Skip to content
Flamekite
ContactFree fire NOC check

Fire systems 18 min read

Fire sprinkler system in India: types, where the code requires it, IS 15105 design, installation, tests, upkeep and cost

Updated By Flamekite Editorial DeskFacts checked against official sources on

Fire sprinkler system in India: wet, pre-action and deluge types, where NBC Table 7 requires them, IS 15105 design (12 m² a head, 5 lpm/m²), tests and rates.

Ordinary hazard density
5 lpm/m²
Over at most 360 m² operating at once (IS 15105 cl. 8.1.2)
Design numbers 
Basement trigger
200 m²
Low buildings need sprinklers in a basement above this (NBC 2016 Table 7)
Table 7 rows 
Acceptance pressure test
120 minutes
At 150 percent of maximum working pressure (cl. 14.2)
Acceptance tests 
68 °C bulb sprinkler head
Rs 396
Supplied, erected and tested; Maharashtra PWD CSR 2018-19, GST extra
Official rates 

Quick answer

A fire sprinkler system is a network of pipes with heat-sensitive heads that open one by one over a fire and spray water, fed by a dedicated tank and pumps through an installation valve that also sounds an alarm gong. India designs it to IS 15105:2021, which sorts buildings into light, ordinary, high and storage hazard and sets, for example, 5 litres a minute per m² with at most 12 m² a head for ordinary hazard (cl. 8.1, 9.17).

Under NBC 2016 Table 7, most low buildings need sprinklers only in a basement over 200 m², while offices and shops above 15 m, hospitals, five-star hotels, malls, factories over 1,000 m², warehouses over 250 m² and flats above 45 m need them throughout. Your state rule and NOC conditions decide the final list.

Fire sprinkler system diagram: water tank and fire pumps feed the installation valve set, the riser, a flow switch on each floor and the range pipes with sprinkler heads
Fire sprinkler system diagram: how the 10 parts connect in a three-storey building
  1. Sprinkler head
  2. Glass bulb colour
  3. Installation (alarm) valve set
  4. Water motor alarm gong
  5. Flow switch
  6. Distribution and range pipes
  7. Fire pumps
  8. Water tank
  9. Spare heads and wrench
  10. Test and drain valve
Schematic, not to scale. Each number is a part explained on this page.

Fire sprinkler system code and key numbers at a glance

The Indian sprinkler standard, its status on 24 October 2026, and the numbers most asked about, each with its clause.
WhatThe ruleSource
StandardIS 15105:2021, Design, Installation and Maintenance of Fixed Automatic Sprinkler Fire Extinguishing Systems, first revision, July 2021BIS, IS 15105:2021
ReplacedIS 15105:2002, withdrawn on 14 March 2022BIS, IS 15105:2021
Not coveredWater spray and deluge design (IS 15325, IS 15519), and ships, aircraft, vehicles and mines (cl. 1.4, 1.5)BIS, IS 15105:2021
Water and pumps for most buildingsTaken from Table 7 of NBC Part 4; the code's own tank and pump tables apply only where that table is silent (cl. 1.6)BIS, IS 15105:2021
Hazard classesLight, ordinary, high and storage (cl. 5.1)BIS, IS 15105:2021
Maximum pressure in an installation7 bar (cl. 10.3.3)BIS, IS 15105:2021
Height of one installation45 m; above it the high-rise rules of Annex B apply (cl. 6.5)BIS, IS 15105:2021
BIS mark for sprinkler headsNot compulsory: IS 9972 heads had only a draft Quality Control Order on 24 October 2026BIS, IS 15105:2021
Travel distance bonus50 percent more travel distance allowed in a fully sprinklered building (NBC 2016 Table 5, Note 1)NBC 2016, Part 4
Life CPWD assigns a sprinkler system20 yearsCPWD Maintenance Manual

