Fire hydrant system in India: parts, which buildings need one, IS 3844 values, installation, testing, maintenance and cost

Updated By Flamekite Editorial DeskFacts checked against official sources on

Fire hydrant system in India: parts, types, which buildings need a wet riser (NBC Table 7), IS 3844 values like 30 m reach and 700 kPa test, and official rates.

Hydrant reach
30 m
No point a hydrant covers may be further away (IS 3844 cl. 5.2.2)
Pressure and pumps 
Initial pressure test
700 kPa
Held at least 30 minutes, drop at most 50 kPa
Test checklist 
Flats need a wet riser above
35 m
A down-comer from 15 m to 35 m (NBC 2016 Table 7)
Table 7 rows 
Gun metal landing valve
Rs 7,863
Single outlet, supplied and erected; Maharashtra PWD CSR 2018-19, GST extra
Official rates 

Quick answer

A fire hydrant system is a fixed network of a dedicated water tank, fire pumps, rising mains and hydrant outlets with hose and branch pipes, kept ready so the fire brigade or trained staff can put water on a fire on any floor (IS 3844:1989, cl. 4.0). Inside a building it takes the form of a wet riser, a down-comer or hose reels; outside it is a ring of yard hydrants.

Indian buildings need one by occupancy and height under NBC 2016 Table 7 and the state rule that names it: flats get a down-comer from 15 m and a wet riser above 35 m, offices and shops a wet riser and yard hydrant above 15 m, and hospitals, five-star hotels, malls and warehouses over 250 m² a wet riser at any height. Maharashtra lets only a licensed agency install it.

Fire hydrant system diagram: fire water tank, main, diesel and jockey pumps, wet riser with a landing valve, hose and hose reel on each floor, fire service inlet and a yard hydrant
Fire hydrant system diagram: the 12 parts from the tank to the yard hydrant
  1. Fire water tank
  2. Main (duty) pump
  3. Standby (diesel) pump
  4. Jockey pump
  5. Wet riser or down-comer
  6. Landing valve
  7. Hose and branch pipe
  8. First-aid hose reel
  9. Hose cabinet
  10. Fire service inlet
  11. Yard hydrant
  12. Orifice plate
Schematic, not to scale. Each number is a part explained on this page.

Fire hydrant system IS codes and key numbers at a glance

The standards a hydrant installation is built and kept to, with the editions BIS listed on 24 October 2026, and the numbers searchers ask for most.
WhatThe ruleSource
Internal hydrants and hose reelsIS 3844:1989, first revision, reaffirmed 2020 and valid to 20 June 2030BIS, IS 3844:1989
External (yard) hydrantsIS 13039:2014BIS standards database
Water supply for fire fightingIS 9668:1990BIS standards database
Landing valves, branch pipes, hose reelsIS 5290:2025, IS 903:2025 and IS 884:2025; the 1985 and 1993 editions were withdrawn in September 2025BIS standards database
Fire pumpsIS 15301:2003, installation and maintenance of fire fighting pumpsBIS standards database
Four internal hydrant systemsDry riser, wet riser, wet-riser-cum-down-comer and down-comer (IS 3844 cl. 5.0)BIS, IS 3844:1989
Hydrant to any point it covers30 m at most; rising mains not more than 50 m apart (cl. 5.2.2)BIS, IS 3844:1989
Hose reel reachNo floor point more than 6 m from the nozzle at full extension (cl. 6.5)BIS, IS 3844:1989
Hose at each single-headed hydrantAt least 30 m of 63 mm hose, or two lengths of up to 15 m, plus 10 percent spares (cl. 5.12)BIS, IS 3844:1989
Life CPWD assigns a wet riser or sprinkler system20 yearsCPWD Maintenance Manual

