewed 45 days before expiry. WB Cold Storage Act
20 September 1975
The UP Regulation of Cold Storages Act takes effect from this date; passed as Act 11 of 1976. LawGistnews report
27 November 1989
The MSIHC Rules list ammonia with its threshold quantities. MSIHC Rules 1989
1992
Bihar's State Regulation of Cold Storages Act. Indian Kanoonnews report
9 January 2010
NHB uploads its cold storage technical standards, with a safety section for ammonia and fire. NHB standards
27 April 2017
WDRA's insurance circular adds power-failure and fire cover options for cold stores. WDRA circular 1/2017
1 March 2024
West Bengal lets small single-floor cold stores self-certify on Form-12. WB notification 1930
9 October 2024
BIS announces IS 3594:2024, the second revision of the storage and cold storage fire code. BIS
30 April 2026
NBC 2016 is withdrawn; NBCS 2026 brings Table 7H's protection levels for storage. Gazette of India
June 2026
Telangana's Directorate of Factories issues Safety Alert 10/2026 for ammonia chilling plants in cold stores. Telangana Factories
Cold storage collapses and ammonia leaks: Chandausi 2023 to Tiruvallur 2026
From news reports, not yet an official source.
News reports only: Flamekite found no official probe report or government order for these events on 25 October 2026. Tolls differ between reports. The rules in force are in the sections above.
17 March 2023
The roof of a cold storage in Chandausi, Sambhal district, UP, fell during potato loading; 10 dead among 21 pulled out by then. Ammonia cylinders kept in the store slowed rescue; the Chief Minister set up a probe. National Heraldnews report
23 July 2026
After the 21 June ammonia leak at a seafood export unit in Kannigaipair, Tiruvallur, that killed 18 workers by this report, Tamil Nadu formed 21 inspection teams and served 28 units notices. DT Nextnews report
What Flamekite could not confirm about cold storage fire NOCs
These 8 points are where a reader would expect an answer and no official source gave one on 25 October 2026.
- The official UP Act: India Code refused access, so this page reads it from a legal database copy and says so.
- The UP and West Bengal cold storage Rules: their licence periods, fees, building specifications and any fire condition were not found online.
- Whether Punjab has a cold storage licensing Act: none found.
- The text of IS 3594:2024, including its stack heights, compartment sizes and the new height for multi-storey cold stores: BIS sells it, and Flamekite has not read it.
- How NBC 2016's Group J test (ammonia under pressure above 70 m³) applies to a refrigeration plant's own charge: no clause or circular says.
- Which MSIHC schedule a refrigeration plant falls under: Telangana's alert names 50 t as Schedule 1, while the Rules print 50 t in Schedule 3 and 60 t in Schedule 2.
- Whether NHB's subsidy rates on its page, which carries a 2010 footer, are still the rates in force.
- Whether West Bengal's 19 high-risk occupancies take in a cold store above the 500 m² self-certification limit.
Questions about fire NOCs for cold storages
Is a fire NOC mandatory for a cold storage?
- Above your state's line, yes. Uttar Pradesh covers every storage building; Delhi, Gujarat, Rajasthan, Chhattisgarh, Manipur and Nagaland draw the line above 250 m²; Haryana, Bihar and Odisha near 500 m². Most cold storage states also want a separate cold storage licence.
Which NBC occupancy is a cold storage?
- Group H, storage. NBC 2016 clause 3.1.9 names cold storages among its examples and its Annex B puts cold storage premises in moderate hazard. NBCS 2026 keeps both and adds cold freezer rooms to the moderate column.
Who issues a cold storage licence?
- In Uttar Pradesh the Director of Horticulture and Fruit Utilization under the 1976 Act; in West Bengal the Director of Agriculture, the Additional Director (Marketing) or an empowered District Magistrate under the 1966 Act. Both also need permission before a new store is built.
What fire systems does a cold storage need?
