IS codes 20 min read

IS 2190:2024: how many extinguishers, how often to refill and hydro test, and what changed from the 2010 edition

Updated By Flamekite Editorial DeskFacts checked against official sources on

Quick answer

IS 2190:2024 is the fifth revision of India's code of practice for choosing, installing, inspecting, maintaining and testing portable and wheeled fire extinguishers. BIS published it in October 2024 and withdrew the 2010 edition on 9 April 2025. The Fire Fighting Sectional Committee, CED 22, prepared it.

On numbers: at least two extinguishers per floor (one if the floor is under 100 m²), each covering at most 100, 150 or 300 m² for high, moderate or light hazard (cl. 7.2). Water and foam types are hydro-tested every 3 years; powder, CO2 and clean agent every 5 (Annex F). Water, foam and cartridge powder units are refilled or discharge-tested every 3 years, and CO2, stored-pressure powder and clean agent units every 5 (Annex E). Service life is 10 years, or 15 for CO2 (Annex G). The standard itself is voluntary; the extinguisher product carries a compulsory BIS mark.

Current edition
IS 2190:2024
Fifth revision; the 2010 edition was withdrawn 9 April 2025
Edition history
Test pressure, water, foam, powder, clean agent
35 kg/cm²
Held for 150 seconds; CO2 is 225 kg/cm² for 30 seconds
Interval table
Light hazard floor area per extinguisher
300 m²
150 m² moderate, 100 m² high; two per floor minimum
Count by hazard
Routine check
90 days
Quarterly check, yearly maintenance; the 2024 edition dropped the monthly check
Upkeep cycle

IS 2190:2024 at a glance: edition, committee and scope

The standard's identity, scope and status in 9 facts, each with its source. Standard read 26 October 2026; BIS status read 25 October 2026.
WhatThe ruleSource
Title and editionIS 2190:2024, Selection, Installation and Maintenance of First-Aid Fire Extinguishers, Portable and Mobile, Code of Practice (fifth revision), October 2024; BIS lists it as published 18 October 2024BIS standards database
What it replacedIS 2190:2010, withdrawn on 9 April 2025. The code was first issued in 1962 and revised in 1970, 1979, 1992, 2010 and 2024BIS standards database
BIS committeeFire Fighting Sectional Committee, CED 22, approved by the Civil Engineering Division Council; the foreword says it drew significantly on ISO/TS 11602-1 and 11602-2IS 2190:2024
What it coversSelection, installation, maintenance and testing of portable and wheeled extinguishers (cl. 1.1). Portable means a working mass of 17 kg or less (cl. 3.13)IS 2190:2024
What it excludesAircraft, watercraft and vehicle extinguishers (cl. 1.4), and it is no alternative to fixed systems such as sprinklers, which are needed alongside extinguishers (cl. 1.1, 1.2)IS 2190:2024
Strength of its numbersMinimums only: larger, higher-rated or more numerous extinguishers improve protection (cl. 1.3)IS 2190:2024
Which extinguishersThe foreword limits it to ISI-marked extinguishers made to IS 15683 (portable) and IS 16018 (wheeled); cl. 4.3 requires conformity with bothIS 2190:2024
Is it compulsory?The code of practice is not a Quality Control Order product. The extinguishers themselves need the BIS mark under the Fire Extinguishers (Quality Control) Order, 2023, S.O. 3585(E) of 9 August 2023Gazette of India
AmendmentsNone appear in the copy read; BIS issues amendments as needed, so check the BIS database for the current positionIS 2190:2024

IS 2190 refilling and hydro test period by extinguisher type

Refill or discharge-test cycle (Annex E), hydro test interval and minimum pressure (Annex F) and service life (Annex G), by extinguisher type.
OptionRefill or discharge test (Annex E)Hydro test interval and minimum pressure (Annex F)Service life from manufacture (Annex G)Source
Water, stored pressureEvery 3 yearsEvery 3 years at 35 kg/cm², held 150 s10 yearsIS 2190:2024
Water, gas cartridge (9 L portable, 50 L wheeled)Every 3 yearsEvery 3 years at 35 kg/cm², held 150 s10 yearsIS 2190:2024
Foam, stored pressure or cartridgeEvery 3 yearsEvery 3 years at 35 kg/cm², held 150 s10 yearsIS 2190:2024
Dry powder, cartridge type (ABC or BC)Every 3 yearsEvery 5 years at 35 kg/cm², held 150 s10 yearsIS 2190:2024
Dry powder, stored pressureEvery 5 years; 10 percent of a test lot also gets a performance test (note 4)Every 5 years at 35 kg/cm², held 150 s10 yearsIS 2190:2024
Carbon dioxide (portable and wheeled)Every 5 yearsEvery 5 years and before every refill, at 225 kg/cm², held 30 s15 yearsIS 2190:2024
Clean agent, stored pressureEvery 5 yearsEvery 5 years and each time sent for recharge, at 35 kg/cm², held 150 s10 yearsIS 2190:2024

