Fire exit rules in India: how many exits, how wide, which way the doors open, signs and lighting under NBC 2016
Updated By Flamekite Editorial DeskFacts checked against official sources on
Fire exit rules in India under NBC 2016: 1,000 mm doors that open outward, 30 m travel distance, 2 stairs, green signs every 30 m and 90 minutes of exit light.
- Travel distance in most buildings
- 30 m
- Types 1 and 2 construction; plus 50% if fully sprinklered
- By building
Quick answer
Fire exit rules in India come from Part 4 of the National Building Code 2016, which state fire rules and building bye-laws adopt. A building it covers needs at least 2 staircases, no point on a floor more than 30 m from an exit in most buildings (45 m in low and moderate hazard industry, plus 50% if fully sprinklered), exit doors at least 1,000 mm wide and 2,000 mm high (2,000 mm wide in assembly buildings), opening in the direction of exit without a key.
Exit width is worked from people, not floor area: 500 mm is one unit, and a level exit carries one person per 6.5 mm in most uses, so a 1,000 mm door serves about 150 people (Table 4). Exits are signed in green so that no point is more than 30 m from a sign, lit on an independent supply, and escape lighting must come on within 5 seconds and last at least 90 minutes (clause 3.4.7).
Free, on WhatsApp. Or check if you need one
Fire exit rules in India at a glance: 10 numbers
| What | The rule | Source |
|---|---|---|
| Staircases | At least 2 in every building Part 4 covers; at least half discharge directly outside or through an exit passageway (4.4.2.4.3) | NBC 2016, Part 4 |
| Travel distance | 30 m in most buildings, 22.5 m for high hazard industry and hazardous uses, 45 m for low and moderate hazard industry (Table 5) | NBC 2016, Part 4 |
| Sprinkler bonus | Travel distance may grow by 50% in a fully sprinklered building (Table 5, note 1) | NBC 2016, Part 4 |
| Dead-end corridor | 6 m in schools, hospitals and assembly buildings; 15 m elsewhere (4.4.2.2) | NBC 2016, Part 4 |
| Exit door | At least 1,000 mm wide (2,000 mm in assembly buildings) and 2,000 mm high (4.4.2.4.1) | NBC 2016, Part 4 |
| Unit of exit width | 500 mm; an extra 250 mm counts as half a unit, anything narrower counts for nothing (4.4.2.3) | NBC 2016, Part 4 |
| Door swing | In the direction of exit; overhead and sliding doors are not allowed on exits (4.2.9) | BIS, NBC 2016 Part 4 |
| Exit signs | Green, lit, on an independent circuit, with no point more than 30 m from a visible directional sign (3.4.7.4) | BIS, NBC 2016 Part 4 |
| Escape lighting | On within 5 s, lasting at least 90 min, at least 10 lux along the route's centreline (3.4.7.1) | BIS, NBC 2016 Part 4 |
| Who Part 4 covers | All buildings of 15 m or more, all assembly buildings, and hotels, offices, shops, factories and others with a floor over 500 m² (1.2) | NBC 2016, Part 4 |
Fire exit rules by building type under NBC 2016
| Option | Travel distance | Dead-end corridor | Narrowest exit door | Stair width | Width per person: stairs / level | Source |
|---|---|---|---|---|---|---|
| Houses (A-2) | 30 m | 15 m | 1,000 mm | 1.00 m; 0.75 m in 2-storey row housing | 10 / 6.5 mm | NBC 2016, Part 4 |
| Lodging, dormitories, flats (A-1, A-3, A-4) | 30 m | 15 m | 1,000 mm | 1.25 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Hotels (A-5, A-6) | 30 m | 15 m | 1,000 mm | 1.50 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Schools and colleges (B) | 30 m | 6 m | 1,000 mm | 1.50 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Hospitals (C) | 30 m | 6 m | 1,000 mm | 2.00 m | 15 / 13 mm | NBC 2016, Part 4 |
| Assembly: halls, cinemas, restaurants (D) | 30 m | 6 m | 2,000 mm | 2.00 m; 1.50 m under 150 persons | 10 / 6.5 mm | NBC 2016, Part 4 |
| Offices (E) | 30 m | 15 m | 1,000 mm | 1.50 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Shops and malls (F) | 30 m | 15 m | 1,000 mm | 1.50 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Low and moderate hazard industry (G-1, G-2) | 45 m | 15 m | 1,000 mm | 1.50 m | 10 / 6.5 mm | NBC 2016, Part 4 |
| Hazardous (J) and high hazard industry (G-3) | 22.5 m | 15 m | 1,000 mm | 1.50 m | 18 / 10 mm (J) | NBC 2016, Part 4 |
How to check your building's fire exits in 7 steps
Confirm Part 4 applies
Check the building against clause 1.2: 15 m or more, any assembly use, a floor over 500 m², or a school or hospital of 9 m or more. If none fits, your state's bye-laws still set exits.