Types of fire hydrant system: wet riser, down-comer, dry riser and yard hydrant

The five forms a hydrant installation takes in an Indian building, by IS 3844 and NBC 2016 Table 7. Your approved plan names the one you have.
OptionWater in the pipeFed byTypical NBC 2016 useMain size and outletSource
Wet riserAlways, under pressureGround or underground tank and pump house; pressure switch starts the duty pumpOffices and shops above 15 m, hospitals, hotels with floors over 1,000 m², flats above 35 m100 or 150 mm main; 63 mm landing valve, hose and branch pipe on every floorBIS, IS 3844:1989
Down-comerAlways, from the terraceTerrace tank and terrace pumpFlats and hostels from 15 m to 35 m, schools from 15 m to 24 m, offices under 10 m100 mm pipe; single-headed landing valve and hose reel on each floor (cl. 5.4.2)NBC 2016, Table 7
Wet-riser-cum-down-comerAlwaysStatic tank and pumps below, terrace tank above, two pumps of different capacityOlder approvals; a wet riser may replace it (cl. 5.3.2)Positions and spacing as for the wet riserBIS, IS 3844:1989
Dry riserNo; charged by the fire brigadeFire tender through a ground-level inletCold regions, and Group A buildings of 15 m to 24 m (cl. 5.1); every high-rise while under constructionAt least 100 mm under NBC 2016 for buildings under constructionNBC 2016, Part 4
Yard (courtyard) hydrantYes, on the ring mainThe same pump set as the wet riserMarked Yes in Table 7 for offices and shops above 15 m, hospitals of 15 m to 24 m, malls, warehouses, factories over 1,000 m²At least 2 per premises (IS 3844 cl. 5.11); design to IS 13039NBC 2016, Table 7

Fire hydrant system installation in 8 steps, from plan to final NOC

  1. Fix the occupancy, height and floor area

    These pick the Table 7 row that sets the riser type, yard hydrants, tank sizes and pump set; a basement over 200 m² adds 5,000 litres to the terrace tank (Note 6).

  2. Get the fire plan approved

    Submit hydrant layout, tank and pump house drawings with the building plan for the provisional or plan-stage approval your state runs.

  3. Build the tank and pump house

    Underground tank at most 3.5 m deep with a sump, two manholes and a 6 m access road for 18 tonne appliances; pump house 6 m from other buildings or behind a 2 hour wall (IS 3844 cl. 4.1.1, 4.2.1).

  4. Set the pumps

    A duty and a standby pump on different power sources, a jockey pump to hold pressure, and a manual push button as the only way to stop the main pump (cl. 4.2.2, 4.2.6).

  5. Run the mains and outlets

    Riser or down-comer, a landing valve and hose cabinet on each floor within 30 m of every point, fire service inlets at ground level, yard hydrants on the ring main.

  6. Pressure-test and flow-test

    Hold 700 kPa for at least 30 minutes with no more than 50 kPa drop, then run the flow test (cl. 8.1, 8.2).

  7. Certify the installation

    In Maharashtra the licensed agency signs Form A for the building under rule 4(1) of the 2009 Rules; other states ask for the installer's completion certificate with the test records.

  8. Fire service inspection and final NOC

    The fire officer runs the pumps and outlets on site against the approved plan before granting the final fire NOC; keep the test sheets for the first AMC.

Fire hydrant system parts name: 12 components and what each does

IS 3844 lists the parts of an installation as a tank, rising or down-comer mains, pumps with a control panel in a pump house, and the hydrants, hose reels, hoses and branch pipes (cl. 4.0). Here they are one by one.