- Under NBC 2016, a store under 250 m² needs extinguishers, hose reels, sprinklers and a 25,000 litre terrace tank. Above 250 m² add a wet riser, yard hydrant, alarm, detection, a 50,000 to 1,00,000 litre underground tank and a pump set.
Is ammonia in a cold storage covered by the hazardous chemical rules?
- Ammonia is listed in the MSIHC Rules 1989, with 50 t and 500 t in Schedule 3 and 60 t and 600 t in Schedule 2. Telangana's 2026 alert applies to cold storage ammonia plants whatever their charge.
How tall can a cold storage building be?
- NBC 2016 permits no storage building above 15 m, and Uttar Pradesh repeats it. Haryana allows storage to 21 m, and Maharashtra up to 24 m where local fire-fighting can serve it.
Does a cold storage need fire insurance?
- In Uttar Pradesh the licensee must insure the stored produce against fire and breakdown (s.23). In West Bengal the building, machinery and produce must be insured as the Licensing Officer decides (s.15).
Are PUF panels allowed in a cold storage?
- The codes do not ban them by name. They ask linings to meet a flame spread class on both faces, rate polyurethane at 35.2 thousand kJ per kg in the fire load table, and NHB lists PUF and EPS among usual insulation.
Keep reading
- Fire NOC in IndiaWho needs a fire NOC, how to apply and the rules in every state.
- Fire NOC by buildingLines for every building type, state by state.
- Fire NOC for warehousesGeneral warehouses, godowns and logistics parks.
- Fire NOC feesAll published rates side by side.
- Fire NOC validityEvery state's term and renewal date.
- Documents for a fire NOCWhat each state asks you to upload.
- Fire NOC penaltiesEvery state's penalty ladder.
- OSH Code 2020Factory safety duties that reach cold store plant rooms.
Free tools for this
Words on this page, explained
Keep exploring
Fire NOC for other industrial and storage buildings
Fire NOC: the steps
Sources
Each source was opened and read on the date shown. How Flamekite checks its sources
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016 (SP 7:2016), Part 4: Fire and Life Safety, clauses 1.2, 2.38 and 3.1 (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clause 3.1.10 (Group J), Table 3 occupant load, Table 5 travel distance, Table 8 size of mains, clause 6.8 storage buildings and Annex B hazard classes (read off the page images, printed pages 16, 29, 32, 57, 66 and 69) (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Puducherry Fire Service): National Building Code of India 2016, Volume 1, Part 4 Fire and Life Safety: Table 7, Minimum Requirements for Fire Fighting Installations, and its notes 6 to 24 (read from the page images) (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)
- Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: minimum fire fighting installations for apartment houses (A-4) by height, with Notes 1, 4, 6, 10, 11 and 15 (read off the page images, pp. 13 to 15 and 32 to 34) (opens in a new tab)
- Government of Maharashtra (copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023 (Mah. Act No. XXIV of 2023), first published 11 May 2023 (opens in a new tab)
Show all 61 sourcesShow fewer
- Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)
- Government of West Bengal (Act copy hosted by PRS Legislative Research): The West Bengal Cold Storage (Licensing and Regulation) Act, 1966 (West Ben. Act VI of 1966, as amended to 1978): sections 2(6), 2A, 3, 4, 15, 21, 22 and 24 (read off the page images) (opens in a new tab)
- Ministry of Environment and Forests (Rules copy hosted by the Inspectorate of Factories and Boilers, Goa): Manufacture, Storage and Import of Hazardous Chemical Rules, 1989 (S.O. 966(E), as amended to S.O. 57(E) of 2000): Schedule 2 item 2 and Schedule 3 Part I item 105, ammonia (opens in a new tab)