Types of fire sprinkler system: wet, dry, pre-action, deluge and recycling

The installation types named in IS 15105:2002 clause 16, the first edition that the 2021 revision replaced. A wet system is the default in Indian buildings.
OptionPipe above the valveWhat opens the waterWhere it is usedSource
Wet pipeAlways full of water under pressure (cl. 3.29)Heat breaks the head's bulb or link; water flows at onceHeated buildings: offices, hotels, hospitals, shops, warehousesIS 15105:2002 (withdrawn)
Dry pipeAir under pressureA head opens, air escapes, the valve admits waterAllowed as an alternative type (cl. 16.1 note) where pipes could freezeIS 15105:2002 (withdrawn)
Pre-actionDry, often with supervisory airA separate detection system opens the alarm valve first (cl. 3.27)Recommended for computer and data rooms, where an accidental discharge is costly (cl. 11.12.3)IS 15105:2002 (withdrawn)
RecyclingDryHeat detectors open and close the valve repeatedly (cl. 3.28)To limit water damage after the fire is out (cl. 16.4)IS 15105:2002 (withdrawn)
DelugeDry, with open headsDetection opens a deluge valve; every head dischargesWhere water must cover the whole area a fire may start in (cl. 16.6); outside IS 15105:2021, which sends spray and deluge to IS 15325 and IS 15519IS 15105:2002 (withdrawn)

Fire sprinkler system installation in 8 steps

  1. Read the Table 7 row

    Occupancy, height and floor area decide whether sprinklers go in the basement only or the whole building, and the tank and pump set.

  2. Classify the hazard

    Light, ordinary, high or storage under IS 15105 clause 5; an unlisted risk goes to the authority in writing before design (cl. 5.6).

  3. Size the pipes

    Tables may be used only for light and ordinary systems up to 5,000 m² and not gridded; everything else is hydraulically calculated (cl. 10.3).

  4. Get the layout approved

    Submit the sprinkler drawings with the fire plan for the provisional approval your state runs.

  5. Install pumps, valves and pipework

    Pumps exceed the calculated flow and pressure by at least 20 percent (cl. 12.1(e)); the installation valve set carries the alarm gong and gauges.

  6. Fit and space the heads

    Choose K-factor and temperature rating per Table 1 and cl. 7.7, and keep within the coverage and spacing limits of cl. 9.17.

  7. Run the acceptance tests

    Pressure test, flushing, full-flow test, diesel start sequence and alarm checks of clause 14, recorded for the authority.

  8. Certify and get the final NOC

    The installer certifies the work (Form A by a licensed agency in Maharashtra) and the fire officer inspects before the final NOC.

Fire sprinkler system components: 10 parts and their job

A sprinkler installation is a set of main control valves with the pipes and heads downstream of it (IS 15105:2002, cl. 3.26), plus the water supply that feeds it.

Sprinkler head
A sealed nozzle that opens at its rated temperature; orifices are 10, 15, 20 or 25 mm (IS 15105 cl. 7.4). BIS, IS 15105:2021
Glass bulb colour
Shows the rating: orange 57 °C, red 68 °C, yellow 79 °C, green 93 °C (Table 3). BIS, IS 15105:2021
Installation (alarm) valve set
The control valve, alarm valve, gauges and drain for one installation; gauges above and below it are read daily (cl. 15.6). BIS, IS 15105:2021
Water motor alarm gong
Sounds within 45 to 60 seconds of water flowing (cl. 11.10(b)), at least 85 dB above background noise (cl. 14.8(b)). BIS, IS 15105:2021
Flow switch
Signals the fire panel which zone is flowing; signals must reach the panel at acceptance (cl. 14.9). BIS, IS 15105:2021
Distribution and range pipes
The pipe grid feeding heads; arm pipes are kept to 32 mm bore where the feed is over 65 mm (cl. 10.1(c)). BIS, IS 15105:2021
Fire pumps
Direct-coupled, never belt-driven, with an engine pump backing an electric one (cl. 12.1(b), (f)). BIS, IS 15105:2021
Water tank
Sized from the Table 7 row for most buildings; a reservoir of 225 m³ or more needs two interconnected compartments (cl. 13.3(e)). BIS, IS 15105:2021
Spare heads and wrench
Kept at 38 °C or less: 5 light, 15 ordinary, 30 high hazard near a state capital, more elsewhere (cl. 7.10, Table 5). BIS, IS 15105:2021
Test and drain valve
Used to prove the alarm and the water supply; the full-flow test opens a head or the pump-room test line (cl. 14.5). BIS, IS 15105:2021