Fire water tank
Underground or ground-level static tank for the riser, plus a terrace tank; sizes come from the Table 7 row, from 5,000 litres on the terrace of a small hostel to 2,50,000 litres underground for a five-star hotel. NBC 2016, Table 7
Main (duty) pump
Electric pump that starts on its own when a landing valve or hose reel opens and pressure falls (IS 3844 cl. 4.2.6, 7.3). BIS, IS 3844:1989
Standby (diesel) pump
Takes over on power failure; it has its own panel, battery and charger and is interlocked so only one pump runs (cl. 4.2.2). BIS, IS 3844:1989
Jockey pump
Small pump that makes up leakage so the main pump does not start for nothing; IS 3844 suggests 200 to 300 litres a minute (cl. 7.11), NBC 2016 Table 7 notes ask 180 litres a minute. BIS, IS 3844:1989
Wet riser or down-comer
The vertical main, 100 or 150 mm, kept full of water, with an air release valve at the top (cl. 7.6). BIS, IS 3844:1989
Landing valve
The 63 mm outlet on each floor where the hose couples; its control line sits 1 to 1.2 m above the floor (cl. 5.9). Product standard IS 5290:2025. BIS, IS 3844:1989
Hose and branch pipe
At least 30 m of 63 mm delivery hose per single-headed hydrant with a branch pipe and nozzle (cl. 5.12). BIS, IS 3844:1989
First-aid hose reel
A reel tapped from the riser through a 37 mm socket, run by untrained occupants, with the nozzle and valve about 900 mm above the floor (cl. 6.1, 6.2). BIS, IS 3844:1989
Hose cabinet
Steel box with a glass front holding the hose and branch pipe beside the landing valve (cl. 5.14). BIS, IS 3844:1989
Fire service inlet
Ground-level connection through which a fire tender pumps into the riser: 2 inlets of 63 mm on a 100 mm main, 4 on a 150 mm main (cl. 5.2.3). BIS, IS 3844:1989
Yard hydrant
Outdoor hydrant on the ring main round the building; at least 2 per premises (cl. 5.11). BIS, IS 3844:1989
Orifice plate
Flange that throttles lower-floor outlets where pressure would exceed 400 kPa (cl. 7.8). BIS, IS 3844:1989

How a fire hydrant system works: water from tank to nozzle in 6 stops

Water sits still under pressure until an outlet opens. The pressure drop starts the duty pump, and the pump keeps the riser charged while the hose is in use.

  1. 1. Static tank

    Two equal compartments joined by valves, so one can be cleaned while the other stays full; an indicator plate marked SWT shows the capacity (IS 9668 cl. 5.11). BIS, IS 9668:1990

  2. 2. Pump suction

    Flooded suction is preferred; where a pump lifts water, a priming tank of 8 times the suction pipe volume keeps it primed (IS 3844 cl. 4.2.4). BIS, IS 3844:1989

  3. 3. Jockey and main pumps

    The jockey pump holds the line pressure; when an outlet opens and pressure falls further, the pressure switch starts the main pump. BIS, IS 3844:1989

  4. 4. Riser or ring main

    The charged main rises through the building, with rising mains no more than 50 m apart on large floors (cl. 5.2.2). BIS, IS 3844:1989

  5. 5. Landing valve and hose

    Firefighters couple 63 mm hose to the landing valve; static pressure in a shut hose may not exceed 700 kPa (cl. 7.7). BIS, IS 3844:1989

  6. 6. Fire service inlet

    If the building's water runs low, the brigade pumps into the riser through the inlet; IS 9668 wants a water source within 1 km of the risk (cl. 3.1). BIS, IS 9668:1990

Which buildings need a fire hydrant system under NBC 2016 Table 7

Table 7 of NBC 2016 Part 4 marks the riser, yard hydrant and tanks for each occupancy and height. These rows were read off the printed pages; a state that names the code applies them through its NOC.

RiserYard hydrantUnderground tank (litres)Terrace tank (litres)
Flats and hostels under 15 mHose reel onlyNoNone5,000
Flats and hostels, 15 m to 35 mDown-comerNoNone25,000
Flats and hostels, above 35 m to 45 mWet riserNo75,0005,000
Flats and hostels, above 45 m to 60 mWet riserYes1,50,00010,000
Hotel under 15 m, floor 300 to 1,000 m²Wet riser above ground plus oneNo10,000 per 500 m² of floor, at least 50,00010,000
Five-star hotel, any heightWet riserYes2,50,00020,000
School, 15 m to 24 mDown-comerNoNone25,000
Hospital under 15 m, ground plus 2 or more with bedsWet riserNo75,00010,000
Hospital, 15 m to 24 mWet riserYes1,50,00020,000
Office or shops above 15 m to 24 mWet riserYes1,00,00010,000
Mall with cinemas or food courtsWet riserYes2,00,00020,000
Moderate hazard factory over 1,000 m²Wet riserYes1,50,00020,000
Warehouse under 15 m, over 250 m², ground floor onlyWet riserYes50,00010,000
Multi-level car parkWet riserYes1,50,00010,000

Add 5,000 litres to the terrace tank where a basement exceeds 200 m² (Note 6). Table 7 does not permit storage buildings above 15 m (Note 20). The full set of rows, with sprinklers and alarms, is on the NBC 2016 page. NBC 2016, Table 7

Fire hydrant system requirements in India: which rule your state applies

BIS withdrew NBC 2016 on 30 April 2026, but a state that names it in its fire law keeps applying Table 7. Find your situation below.