Count the people on each floor
Divide the gross floor area by the Table 3 factor for its use, or take the declared number if higher. Fixed seats count as seats times 1.2.
Work out the width
Multiply the people by the Table 4 factor (6.5 mm a person on level routes in most uses) and round up to whole or half 500 mm units.
Split it across exits
Provide at least 2 stairs, as far apart as possible, each at least the Part 4 minimum width for the occupancy. The narrowest part of each route sets its capacity.
Walk the travel distance
From the most remote point on the floor, along the real path round furniture and partitions, to the door of an exit: 30 m in most buildings.
Test every door
Each exit door opens in the direction of travel, without a key, is at least 1,000 mm by 2,000 mm, and fire doors close by themselves.
Check signs, lights and clear paths
Green lit signs within 30 m of every point, escape lighting that holds 90 minutes, and nothing stored in corridors or stairs.
What counts as a fire exit: the NBC's 3-part escape route
NBC 2016 splits the way out into 3 parts. "Fire exit" and "emergency exit" mean the same thing in practice; the code's word is exit.
1. Exit access
The path from where you stand to an exit: room doors, corridors, lobbies, verandahs. Its length is the travel distance, capped at 30 m in most buildings (2.17, Table 5). BIS, NBC 2016 Part 4
2. Exit
The protected part: an enclosed stair with a 120 min enclosure, an exit passageway, an external stair or ramp, or a horizontal exit into another fire compartment (2.16, 4.2.1). BIS, NBC 2016 Part 4
3. Exit discharge
From the end of the exit to the street or another public way. At least half the stairs must reach it directly or through an exit passageway (2.19, 4.4.2.4.3). BIS, NBC 2016 Part 4
Not an exit
Lifts, escalators, moving walks and revolving doors do not count, and a fire curtain is never a fire exit (4.2.2; 2.22 note 5). BIS, NBC 2016 Part 4
How wide must a fire exit be? The numbers
Width follows the number of people, using clause 4.4.2.3 and Table 4. Minimum door sizes apply on top.
500 mm
One unit of exit width; 250 mm more counts as half a unit, less than 250 mm is ignored NBC 2016, Part 4
6.5 mm
Width a person needs on doors, corridors and ramps in homes, schools, offices, shops, assembly, industry and storage NBC 2016, Part 4
10 mm
Width a person needs on stairs in the same uses; 15 mm in hospitals and 18 mm in hazardous buildings NBC 2016, Part 4
13 mm
Width a person needs on level routes in hospitals, where patients may be moved on beds or chairs NBC 2016, Part 4
150
People a 1,000 mm exit door serves at 6.5 mm each (1,000 / 6.5 = 153, rounded down) NBC 2016, Part 4
2,000 mm
Minimum height of every exit doorway, and minimum width in assembly buildings NBC 2016, Part 4
How many fire exits does a building need? Width by occupant load
Flamekite’s working from the official rules; no government publishes this figure.
Flamekite's working from Table 3 and Table 4 for a 1,000 m² floor of each use. The 1,000 mm minimum door and 2-stair rule still apply on top of these widths.