- Directorate of Factories, Government of Telangana (copy hosted by Simpliance): Safety Alert No. 10/2026 (June 2026), Ammonia refrigeration and chilling plants: cold storage units and chemical and pharmaceutical factories, file FACT-MAH/OHS/13/2026 (opens in a new tab)
- National Horticulture Board, Ministry of Agriculture: Technical Standards and Protocol for the Cold Chain in India, NHB-CS-Type 01-2010: cold storages for fresh produce without pre-cooling (insulation, section 9 safety, basic data sheet) (opens in a new tab)
- National Horticulture Board: Capital Investment Subsidy for Construction, Modernization and Expansion of Cold Storages and Storages for Horticulture Produce: components and pattern of assistance (opens in a new tab)
- Bureau of Indian Standards: IS 3594:2024, Fire Safety of General Storage and Warehousing Including Cold Storages, Code of Practice (Second Revision): BIS note of 9 October 2024 on the changes (opens in a new tab)
- Uttar Pradesh Gazette Extraordinary, 18 January 2024 (copy hosted by UP Fire and Emergency Services): Uttar Pradesh Fire and Emergency Services Rules, 2024, Notification No. 181/VI-Pu-8-2024-801(1)-2023: rules 40 to 56, 65, 66 and 72, Schedules VI and VII, Forms A-4, A-8 and A-11 to A-13 (opens in a new tab)
- Department of Fire and Emergency Services, Government of West Bengal: Notification 1930/FES/O/MISC-08/2023, 1 March 2024: 12 occupancies moved to yearly self-certification (with forwarding letter 1961 of 5 March 2024) (opens in a new tab)
- Directorate of Fire and Emergency Services, Tripura: Tripura Fire Safety Rules, 2026 (Tripura Gazette, 2 June 2026) (opens in a new tab)
- Gazette of India (copy hosted by PRS Legislative Research): Occupational Safety, Health and Working Conditions Code, 2020 (Act 37 of 2020), section 22 (opens in a new tab)
- Home (F) Department, Kerala (on the Kerala Fire and Rescue renewal portal): G.O.(Ms)No.143/2025/HOME, 4 August 2025: fire NOC valid 5 years (non-hazardous) or 2 years (hazardous) (opens in a new tab)
- Uttar Pradesh Gazette Extraordinary, 13 December 2022 (copy hosted by PRS Legislative Research): Uttar Pradesh Fire and Emergency Services Act, 2022 (U.P. Act No. 16 of 2022), English translation: sections 1, 26 to 29, 33 to 39, 45, 48, 58 and 66 (opens in a new tab)
- Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, Schedule II: Fire and Emergency Service Fee as a percentage of the Annual Statement of Rates, with malls and multiplexes in the commercial category (gazette pages 36 and 37) (opens in a new tab)
- Government of Haryana (PRS copy): Haryana Fire and Emergency Services Act, 2022 (Act 14 of 2022) (opens in a new tab)
- Warehousing Development and Regulatory Authority (WDRA): Circular No. 01/Tech.II/2017 of 27 April 2017: insurance policies for registration and renewal of warehouses (fire, flood, burglary, misappropriation, riots and strikes; Standard Fire and Special Perils policy) (opens in a new tab)
- Sewa Setu, Government of Assam: Fire NOC for one storied, multi-storied or high-rise building (Form I): required documents, and the Form II to XIII services (opens in a new tab)
- Home Department, Government of Odisha: Order No. 50908 of 19 November 2019: procedure for issue and renewal of Fire Safety Certificates and Fire Safety Recommendations (issuing officer, validity, inspecting team and time limit by building type) (opens in a new tab)
- Government of Sikkim, Sikkim Government Gazette Extraordinary No. 466, 17 December 2025: The Sikkim Fire and Emergency Services Rules, 2025: Home Department notification No. 99/Home/2025, 17 December 2025, under section 63 of Act 4 of 2023, with Schedules I to V and Forms A1 to A20 (opens in a new tab)