  1. IfYour state's fire act, rules or bye-laws name NBC 2016 (Flamekite found 17 states and UTs)

    The Table 7 row for your occupancy and height decides the riser, yard hydrants, tanks and pumps, and the fire officer's NOC conditions add to it. NBC 2016 Gazette of India

  2. IfYour building is in Maharashtra

    Schedule-I of the 2006 Act, substituted in 2023, sets the installations by row; for big storage and industrial buildings Note 21(a) sends hydrant design to IS 13039. Fire NOC Maharashtra MH Act 2023 Schedule-I

  3. IfYour building is in Uttarakhand and under 12 m

    The order of 6 June 2025 replaces Table 7 with lighter state kits below 12 m. Fire NOC Uttarakhand Uttarakhand GO 2025

  4. IfYour building is in Assam

    Since 14 August 2026 the fire Act asks for measures as per the BIS National Building Construction Standards, so NBCS 2026 Part F tables apply. NBC 2026 Assam Act XIII of 2026

  5. IfYour workplace is in Uttar Pradesh with 5 or more floors or 20 m or more

    Rule 12 of the UP OSH Rules 2026 binds the employer to NBCS 2026 Part F as well. NBC 2026 UP Gazette

  6. IfYou run a factory

    The Model Rules under the Factories Act treat sprinklers and hydrants as additions to, never substitutes for, first-aid fire fighting (rule 68(13)); the fire NOC still follows the state fire rule. Factories DGOSH Model Rules

Fire hydrant system for a building: 3 worked examples

Flamekite's reading of Table 7 for three common buildings in states that name NBC 2016. Your fire service's reading prevails.

  1. Case 1

    A 16 m block of flats

    Group A-4 apartments, ground plus 4, top floor 16 m, no basement.

    What applies A down-comer with a landing valve and hose reel on each floor, fed by a 25,000 litre terrace tank and a terrace pump. No wet riser, yard hydrant or underground tank until the building passes 35 m. NBC 2016, Table 7

  2. Case 2

    A 20 m office building

    Group E business, 20 m, 1,200 m² floors, no basement.

    What applies A wet riser, yard hydrants, a 1,00,000 litre underground tank and a 10,000 litre terrace tank, with one electric and one diesel pump of 2,280 litres a minute and a 180 litre a minute jockey (Note 10). NBC 2016, Table 7

  3. Case 3

    A single-storey warehouse of 2,000 m²

    Group H storage, 9 m, ground floor only.

    What applies Over 250 m², so a wet riser, yard hydrants, a 50,000 litre underground tank and a 10,000 litre terrace tank. Raising it above 15 m is not permitted by Note 20. NBC 2016, Table 7

Fire hydrant system pressure, flow and pump numbers

Six figures from IS 3844 and the NBC 2016 Table 7 notes recur in every hydrant design and test.

  • 30 m

    Greatest distance from a hydrant to any point it covers (IS 3844 cl. 5.2.2) BIS, IS 3844:1989

  • 700 kPa

    Highest static pressure allowed in a hose line with the nozzle shut (cl. 7.7) BIS, IS 3844:1989

  • 400 kPa

    Pressure above which lower-floor outlets get an orifice plate (cl. 7.8) BIS, IS 3844:1989

  • 2,280 l/min

    Main and diesel pump size for an office of 15 m to 24 m (Table 7 Note 10); Note 14 asks 1,620 and Note 12 2,850 NBC 2016, Table 7

  • 180 l/min

    Jockey pump in the Table 7 pump sets; IS 3844 cl. 7.11 suggests 200 to 300 NBC 2016, Table 7

  • 1,125 l/min

    Output 3 adjacent hydrants must give at 5.25 kgf/cm² in Maharashtra's quarterly test MFS Form B guidelines

Fire hydrant pump room and tank rules from IS 3844

Clause 4 fixes where the pump house and tank go and how the pumps are controlled. These are the points inspectors check first.