| Floor area per person (Table 3) | People on 1,000 m² | Door and corridor width needed | Stair width needed | |
|---|---|---|---|---|
| Homes and flats | 12.5 m² | 80 | 520 mm | 800 mm |
| Schools | 4 m² | 250 | 1,625 mm | 2,500 mm |
| Hospital wards | 15 m² | 67 | 871 mm (13 mm each) | 1,005 mm (15 mm each) |
| Hall with no fixed seats, crowded | 0.65 m² | 1,539 | 10,004 mm | 15,390 mm |
| Restaurant dining area | 1.8 m² | 556 | 3,614 mm | 5,560 mm |
| Shop, street floor | 3 m² | 334 | 2,171 mm | 3,340 mm |
| Offices and factories | 10 m² | 100 | 650 mm | 1,000 mm |
| Warehouses | 30 m² | 34 | 221 mm | 340 mm |
| Hazardous buildings | 10 m² | 100 | 1,000 mm (10 mm each) | 1,800 mm (18 mm each) |
Counts are rounded up to whole people. Upper shop floors use 6 m² a person and hospital outpatient areas 10 m²; dormitories in homes for the aged use 7.5 m². Required exits are counted floor by floor, and their capacity may never fall along the way out (4.4.2.3). NBC 2016, Part 4
Fire exit door rules: 9 things the NBC asks
Doors are where most exits fail. Clauses 4.2.9 and 4.4.2.4.1 set these, and a fire officer tests them by hand.
- Every exit door opens in the direction of exit; overhead and sliding doors are not used (4.2.9). BIS, NBC 2016 Part 4
- It opens from the side it serves without a key (4.4.2.4.1(c)). Panic bars, which release the latch when pushed in the direction of travel, are the usual hardware (2.37). NBC 2016, Part 4
- Clear width at least 1,000 mm, or 2,000 mm in an assembly building, and at least 2,000 mm high (4.4.2.4.1(b)). NBC 2016, Part 4
- In hospitals and assembly buildings the door does not open straight onto a flight: it opens onto a landing. Elsewhere it may block no more than half the landing (4.2.9). BIS, NBC 2016 Part 4
- No mirrors on exit doors or inside exits, so no one mistakes the way out (4.4.2.4.1(d)). NBC 2016, Part 4
- Fire doors in exits close by themselves, are never held open, carry intumescent seals and a 20 min insulation rating (2.22 notes 2 to 4). BIS, NBC 2016 Part 4
- Every fire-rated door carries a label with its maker, type, serial number, month and year of manufacture and rating (4.4.2.4.1(f)). NBC 2016, Part 4
- Access-controlled and magnetic doors unlock when the alarm or sprinklers operate and on power loss, with a PUSH TO EXIT release beside them (4.4.2.4.1(g)). NBC 2016, Part 4
- Revolving doors count for only 50 persons and need a hinged door within 3 m; turnstiles need a full-width door within 3 m (4.4.2.4.1(e), (h)). NBC 2016, Part 4
Fire exit signs and emergency lighting: dos and don'ts
Clause 3.4.7 makes the way out visible in smoke and darkness. These are its numbers.
Do
- Use green exit signs, lit and wired to an independent circuit on an alternative supply (3.4.7.4). BIS, NBC 2016 Part 4
- Place them so that no point is more than 30 m from a visible directional sign, and at every change of direction (3.4.7.4). BIS, NBC 2016 Part 4
- Light the escape route's centreline to at least 10 lux, and half the width of routes up to 2 m wide to at least 5 lux (3.4.7.1(d)). BIS, NBC 2016 Part 4
- Make emergency lighting come on within 5 s of a power cut and last at least 90 min (3.4.7.1(f)). BIS, NBC 2016 Part 4
- Fit escape luminaires at least 2 m above the floor and within 2 m of each exit door, stair, corridor junction, call point and fire equipment (3.4.7.1(h), (j)). BIS, NBC 2016 Part 4
- Put a floor board of at least 300 mm by 200 mm inside each stair beside the fire door (4.4.2.4.3). NBC 2016, Part 4
Don’t
- Rely on battery packs in place of a diesel generator supply for emergency lighting (3.4.7.1(g)). BIS, NBC 2016 Part 4
- Let one failed lamp leave any part of the route dark (3.4.7.1(e)). BIS, NBC 2016 Part 4
- Mount signs where furniture or trolleys will knock them (3.4.7.4). BIS, NBC 2016 Part 4
- Dim auditorium aisles below 2 lux during a show (3.4.7.1(d)). BIS, NBC 2016 Part 4
Does the NBC fire exit chapter apply to your building?
Clause 1.2 decides. If your building is outside it, the state bye-laws still set exits, usually by the same numbers.