How a fire sprinkler system works: from heat to alarm in 5 stops

Only the heads heated past their rating open. The rest stay shut, which is why a sprinkler fire uses far less water than a hose.

  1. 1. Heat reaches the ceiling

    The head's rating is at least 30 °C above the hottest ceiling temperature expected, so normal heat never opens it (cl. 7.7.1). BIS, IS 15105:2021

  2. 2. The bulb or link breaks

    A red bulb gives way at 68 °C; that head alone starts to spray. BIS, IS 15105:2021

  3. 3. Water flows through the valve

    Water moving through the installation valve set feeds the alarm gong and trips the flow switch, whose signal must reach the fire panel (cl. 14.9). BIS, IS 15105:2021

  4. 4. The gong and panel sound

    Within 45 to 60 seconds of flow the gong must ring (cl. 11.10(b)). BIS, IS 15105:2021

  5. 5. The pump keeps pressure

    Falling pressure starts the main pump, which runs until stopped by hand; the tank holds 30 to 120 minutes of pump running by hazard where IS 15105 sets the storage (Table 30). BIS, IS 15105:2021

Where NBC 2016 Table 7 requires a fire sprinkler system

Table 7 has a sprinkler column for every occupancy and height. In low buildings it usually points to Note 4: sprinklers only in a basement over 200 m². These rows were read off the printed pages.

SprinklersUnderground tank (litres)
Flats and hostels under 35 mBasement over 200 m² onlyNone
Flats and hostels, above 35 m to 45 mBasement, fed from both tanks75,000
Flats and hostels above 45 mWhole building1,50,000 to 2,00,000
Hotel under 15 m, floor up to 1,000 m²Basement over 200 m² onlyNone to 50,000 or more
Hotel under 15 m, floor over 1,000 m²; five-star hotelWhole building1,00,000; 2,50,000
School under 24 mBasement over 200 m² onlyNone
Hospital with beds above ground plus 2, or 15 m to 24 mWhole building75,000; 1,50,000
Office or shops above 15 mWhole building1,00,000 to 2,00,000
Mall with cinemas or food courtsWhole building2,00,000
Moderate hazard factory over 1,000 m²Whole building1,50,000
Warehouse under 15 m, over 250 m²Whole building50,000
Multi-level car parkWhole building1,50,000

Annex E adds sprinklers to every refuge area, and above 120 m for homes and 60 m for other buildings sprinklers are fed from a main and an alternate riser. In Maharashtra, Note 21(a) of Schedule-I sends large storage and industrial sprinkler design to IS 15105. NBC 2016, Table 7

Fire sprinkler hazard classification: which class your building is

IS 15105 clause 5 puts every occupancy in one of 4 classes, and the class sets density, coverage and water. Find yours below.

  1. IfOffices, hotels, hospitals, schools, libraries, museums, places of worship, prisons or homes

    Light hazard, but only where no compartment exceeds 126 m² and compartments have 30 minute walls and doors; otherwise ordinary (cl. 5.2.2, 5.6.1). Kitchens, stores and utilities are excluded. Hotels BIS, IS 15105:2021

  2. IfShops, car parks inside buildings, airport terminals, metro stations, laboratories, garages, garment and electronics units, bakeries

    Ordinary hazard (cl. 5.3, 5.6.2); the list is not complete, so ask the authority about an unlisted risk before design. Malls and shops BIS, IS 15105:2021