Do

  • Put the pump house outside the building, 6 m from adjoining buildings, where you can (cl. 4.2.1). BIS, IS 3844:1989
  • Inside the building, use only floor one or the basement, behind a 2 hour wall and a 1 hour fire door, with forced ventilation below ground (cl. 4.2.1). BIS, IS 3844:1989
  • Leave 1 m in front of and behind pumps above 2,280 litres a minute and 0.75 m at the sides, with 2.75 m headroom (cl. 4.2.2). BIS, IS 3844:1989
  • Run the duty and standby pumps from different power sources, with a diesel generator or separate sub-station and automatic changeover (cl. 4.2.6, 4.2.7). BIS, IS 3844:1989
  • Keep the underground tank at most 3.5 m deep, sloped 1 in 100 to a sump, with at least 2 manholes (cl. 4.1.1). BIS, IS 3844:1989

Don’t

  • Do not wire the main pump to stop on its own: only a manual push button on the panel may stop it (cl. 4.2.2). BIS, IS 3844:1989
  • Do not leave the diesel pump without its own control panel, battery and charger, interlocked with the electric pump (cl. 4.2.2). BIS, IS 3844:1989
  • Do not prime a suction-lift pump from a tank smaller than 8 times the suction pipe volume (cl. 4.2.4). BIS, IS 3844:1989
  • Do not block the 6 m access road to the tank, which must carry 18 tonne appliances (cl. 4.1.1). BIS, IS 3844:1989

Who may install a fire hydrant system in India

No national licence exists for hydrant installers. Maharashtra licenses agencies by system and class; elsewhere the fire service accepts the installer's certificate with the NOC file.

Fire hydrant system testing and commissioning checklist

IS 3844 clause 8 asks for a pressure test and then a flow test before use; Maharashtra's guidelines add the commissioning points below.

  • Hydraulic test of the whole installation at 700 kPa for at least 30 minutes, with a pressure drop of at most 50 kPa (cl. 8.1). BIS, IS 3844:1989
  • Flow test at the outlets after the pressure test (cl. 8.2). BIS, IS 3844:1989
  • Pump flow at 7 kgf/cm² and at 4.5 kgf/cm² recorded and displayed in the pump house at commissioning. MFS Form B guidelines
  • Pump alignment checked after a 15 minute run. MFS Form B guidelines
  • Highest hose reel on each riser gives at least 30 litres a minute (0.5 litre a second) when run fully out (cl. 9.7). BIS, IS 3844:1989
  • Orifice plates fitted where lower floors see more than 400 kPa (cl. 7.8). BIS, IS 3844:1989
  • Diesel engine started and run for 10 minutes, with fuel in the day tank for 4 hours of running. MFS Form B guidelines
  • Static tank carries a yellow SWT plate with its capacity in litres (IS 9668 cl. 5.11). BIS, IS 9668:1990
  • Isolating valves locked open and indicator plates in place at every hydrant (IS 3844 cl. 9.1, 9.2). BIS, IS 3844:1989

Fire hydrant system maintenance checklist: daily to yearly

IS 3844 fixes only a 6-monthly valve inspection and a yearly hose reel test. Maharashtra's Form B guidelines of 7 July 2026 fill in the other cycles, and most AMCs follow them.