- Chhattisgarh Gazette Extraordinary No. 300, 18 August 2018 (on the CG Fire NOC portal): Chhattisgarh Fire and Emergency Service Act, 2018 (No. 19 of 2018), Hindi and English text: sections 1, 2, 14 to 20, 26, 28, 32 to 35, 41 and 47 to 58 (opens in a new tab)
- Delhi Fire Service (copy of Delhi Gazette Extraordinary, Part IV): Delhi Fire Service (Amendment) Rules, 2025, notification F.No. DFS/HQ/Misc/2025/01(E-259159)/237, gazetted 26 May 2026 (opens in a new tab)
- Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)
- Fire and Emergency Services and SDRF, Chhattisgarh: HQ order No. 204/Agnishaman/2025, 16 October 2025: risk-based NOC validity of 3, 2 or 1 years (opens in a new tab)
- Local Self Government Department, Government of Kerala (Kerala Gazette copies): Kerala Municipality Building Rules, 2019 (G.O.(P) No.77/2019/LSGD, S.R.O. No.828/2019, 8 November 2019) with the Amendment Rules, 2020 (G.O.(P) No.57/2020/LSGD, S.R.O. No.639/2020): rule 5(4) items 12 and 13, rules 28, 29, 35, 80 and 81, Appendix L (opens in a new tab)
- Telangana State Disaster Response and Fire Services Department: Circular Memorandum Rc.No.4039-2/EODB/2015, 5 March 2016: revision of the period of renewal of NOC, risk categories and random inspections (quotes section 13 of the Fire Service Act, 1999) (opens in a new tab)
- Bihar Fire Service: Fire NOC and Audit portal: Schedule C, prescribed rate of fee for NOC, renewal, fire audit and fire consultation (opens in a new tab)
- Fire and Emergency Services, Meghalaya: Annexure B2 to notification HPL.179/2017/85: mercantile, industrial, storage and hazardous buildings (opens in a new tab)
- Municipal Corporation Chandigarh, Fire and Rescue Services: Office Order No. 23 of 10 February 2025: Fire Safety Certificate charges by NBC occupancy group from 1 April 2025, validity 3 years, exemptions (read from the page images) (opens in a new tab)
- Government of Telangana, Home (Ser.IV) Department: G.O.Ms.No.142, Home (Ser.IV), 9 August 2016: fire precaution fee amending the Levy of Fee Rules, 2006 (opens in a new tab)
- Urban Development, Housing and Local Self Government Departments, Rajasthan: Joint order No. P.11(9)UDH/2020 Part, 14 September 2023, on the fire safety certificate and fire NOC (18-page Hindi scan) (opens in a new tab)
- Fire and Emergency Services, Assam: Annexure A, proposed rates of fee for issuance of No Objection Certificate, renewal NOC etc. (5 image pages, read from the page images) (opens in a new tab)
- Uttar Pradesh Fire and Emergency Services: Dashboard: provisional, final and renewal applications, approvals and days to certificate (printed 24 October 2026) (opens in a new tab)
- Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures Act, 2006, English gazette of 5 February 2007 (sections 3, 8, 36 to 38 read off the page images) (opens in a new tab)
- Gujarat Government Gazette (copy hosted by PRS Legislative Research): Gujarat Fire Prevention and Life Safety Measures Act, 2013 (Guj. Act 11 of 2013), Gazette Extraordinary of 1 April 2013, with Gujarat Act No. 5 of 2021 appended (Gazette of 23 March 2021) (opens in a new tab)
- Assam Gazette Extraordinary No. 811, 24 December 2025 (PRS copy of the gazette): The Assam Fire and Emergency Services Act, 2025 (Assam Act No. LIII of 2025), notification No. LGL.52/2025/3: sections 1 to 67 and Schedule I (opens in a new tab)
- Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)
- Gazette of India, Ministry of Home Affairs (copy hosted by TaxHeal): S.O. 2264(E) of 6 May 2026: the Haryana Fire and Emergency Services Act, 2022 extended to the Union territory of Chandigarh, with modifications (opens in a new tab)