  3. IfProcesses with a high fire load that spreads fast

    High hazard (cl. 5.4.1); some need water spray under IS 15325 instead (cl. 5.4.2). Factories BIS, IS 15105:2021

  4. IfWarehouses stacked above ordinary hazard heights

    Storage hazard by commodity category, with Annex C densities; ESFR heads reach storage up to 13.7 m (cl. 5.5, Table 1). Warehouses BIS, IS 15105:2021

  5. IfA hospital ward block

    Light hazard if the compartment rule is met; Table 7 still asks for sprinklers in the whole building once beds sit above ground plus 2. Hospitals NBC 2016, Table 7

  6. IfA small higher-hazard area inside a larger occupancy

    If it is 40 m² or less it follows the dominant occupancy (cl. 13.2). BIS, IS 15105:2021

Fire sprinkler design numbers: density, coverage and spacing

Clauses 8.1 and 9.17 of IS 15105 set the water each square metre gets and how much ceiling one standard head may cover.

  • 2.25 lpm/m²

    Light hazard density, over at most 84 m² operating (cl. 8.1.1) BIS, IS 15105:2021

  • 5 lpm/m²

    Ordinary hazard density, over at most 360 m² (cl. 8.1.2) BIS, IS 15105:2021

  • 12.2 lpm/m²

    High hazard density, over at most 260 m² (cl. 8.1.3) BIS, IS 15105:2021

  • 21 m²

    Most ceiling one standard head may cover in light hazard; 12 m² ordinary, 9 m² high (cl. 9.17.1) BIS, IS 15105:2021

  • 4.5 m

    Most distance between heads in light and ordinary hazard; 3.75 m in high (cl. 9.17.2) BIS, IS 15105:2021

  • 1.8 m

    Least distance between heads, so one does not wet the next (cl. 9.17.3) BIS, IS 15105:2021

Fire sprinkler system for warehouses, hotels, hospitals and offices

Each building page sets out the full NOC regime; these are the sprinkler points that differ by use.

Fire sprinkler head selection and placement: do's and don'ts

Most site rejections come from the wrong head in the wrong place. These IS 15105 rules prevent them.

Do

  • Pick a temperature rating at least 30 °C above the highest expected ceiling temperature (cl. 7.7.1). BIS, IS 15105:2021
  • Use 141 °C roof heads over high-piled storage (cl. 7.7.2). BIS, IS 15105:2021
  • Match K-factor to hazard and height: K 80 or 115 for ordinary hazard up to 9 m, K 115 from 9 to 15 m (Table 1). BIS, IS 15105:2021
  • Keep heads at least 100 mm from a wall (cl. 9.17.5) and the deflector 75 to 450 mm below a non-combustible ceiling (Table 8). BIS, IS 15105:2021
  • Fit an approved metal guard where a head can be knocked (cl. 7.9(a)). BIS, IS 15105:2021

Don’t

  • Do not paint, coat or load a head; every head is inspected for position, loading and corrosion at least every 6 months (cl. 15.6.4). BIS, IS 15105:2021
  • Do not place heads closer than 1.8 m apart (cl. 9.17.3). BIS, IS 15105:2021
  • Do not run water pipes over salt baths, metal melt pans, frying ranges or grain silos (cl. 6.2.2). BIS, IS 15105:2021
  • Do not exceed 6 m/s of water through valves or 10 m/s elsewhere (cl. 10.5). BIS, IS 15105:2021

Fire sprinkler system acceptance tests before handover

Clause 14 of IS 15105 lists the tests between installation and use. Keep every result for the fire officer and the first AMC.