  1. Daily

    Time the jockey pump cut-in and run the main pump for at least 5 minutes. MFS Form B guidelines

  2. Weekly

    Inspect every hydrant, keep isolating valves locked open, and run the diesel engine for 10 minutes. MFS Form B guidelines

  3. Monthly

    Open each hydrant and check its washers. MFS Form B guidelines

  4. Quarterly

    Flow 3 adjacent hydrants together: at least 1,125 litres a minute at 5.25 kgf/cm². MFS Form B guidelines

  5. Every 6 months

    Inspect inlets, landing valves, drain valves and the hinges and locks of inlet and valve boxes (IS 3844 cl. 9.3). BIS, IS 3844:1989

  6. Every 6 months to 2 years

    Clean static tanks: open tanks every 6 months, covered tanks at least every 2 years (IS 9668). BIS, IS 9668:1990

  7. Yearly

    Run each hose reel fully out under pressure for at least 30 litres a minute, at least the highest on each riser (IS 3844 cl. 9.7). BIS, IS 3844:1989

Fire hydrant system price: official item rates

Flamekite’s working from the official rules; no government publishes this figure.

No Indian schedule prices a whole hydrant system; cost is built up item by item. The Maharashtra PWD Current Schedule of Rates 2018-19 is the official public list Flamekite could read: supplied, erected, tested and commissioned, GST extra.

As published

Rates are eight years old and Maharashtra-specific; the schedule adds a location uplift outside district headquarters. CPWD's current Delhi Schedule of Rates for these items was not available to read. The tank, pump house and civil work are priced in other chapters.

Fire hydrant faults that hold up a fire NOC

Each fault below is a departure from IS 3844 or the Table 7 row that a fire officer can see on site.

  • If Fire tank smaller than the Table 7 row for the building

    Recheck the row for your occupancy and height; a basement over 200 m² adds 5,000 litres to the terrace tank (Note 6). NBC 2016, Table 7

  • If Only one fire pump, or both pumps on the same power source

    Fit a standby pump on a different source, interlocked with the duty pump (IS 3844 cl. 4.2.6, 7.3). BIS, IS 3844:1989

  • If A point on the floor more than 30 m from any hydrant

    Add a landing valve or a second rising main; mains may be at most 50 m apart (cl. 5.2.2). BIS, IS 3844:1989

  • If Hose reel that leaves a corner more than 6 m from the nozzle

    Move the reel or add one, so no point is beyond 6 m at full extension (cl. 6.5). BIS, IS 3844:1989

  • If Main pump set to stop automatically

    Rewire so only the manual push button on the pump panel stops it (cl. 4.2.2). BIS, IS 3844:1989

  • If Lower floors over pressure, bursting hose

    Fit orifice plates where pressure exceeds 400 kPa (cl. 7.8). BIS, IS 3844:1989

  • If System shut for repair with no notice

    Tell the fire service at once and post a notice that the installation is out of use (cl. 9.9). BIS, IS 3844:1989

Fire hydrant system myths owners repeat

Four claims about hydrant systems that the codes do not support.

  • You may have read

    Every building above 15 m needs a wet riser.

    Myth

    What the sources say

    Table 7 gives flats and hostels a down-comer from 15 m to 35 m and a wet riser only above 35 m; schools get a down-comer from 15 m to 24 m. NBC 2016, Table 7

  • You may have read

    IS 3844 sets weekly, monthly and quarterly hydrant checks.

    Myth

    What the sources say

    It sets a 6-monthly inspection of inlets and valves and a yearly hose reel test (cl. 9.3, 9.7); the shorter cycles come from Maharashtra's guidelines and AMC contracts. BIS, IS 3844:1989

  • You may have read

    A hydrant system replaces fire extinguishers.

    Myth

    What the sources say

    Table 7 requires extinguishers in every row except A-2 homes, and the Factories Act Model Rules call hydrants an addition to first-aid fire fighting (rule 68(13)). DGOSH Model Rules

  • You may have read

    IS 3844 covers yard hydrants too.

    Myth

    What the sources say

    Its scope note sends external hydrants to a separate standard, now IS 13039:2014. BIS, IS 3844:1989

What Flamekite could not confirm about fire hydrant systems

Four facts a reader would expect here are not stated, because no official text was available to read on 28 October 2026.

  • IS 13039:2014 values for yard hydrant spacing and outlet pressure: no lawful copy was read, so they are left to the standard.
  • Current CPWD Delhi Schedule of Rates (E&M) prices for hydrant items: the rates above are Maharashtra's 2018-19 schedule instead.
  • HSN code and GST rate for a hydrant installation contract: not confirmed from a CBIC or GST Council notification.
  • Table 7 tank and pump rows for occupancies not listed above, such as G-1 and G-3 factories: read your row off the printed code or the NBCS 2026 Part F table your state names.