IfIt is 15 m or taller
Yes: every high-rise, whatever its use (1.2(a), 2.38). High Rise Building Height as per NBC NBC 2016, Part 4
IfIt is an assembly building: hall, cinema, banquet, place of worship
Yes, at any size (1.2(b)(4)), and doors are 2,000 mm wide. Cinemas and theatres NBC 2016, Part 4
IfIt is a school or hospital of 9 m or more
Yes (1.2(b)(2), (3)). Schools and colleges NBC 2016, Part 4
IfIt is a hotel, office, shop, factory or warehouse with any floor over 500 m²
Yes (1.2(b)(1)). A floor with more than 300 m² of assembly use also brings it in. Commercial buildings NBC 2016, Part 4
IfIt has 2 or more basements, or 1 basement over 500 m²
Yes (1.2(b)(6)), and the basement needs its own stair. NBC 2016, Part 4
IfNone of these, for example a small house or a 2-storey shop
Part 4 does not bind it, but your municipal bye-laws set stairs and exits; the owner may still choose to follow Part 4. Do I need a fire NOC? NBC 2016, Part 4
Do the NBCS 2026 fire exit rules change anything?
NBC 2016 was withdrawn on 30 April 2026 and replaced by the voluntary NBCS 2026 (SP 7:2026). It gives more travel distance to sprinklered buildings; base distances are unchanged.
Fire officers still work from NBC 2016 because state laws name it; only Assam has written NBCS 2026 into its fire law, and Uttar Pradesh's OSH Rules 2026 apply its Part F to workplaces of 5 floors or 20 m. Where a state follows the new standard, the sprinklered travel distances below replace the 2016 figure of base plus 50%.
| What | The rule | Source |
|---|---|---|
| Flats and hostels | NBC 2016: 30 m, 45 m sprinklered. NBCS 2026: 30 m, 60 m sprinklered | BIS, SP 7:2026 |
| Schools, hospitals, shops and malls | NBC 2016: 30 m, 45 m sprinklered. NBCS 2026: 30 m, 45 m sprinklered | BIS, SP 7:2026 |
| Offices | NBC 2016: 30 m, 45 m sprinklered. NBCS 2026: 30 m, 60 m sprinklered | BIS, SP 7:2026 |
| Low and moderate hazard industry | NBC 2016: 45 m, 67.5 m sprinklered. NBCS 2026: 45 m, 60 m sprinklered | BIS, SP 7:2026 |
| High hazard industry | NBC 2016: 22.5 m. NBCS 2026: 22.5 m, 45 m sprinklered | BIS, SP 7:2026 |
| Dead ends and sign distance | Unchanged: 6 m or 15 m dead ends, and a sign within 30 m | BIS, SP 7:2026 |
State fire exit rules that adopt or add to the NBC
States write Part 4 into their fire rules and bye-laws, sometimes with their own numbers. Seven examples from official texts.
- Kerala, KMBR (amended 2025)
- Travel distance to an exit of 30 m, or 45 m in a fully sprinklered building; apartments of more than 16 units need at least 2 staircases, one a fire escape stair. KMBR amendment 2025
- Ladakh, Fire Rules 2025
- In every class of building: glow-in-the-dark exit signs within 30 m, emergency lights on a second power source, exit doors 1 m by 2 m, and a fire drill a year. Gazette notification S.O. 140
- Ladakh, Building Bye-laws 2024
- Travel to an exit of no more than 22.5 m on residential, educational and institutional floors. Ladakh Gazette
- Delhi, DFS nursing home sheet
- Nursing homes of ground plus 2 storeys or more need 2 staircases, the main one 2.0 m wide. DFS
- Gujarat, Regulations 2023, Regulation 14
- Pandals and temporary structures keep 4.5 m margins all round and make every exit at least 2.5 m wide. Gujarat Fire Safety Compliance Portal
- Odisha, cinema rules of 1964
- Exit doors in cinemas open outwards and are never bolted during a show. Kandhamal district
- Maharashtra, Form B guidelines 2026
- An owner who certifies Form B while exits are blocked or refuge areas misused risks criminal action under section 36 of the 2006 Act. MFS Form B guidelines
Fire exit violations inspectors find, and the fix
Most exits are built right and then undone in use. Clause 4.2.6 bars any change that cuts the number, width or protection of exits.
If An exit door padlocked or chained at night "for security".