- Government of Bihar, Home Department notification (English copy hosted by Bihar Fire Service): Bihar Fire Service Rules, 2021: rules 14 to 27, 33, 34 and 38, Schedules C (fees), D (online NOC), E (pandals) and H (existing buildings) (opens in a new tab)
- Home Department, Government of Odisha: Odisha Fire Prevention and Fire Safety (Amendment) Rules, 2019, notification No. 10573/H of 6 March 2019: rule 9(1) classes, rules 10, 13(3) and 22(5) (opens in a new tab)
- Government of Manipur (PRS copy): Manipur Fire and Emergency Service Act, 2026 (Act 9 of 2026) (opens in a new tab)
- Directorate of Fire and Emergency Services, Nagaland: Nagaland Fire and Emergency Services Act (Act No. 5 of 2023), Nagaland Gazette, 31 August 2023 (opens in a new tab)
- Department of Fire Services, Himachal Pradesh: Acts and Rules: HP Fire Fighting Services Act, 1984 with the 2000 amendment (section 15-A) (opens in a new tab)
- Gazette of Meghalaya No. 12, Part IIA, 25 March 2021 (copy hosted by the Urban Affairs Department): Meghalaya Building Bye-Laws, 2021 (No. UAU.73/2016/Pt/402 of 9 March 2021): A2.30 high-rise, A2.59 special buildings, A4.1.3, A10 occupancy and fire clearance, C11 (opens in a new tab)
- Department of Town Planning and ULBs, Arunachal Pradesh (Gazette No. 347, 4 September 2019; copy on EoDB Arunachal): Arunachal Pradesh Building Bye-Laws, 2019 (notification No. DTP/BBL-03/2011-12/2592-601, 30 August 2019): definitions, bye-laws 2.9 to 2.17, chapter 11, Annexures C and D, and 13.5 (opens in a new tab)
- Andhra Pradesh Legislative Assembly (PRS copy of AP Gazette Part IV-A No. 12, 4 March 2026): Andhra Pradesh Fire Service (Amendment) Bill, 2026 (L.A. Bill No. 12 of 2026): new section 13 thresholds, 21-day and 30-day timelines (opens in a new tab)
- Government of Karnataka (PRS copy): Karnataka Fire Force (Amendment) Ordinance, 2023: section 13(3) high-rise NOC (opens in a new tab)
- Guidance Tamil Nadu, Tamil Nadu Single Window Portal: Planning Permission for Buildings from DTCP: when an NOC from the Fire Service department is needed (opens in a new tab)
- Directorate of Fire and Emergency Services, Goa: Citizen's Charter, December 2024: 17 fire stations, 3 zones, 1,106 posts, the section 13 notification 3/5/97-HD(G) Part/3934 of 17 December 2014 with Annexures I and II, the 2018 Annexure III on shacks and guest houses, and the 2009 fee rules (opens in a new tab)
- Jammu and Kashmir Official Gazette (Extraordinary), copy hosted by the Housing and Urban Development Department: J&K Official Gazette, Vol. 134, No. 39-4, 24 December 2021: the Jammu and Kashmir Unified Building Bye-Laws, 2021 (opens in a new tab)
- Gazette of India Extraordinary (CG-DL-E-02062026-273069): Dadra and Nagar Haveli and Daman and Diu Fire and Emergency Service Regulation, 2026 (No. 6 of 2026) (opens in a new tab)
- Casemine (secondary copy of the Act text): Delhi Fire Service Act, 2007: sections 29, 31, 37, 44, 49, 52 and 54 (opens in a new tab)
- LawGist (legal database copy of U.P. Act 11 of 1976): The Uttar Pradesh Regulation of Cold Storages Act, 1976: sections 1, 2, 5 to 9, 12, 23, 36, 37, 39 and 40 (the India Code copy refused access on 25 October 2026) (opens in a new tab)
- Indian Kanoon (legal database): Bihar State Regulation of Cold Storages Act, 1992, section 40(b): power to inspect a cold storage, its machinery and records (listed under the State of Jharkhand) (opens in a new tab)
- National Herald (PTI), 17 March 2023: Death toll in UP cold storage roof collapse rises to 10, CM sets up probe panel (Chandausi, Sambhal) (opens in a new tab)
- DT Next, 23 July 2026: After Tiruvallur disaster, govt orders statewide audit of ammonia units; 28 firms face notices (opens in a new tab)