  • Working drawings checked against what was built, and deviations listed for the authority (cl. 14.1). BIS, IS 15105:2021
  • Pipework held at 150 percent of maximum working pressure for 120 minutes (cl. 14.2(a)). BIS, IS 15105:2021
  • Pre-action pipework also air-tested at 3 bar for 24 hours (cl. 14.2(c)). BIS, IS 15105:2021
  • All piping flushed at the maximum flow available; hydraulic balance checked where more than 500 heads are connected (cl. 14.4). BIS, IS 15105:2021
  • Full-flow test proving the water supply matches the accepted drawings (cl. 14.5). BIS, IS 15105:2021
  • Diesel pump: 6 cranking cycles of at least 15 seconds with fuel isolated, then the fail-to-start alarm (cl. 14.7). BIS, IS 15105:2021
  • Gong sounds within 45 to 60 seconds and at least 85 dB above background (cl. 11.10(b), 14.8(b)). BIS, IS 15105:2021
  • Flow switch signals reach the fire alarm panel (cl. 14.9). BIS, IS 15105:2021

Fire sprinkler system maintenance: daily to every 2 years

IS 15105 clause 15.6 sets cycles from a daily pump run to a two-yearly painting; Maharashtra's July 2026 guidelines follow the same pattern.

  1. Daily

    Run every fire pump for at least 5 minutes; read gauges above and below the installation valve (cl. 15.6.3). BIS, IS 15105:2021

  2. Weekly

    Visual check, gauge readings logged, tank level recorded and kept full, gong timed after opening the drain (cl. 15.6.1). BIS, IS 15105:2021

  3. Quarterly

    Gong assembly checked thoroughly; every head inspected for position, loading and corrosion. MFS Form B guidelines

  4. Every 6 months

    Discharge test; pump motor insulation measured (cl. 15.6.4(c)). BIS, IS 15105:2021

  5. Yearly

    Pipework examined, installation valves serviced by qualified people, system flushed. BIS, IS 15105:2021

  6. Every 2 years at most

    Reservoir cleaned and sprinkler equipment painted (cl. 13.3(g)). BIS, IS 15105:2021

Fire sprinkler system cost in India: official item rates

Flamekite’s working from the official rules; no government publishes this figure.

No schedule gives a rate per square foot for a sprinkler system. The Maharashtra PWD Current Schedule of Rates 2018-19 prices the items, supplied, erected, tested and commissioned, GST extra.

As published

The schedule has no item for the alarm valve set or pre-action and deluge valves, and its rates date from 12 September 2018. Head count follows from coverage: an ordinary hazard floor of 1,200 m² needs at least 100 heads at 12 m² each.

Fire sprinkler faults that hold up a fire NOC

Each of these is visible on an inspection and traceable to a clause.

  • If Basement over 200 m² left without sprinklers in a low building

    Table 7 Note 4 asks for them; add a basement installation fed from the fire tank. NBC 2016, Table 7

  • If Office designed as light hazard with open floors larger than 126 m²

    Redesign to ordinary hazard density and coverage (cl. 5.2.2). BIS, IS 15105:2021

  • If Gong silent or slower than 60 seconds

    Service the alarm valve and water motor until it rings within 45 to 60 seconds (cl. 11.10(b)). BIS, IS 15105:2021

  • If Heads blocked by ducts, racks or a new false ceiling

    Re-space under the new ceiling within the cl. 9.17 limits, and keep stock below the deflectors. BIS, IS 15105:2021

  • If No spare heads or wrench on site

    Keep the Table 5 count of each type at 38 °C or less (cl. 7.10). BIS, IS 15105:2021

  • If Gridded system sized from tables

    Gridded and looped layouts need a full hydraulic calculation (cl. 10.3.1). BIS, IS 15105:2021

Fire sprinkler myths the codes contradict

Four beliefs about sprinklers that IS 15105 and NBC 2016 do not support.

  • You may have read

    When one sprinkler goes off, they all go off.

    Myth

    What the sources say

    In a wet system only heads heated past their rating open; all heads discharge together only in a deluge system with open heads (IS 15105:2002 cl. 16.6). IS 15105:2002 (withdrawn)

  • You may have read

    Sprinkler tanks are always sized by IS 15105.