It must open from inside without a key (4.4.2.4.1(c)). Fit panic hardware, or an access-control lock that releases on alarm and power loss. NBC 2016, Part 4
If Cartons, scooters or a generator kept in the staircase or corridor.
Clear it: exits stay free of all obstruction at all times, and no store or fire risk may open into a stair (4.2.3; 4.4.2.4.3). BIS, NBC 2016 Part 4
If New cabins or racks that lengthen the walk to an exit.
Re-measure from the most remote point along the real path; past 30 m, add an exit or open a route (4.4.2.2). NBC 2016, Part 4
If A fire door wedged open or its closer removed.
Refit the closer; exit fire doors are never held open (2.22 note 4). BIS, NBC 2016 Part 4
If Exit signs dark during a power cut.
Wire them to an independent circuit on the alternative supply and test them with the emergency lighting (3.4.7.4). BIS, NBC 2016 Part 4
If A glass or sliding door fitted as the main exit.
Overhead and sliding doors are not allowed on exits; fit a side-hung door that swings outward (4.2.9). BIS, NBC 2016 Part 4
Fire exit myths owners repeat
Five beliefs that fail an inspection, against what Part 4 says.
You may have read
The lift is our second way out.
Myth
What the sources say
Lifts and escalators are not exits (4.2.2). Part 4 buildings need at least 2 staircases. BIS, NBC 2016 Part 4
You may have read
Every door in the building must open outward.
Myth
What the sources say
Exit doors open in the direction of exit, but room doors onto a central corridor open inward so they do not block it, except in assembly rooms (4.2.9; 4.4.2.4.2(b)). BIS, NBC 2016 Part 4
You may have read
A curved or spiral stair can be the fire exit.
Myth
What the sources say
Curved stairs are not part of the means of egress, and spiral stairs are only for low occupant loads in buildings up to 9 m, at least 1,500 mm across (4.4.2.4.3.3, 4.4.2.4.3.4). BIS, NBC 2016 Part 4
You may have read
A wider corridor makes up for a narrow stair.
Myth
What the sources say
The route carries only what its narrowest part carries: a stair for 150 behind doors for 153 gives 150 (4.4.2.3(d)). NBC 2016, Part 4
You may have read
Exit signs are needed in every building.
Myth
What the sources say
The lit sign rule does not apply to houses and flats (A-2 and A-4) under 15 m, though bye-laws may still ask for them (3.4.7.4 note). BIS, NBC 2016 Part 4
Fire exit rules worked through for 4 buildings
Flamekite’s working from the official rules; no government publishes this figure.
Flamekite's own working from Tables 3, 4 and 5 and the minimum widths. Your architect and fire officer have the final word.
Case 1
An office floor of 1,200 m²
Business use, any floor over 500 m², so Part 4 applies.
What applies 120 people need 780 mm of door width and 1,200 mm of stair width. The minimums govern: 2 stairs of at least 1.50 m each and 1,000 mm doors, with every desk within 30 m of a stair door. NBC 2016, Part 4
Case 2
A school floor of 600 m²
A 3-storey school, 10 m high.
What applies 150 pupils at 4 m² each need 975 mm of doors and 1,500 mm of stairs. Two stairs of at least 1.50 m, dead ends no longer than 6 m, travel within 30 m. NBC 2016, Part 4
Case 3
A banquet hall of 400 m² with no fixed seats
Crowded assembly use, ground floor.
What applies 400 / 0.65 gives 616 guests and 4,004 mm of exit width. Two 2,000 mm doors fall 4 mm short, so the hall needs wider doors or a third exit. NBC 2016, Part 4
Case 4
A hospital ward floor of 900 m²
Indoor patients, 20 m high.
What applies 60 patients at 15 m² each need 780 mm at 13 mm a person, but the institutional minimum is a 2.00 m stair, 2 of them, with doors opening onto landings, not flights. NBC 2016, Part 4
Questions about fire exit rules
What are the fire exit requirements as per NBC of India?
What is the minimum width of a fire exit door?
How many fire exits are required in a building?
Should a fire exit door open inward or outward?
Can a fire exit door be locked?
What colour is a fire exit sign in India?
What is the difference between a fire exit and an emergency exit?
How long must emergency exit lighting last?