Questions about fire hydrant systems in India

What is a fire hydrant system?

A fixed network of a fire water tank, fire pumps, a wet riser or down-comer, landing valves with hose and branch pipes, hose reels and yard hydrants, kept charged so the fire brigade or trained staff can fight a fire on any floor (IS 3844:1989).

What are the types of fire hydrant system?

Inside a building: a wet riser, a down-comer, a wet-riser-cum-down-comer or a dry riser charged by the fire brigade (IS 3844 cl. 5.0), plus hose reels. Outside: yard hydrants on a ring main.

How does a fire hydrant system work?

Water sits under pressure in the riser, held up by the jockey pump. When a landing valve or hose reel opens, pressure falls and the main pump starts, keeping the riser charged while the hose is in use.

What are the fire hydrant system parts names?

Fire water tank, main pump, diesel standby pump, jockey pump, riser or down-comer, landing valves, hose and branch pipes, hose reels, hose cabinets, fire service inlet, yard hydrants and orifice plates.

Which IS code applies to a fire hydrant system?

IS 3844:1989 for internal hydrants and hose reels, IS 13039:2014 for yard hydrants and IS 9668:1990 for the water supply; landing valves are IS 5290:2025 and pumps follow IS 15301:2003.

What are the fire hydrant system requirements as per NBC?

Under NBC 2016 Table 7, flats get a down-comer from 15 m and a wet riser above 35 m; offices and shops a wet riser and yard hydrant above 15 m; hospitals, five-star hotels, malls and warehouses over 250 m² a wet riser at any height. Your state rule decides.

What is the pressure in a fire hydrant system?

IS 3844 caps static pressure in a shut hose at 700 kPa, asks for orifice plates above 400 kPa, and tests the installation at 700 kPa for 30 minutes. Maharashtra's quarterly test wants 1,125 litres a minute from 3 hydrants at 5.25 kgf/cm².

What does a jockey pump do in a hydrant system?

It makes up small leaks to keep the riser at pressure so the main pump only starts when an outlet opens. IS 3844 suggests 200 to 300 litres a minute; NBC 2016 Table 7 notes use 180.

What is the difference between a wet riser and a down-comer?

A wet riser is fed from a ground or underground tank by the main pump set; a down-comer is fed from the terrace tank by a terrace pump and is used in lower buildings, such as flats of 15 m to 35 m.

What is the fire hydrant system cost in India?

It is priced item by item. Maharashtra's PWD schedule for 2018-19 gives Rs 7,863 for a gun metal landing valve, Rs 6,234 for a hose reel, Rs 1,473 a metre for 100 mm pipe and Rs 2,86,931 for a 2,400 l/min main pump, GST extra.

How often should a fire hydrant system be tested?

IS 3844 asks for a 6-monthly valve inspection and a yearly hose reel flow test. Maharashtra adds daily pump runs, weekly inspections, monthly hydrant opening and a quarterly 3-hydrant flow test.

Who can install a fire hydrant system?

In Maharashtra only a Licensed Agency, which signs Form A at installation. Other states have their own licensing or empanelment, or none; the fire officer checks the installation before the final NOC.