    Myth

    What the sources say

    For most building groups the Table 7 row of NBC Part 4 sets water and pumps; the code's Table 30 covers the rest (cl. 1.6). BIS, IS 15105:2021

  • You may have read

    Sprinklers make extinguishers and hydrants unnecessary.

    Myth

    What the sources say

    Table 7 rows that require sprinklers also require a wet riser, yard hydrant and extinguishers. NBC 2016, Table 7

  • You may have read

    Any building with sprinklers can use 50 percent longer escape routes.

    Myth

    What the sources say

    Only a fully sprinklered building earns the 50 percent travel distance increase (Table 5, Note 1). NBC 2016, Part 4

Fire sprinkler requirement for 3 buildings: worked examples

Flamekite's reading of Table 7 and IS 15105 in states that name NBC 2016. The fire service's reading prevails.

  1. Case 1

    A 30 m block of flats with a 600 m² basement

    Group A-4, ground plus 9, one basement car park.

    What applies Below 35 m Table 7 asks for sprinklers only in the basement, because it exceeds 200 m²; the car park is ordinary hazard, so 5 lpm/m² and at most 12 m² a head. NBC 2016, Table 7

  2. Case 2

    A 20 m office

    Group E, open-plan floors of 1,000 m².

    What applies Sprinklers throughout (above 15 m). Floors exceed 126 m² compartments, so design as ordinary hazard rather than light. BIS, IS 15105:2021

  3. Case 3

    A 3,000 m² single-storey warehouse with 7 m racks

    Group H, ground floor only, 9 m roof.

    What applies Sprinklers throughout (over 250 m²). Racked storage is storage hazard, so the system is hydraulically calculated with Annex C densities and two tank compartments if storage reaches 225 m³. BIS, IS 15105:2021

What Flamekite could not confirm about sprinkler systems

Four facts searchers ask for that no official text read on 28 October 2026 settled.

  • A per square foot cost for a complete sprinkler system: no official schedule publishes one.
  • HSN code and GST rate for sprinkler installation: not confirmed from a CBIC or GST Council notification.
  • Dry pipe and deluge clauses of the 2021 edition: the type definitions above are from the 2002 edition, which the 2021 text replaced.
  • Current CPWD Delhi Schedule of Rates (E&M) prices for sprinkler items: not available to read.

Questions about fire sprinkler systems in India

What is a fire sprinkler system?

A network of water-filled pipes with heat-sensitive heads that open individually over a fire, fed by a fire tank and pumps through an installation valve that also rings an alarm gong. In India it is designed to IS 15105:2021.

What are the types of fire sprinkler system?

Wet pipe, dry pipe, pre-action, recycling and deluge. Wet pipe, always full of water, is the usual type; pre-action suits computer rooms and deluge discharges every open head at once.

What are the components of a fire sprinkler system?

Sprinkler heads, the installation (alarm) valve set, a water motor alarm gong, flow switches, distribution and range pipes, fire pumps, a water tank, spare heads with a wrench, and a test and drain valve.

How does a fire sprinkler system work?

Heat breaks the bulb or link of the heads over the fire, and only those heads spray. Water flowing through the installation valve rings the gong within 45 to 60 seconds and signals the fire panel, and the pump keeps up the pressure.

At what temperature does a sprinkler activate?

At its rated temperature, shown by bulb colour: orange 57 °C, red 68 °C, yellow 79 °C, green 93 °C. The rating is chosen at least 30 °C above the hottest expected ceiling temperature (IS 15105 cl. 7.7.1).

How much area does one sprinkler cover?

At most 21 m² in light hazard, 12 m² in ordinary hazard and 9 m² in high hazard for a standard head, with heads at most 4.5 m apart (3.75 m in high hazard) and at least 1.8 m apart (IS 15105 cl. 9.17).

What are the sprinkler system requirements as per NBC?

Under NBC 2016 Table 7, most low buildings need them only in a basement over 200 m². Offices and shops above 15 m, hospitals with beds above ground plus 2, five-star hotels, malls, warehouses over 250 m² and flats above 45 m need them throughout.