What is the maximum travel distance to a fire exit?
Keep reading
- NBC 2016 explainedPart 4 in full: Table 7, high-rise rules, refuge areas.
- Refuge areaWhere people wait in a tall building, and how big it must be.
- Fire towerThe protected stair, lobby and lift shaft for firefighters.
- Fire audit checklistHow auditors check exits, signs and lighting.
- Fire NOC checkerDoes your building need a fire NOC?
- NBCS 2026The voluntary 2026 standard and what changed.
- Fire extinguisher refillingWhen and how to refill, and what it costs.
Words on this page, explained
Keep exploring
More in Blog
Also in Resources
- Do I need a fire NOC?
- Fire NOC fee calculator
- Renewal date calculator
- Fire tank calculator
- Extinguisher calculator
- Fireman Salary Calculator
- Fireman Eligibility Checker
- All free tools
- New rules in 2026
- Fire safety norms
- NBC 2016
- OSH Code 2020
- Indian Standards
- Glossary
- Fire stations
- Fire accidents in India
- About Flamekite
Sources
Each source was opened and read on the date shown. How Flamekite checks its sources
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clause 4.3 and Table 3 (occupant load), 4.4.2.2 (dead ends), Table 4 (capacity factors), Table 5 (travel distance), 4.4.2.4.1 (doorways) and 4.4.2.4.3 (staircases), printed pages 29 to 34, read off the page images (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clauses 3.4.5, 3.4.6.2, 3.4.7, 4.4.2 (Tables 4 and 5), 4.4.2.5 (Table 6), 4.5.2 and Annex E (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4 Fire and Life Safety: clauses 2.16 to 2.39 (exit, exit access, exit discharge, fire door notes, fire exit, fire exit hardware), 3.4.7.1 (escape lighting), 4.2 (general exit requirements, door swing) and 4.4.2.4.2 to 4.4.2.4.3.4 (corridors, curved and external stairs) (opens in a new tab)
- Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)
- Bureau of Indian Standards (BIS-licensed copy hosted by Nagpur Municipal Corporation): National Building Code of India 2016, Part 4: clauses 1.1 and 1.2 (scope), 2.6 (height), 2.24 (firefighting shaft), 3.1.11 to 3.1.14 (mixed occupancy), 3.2 (fire zones), 3.3 and Table 1 (types of construction), 3.4.3.2 (high-rise under construction) and Table 2 (floor area ratios), printed pages 7, 9 and 17 to 20, read off the page images (opens in a new tab)
- Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)
Show all 14 sourcesShow fewer
- Uttar Pradesh Gazette Extraordinary, 27 August 2026, English translation (copy hosted by TeamLease RegTech): Uttar Pradesh Occupational Safety, Health and Working Conditions Rules, 2026, Notification No. 962/XXXVI-03-2026-1903305: rules 12, 16, 43, 45, 46, 47 and 127 (opens in a new tab)
- Local Self Government Department, Government of Kerala (Kerala Gazette Extraordinary No. 3808): Kerala Municipality Building (Amendment) Rules, 2025 (G.O.(P) No.53/2025/LSGD, S.R.O. No.1240/2025, 29 October 2025) and Kerala Panchayat Building (Amendment) Rules, 2025 (G.O.(P) No.54/2025/LSGD): rule 5(4) restated, rules 35 and 36 (opens in a new tab)
- Gazette notification S.O. 140 (copy hosted by Simpliance): Ladakh Fire Prevention and Fire Safety Rules, 2025 (S.O. 140, 28 November 2025) (opens in a new tab)
- Ladakh Gazette Extraordinary (Housing and Urban Development Department, UT Ladakh), copy on the OBPS portal: S.O. 123 of 4 November 2024 (SG-LD-E-19112024-1416): Unified Ladakh Building Bye Laws, 2024, for the municipal limits of Leh and Kargil (opens in a new tab)
- Delhi Fire Service: Fire safety requirements for nursing homes (scanned sheet, page dated 23 January 2025) (opens in a new tab)
- Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)
- District Administration, Kandhamal, Government of Odisha: Guidelines to be followed for construction of Cinema Hall in Balliguda as per the Orissa Cinemas (Regulation) Rules, 1964: licence classes, seating, gangways, exits, fire precaution and the projection enclosure (opens in a new tab)
- Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)