Keep reading

Free tools for this

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards: IS 3844:1989, Code of Practice for Installation and Maintenance of Internal Fire Hydrants and Hose Reels on Premises (first revision, reaffirmed 2020); free download after registration; clause numbers cited on the page (opens in a new tab)checked 26 October 2026
  2. Bureau of Indian Standards: IS 9668:1990, Provision and Maintenance of Water Supplies for Fire Fighting, Code of Practice (first revision, reaffirmed 2020); free download after registration; clause numbers cited on the page (opens in a new tab)checked 26 October 2026
  3. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)checked 25 October 2026
  4. Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  5. Public Works Department (Electrical Wing), Government of Maharashtra (copy hosted by Chhatrapati Sambhajinagar Municipal Corporation): Current Schedule of Rates 2018-2019 (in force from 12 September 2018), chapter 13 Fire Fighting and Fire Alarm System: items 13-1-1 to 13-10-3 (fire pumps, jockey and booster pumps, GI pipe, valves, hydrant valves, hose reels, hoses, branch pipes, fire brigade inlets, cabinets, conventional fire alarm, PA system and sprinkler items), rates per unit before GST, printed pages 223 to 231 (opens in a new tab)checked 28 October 2026
  6. Central Public Works Department, Government of India: CPWD Maintenance Manual 2023: services not rendered by CPWD, plinth-area rates for electrical maintenance (Annexure 2A), use of indexed DSR or market rates, and life of fire alarm and wet riser systems (opens in a new tab)checked 25 October 2026
Show all 19 sourcesShow fewer
  1. Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)checked 25 October 2026
  2. Government of Maharashtra (gazette copy hosted by Maharashtra Fire and Emergency Services): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Act, 2023, substituted Schedule-I: minimum fire fighting installations for apartment houses (A-4) by height, with Notes 1, 4, 6, 10, 11 and 15 (read off the page images, pp. 13 to 15 and 32 to 34) (opens in a new tab)checked 25 October 2026
  3. Government of Uttarakhand, Home (Adhishthan) Section-3 (copy hosted by Uttarakhand Fire and Emergency Services): Government order No. 304272/XX-3/2025-02(10)/2024, 6 June 2025: amended NBC 2016 Part 4 Table 7 fire installations for low-rise (below 12 m) and mixed occupancy buildings, Annexures A to G (opens in a new tab)checked 24 October 2026
  4. Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)checked 25 October 2026
  5. Uttar Pradesh Gazette Extraordinary, 27 August 2026, English translation (copy hosted by TeamLease RegTech): Uttar Pradesh Occupational Safety, Health and Working Conditions Rules, 2026, Notification No. 962/XXXVI-03-2026-1903305: rules 12, 16, 43, 45, 46, 47 and 127 (opens in a new tab)checked 25 October 2026
  6. Directorate General Occupational Safety and Health (formerly DGFASLI), Ministry of Labour and Employment: Model Rules under the Factories Act, 1948 (corrected up to 15 December 2020): rule 68 fire protection with Schedules I and II, rule 69 safety officers, rule 82A site appraisal committee, rule 82I emergency plan (opens in a new tab)checked 25 October 2026
  7. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
  8. Maharashtra Fire and Emergency Services: Application for Fire Licence Agency, Form M and checklist (updated 11.07.26) (opens in a new tab)checked 25 October 2026
  9. Urban Development Department, Government of Maharashtra (copy hosted by MFS): Maharashtra Fire Prevention and Life Safety Measures Rules, 2009, gazette of 23 June 2009: rule 4, Form A and Form B (opens in a new tab)checked 25 October 2026
  10. Urban Development Department, Government of Maharashtra (copy hosted by MFS): Maharashtra Fire Prevention and Life Safety Measures (Amendment) Rules, 2025, Notification No. MFS-2023/C.R.370/UD-14, 12 June 2025 (opens in a new tab)checked 25 October 2026
  11. Central Drugs Standard Control Organization, Ministry of Health and Family Welfare (GeM contract): GeM contract GEMC-511687733194234, 28 December 2021: AMC / CMC of Fire Detection, Fire Alarm, Fire Hydrant and Sprinkler System at FDA Bhawan, New Delhi, comprehensive, 4 January 2022 to 3 January 2023 (opens in a new tab)checked 25 October 2026
  12. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clauses 1.1 and 1.2 (scope), 2.6 (height), 2.24 (firefighting shaft), 3.1.11 to 3.1.14 (mixed occupancy), 3.2 (fire zones), 3.3 and Table 1 (types of construction), 3.4.3.2 (high-rise under construction) and Table 2 (floor area ratios), printed pages 7, 9 and 17 to 20, read off the page images (opens in a new tab)checked 25 October 2026
  13. Studio Matrx (consumer guide): Fire hydrants in India guide (competitor page read for its section count) (opens in a new tab)News report · checked 28 October 2026