Does a warehouse need a sprinkler system?

Yes once a ground-floor warehouse exceeds 250 m² under NBC 2016 Table 7, and storage buildings may not exceed 15 m. Racked storage is designed as storage hazard with hydraulic calculation.

How is a sprinkler system tested?

Before use: 150 percent of working pressure for 120 minutes, flushing, a full-flow test, a diesel start test and an alarm gong within 45 to 60 seconds. Afterwards: daily pump runs, weekly gauge checks and a discharge test every 6 months.

What is the fire sprinkler system cost in India per sq ft?

It is priced item by item. Maharashtra's PWD schedule for 2018-19 gives Rs 396 for a 68 °C bulb sprinkler, Rs 374 a metre for 25 mm GI pipe and Rs 6,360 for an 80 mm flow switch, GST extra. No official per square foot rate exists.

What is the fire sprinkler system water tank size?

For most buildings the NBC Table 7 row sets it, for example 1,00,000 litres for an office of 15 m to 24 m. Where IS 15105 sets it, it is 30 minutes of pump running for light hazard, 60 for ordinary and 120 for high hazard.

Keep reading

Free tools for this

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards: IS 15105:2021, Design, Installation and Maintenance of Fixed Automatic Sprinkler Fire Extinguishing Systems, Code of Practice (first revision), July 2021; free download after registration; clause and table numbers cited on the page (opens in a new tab)checked 26 October 2026
  2. Bureau of Indian Standards (copy published by Public.Resource.Org): IS 15105:2002, Design and Installation of Fixed Automatic Sprinkler Fire Extinguishing Systems, Code of Practice: the first edition, withdrawn 14 March 2022; read for its installation types (cl. 3.27 to 3.29, 16.1 to 16.6) and installation size limits (cl. 16.2.2) (opens in a new tab)checked 28 October 2026
  3. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4, Table 7 Minimum Requirements for Fire Fighting Installations: every row, Groups A to J, and Notes 1 to 24, printed pages 41 to 51, read off the page images (opens in a new tab)checked 25 October 2026
  4. Public Works Department (Electrical Wing), Government of Maharashtra (copy hosted by Chhatrapati Sambhajinagar Municipal Corporation): Current Schedule of Rates 2018-2019 (in force from 12 September 2018), chapter 13 Fire Fighting and Fire Alarm System: items 13-1-1 to 13-10-3 (fire pumps, jockey and booster pumps, GI pipe, valves, hydrant valves, hose reels, hoses, branch pipes, fire brigade inlets, cabinets, conventional fire alarm, PA system and sprinkler items), rates per unit before GST, printed pages 223 to 231 (opens in a new tab)checked 28 October 2026
  5. Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  6. Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clause 4.3 and Table 3 (occupant load), 4.4.2.2 (dead ends), Table 4 (capacity factors), Table 5 (travel distance), 4.4.2.4.1 (doorways) and 4.4.2.4.3 (staircases), printed pages 29 to 34, read off the page images (opens in a new tab)checked 25 October 2026
Show all 10 sourcesShow fewer
  1. Central Public Works Department, Government of India: CPWD Maintenance Manual 2023: services not rendered by CPWD, plinth-area rates for electrical maintenance (Annexure 2A), use of indexed DSR or market rates, and life of fire alarm and wet riser systems (opens in a new tab)checked 25 October 2026
  2. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
  3. Central Drugs Standard Control Organization, Ministry of Health and Family Welfare (GeM contract): GeM contract GEMC-511687733194234, 28 December 2021: AMC / CMC of Fire Detection, Fire Alarm, Fire Hydrant and Sprinkler System at FDA Bhawan, New Delhi, comprehensive, 4 January 2022 to 3 January 2023 (opens in a new tab)checked 25 October 2026
  4. Studio Matrx (consumer guide): Sprinkler systems in India guide (competitor page read for its section count) (opens in a new tab)News report · checked 28 October 2026