How to keep the IS 2190 extinguisher register: 6 steps

  1. Give every extinguisher a unique number

    Each unit gets its own identification number in the maintenance record (cl. 10.5).

  2. Record what it is

    Annex H's register holds type, capacity, year of manufacture, make and location, ideally one page per extinguisher with the permanent details at the top.

  3. Log the checks and tests

    Enter quarterly and annual inspection dates, the date it was pressure tested, the date of discharge, the date refilled and the date next due for refilling (Annex H).

  4. Tag each service

    A tag or label shows the month and year of every maintenance, recharge and hydro test and who did it, and never sits on the front of the unit (cl. 10.3, 10.4).

  5. Hold the servicer's records too

    The servicing company keeps its own record of every unit it serviced, with the date, the organisation and the person (cl. 10.1, 10.2).

  6. Record rejections

    Note the date and mode of disposal of every rejected unit, cut across the body before it leaves (cl. 12, 13).

IS 2190 2010 vs 2024: what changed and when 2010 ended

The 2024 edition removed the monthly inspection, added four annexes and a life table, and BIS withdrew the 2010 edition on 9 April 2025, but tenders still cite 2010.

  1. 1962 to 2010

    First issue in 1962, then revisions in 1970, 1979, 1992 and 2010. The 2010 revision phased out soda-acid and chemical-foam extinguishers and limited halon to essential uses such as aviation and defence. IS 2190:2024

  2. 9 August 2023

    The Fire Extinguishers (Quality Control) Order, 2023, S.O. 3585(E), made the BIS mark compulsory for the product. It applied six months after publication on 10 August 2023, nine months for small and twelve for micro enterprises. Gazette of India

  3. 20 May 2024

    IS 15683:2006, the portable extinguisher specification, was withdrawn; IS 15683:2018 is current. BIS standards database

  4. 18 October 2024

    IS 2190:2024 published. Changes it lists: monthly inspection removed with quarterly and yearly checks made more robust; new informative Annex B (hazard type criteria), Annex C (competence of servicing persons), Annex D (obsolete extinguishers) and Annex G (life of extinguishers). IS 2190:2024

  5. 9 April 2025

    IS 2190:2010 withdrawn by BIS. BIS standards database

  6. 19 January 2023 and 31 August 2026

    A university rate contract of January 2023 cited the 2010 edition for refilling, maintenance and hydraulic testing; an institute tender of August 2026 cites the 2024 edition and its record clauses. CURAJ rate contract

  7. 7 July 2026

    Maharashtra's Form B guidelines list IS 2190:2024 and ask owners to follow its clause 8 and Annexes E and F. MFS Form B guidelines

How many fire extinguishers per area under IS 2190:2024

There is no single per-square-metre figure: the standard sets a maximum floor area and a maximum walking distance per extinguisher by hazard type, with at least two on each floor.

Class A minimum ratingClass A maximum travelMaximum floor area per extinguisherClass B and C minimum ratingClass B and C maximum travel
Light hazard IS 2190:20242A20 m300 m²55B15 m
Moderate hazard IS 2190:20243A20 m150 m²144B15 m
High hazard IS 2190:20244A15 m100 m²233B15 m

Clause 7.2 and 7.3: at least 2 extinguishers per floor, or 1 where the floor is under 100 m². Higher-rated units may be used if travel distance and area per unit still hold (cl. 7.2.3). Two adjacent 2A water-type units may stand in for one 3A or 4A. For Class B and C, lower-rated units may not be added up, except up to 3 AFFF units whose ratings sum to the requirement (cl. 7.3.2). Building protection is always Class A, plus B or C units where those hazards exist (cl. 7.1.3, 7.1.6). Class D travel is 20 m and Class F 10 m (cl. 7.6.2, 7.7.2). Annex B gives example hazard criteria, not hard rules: light is under 15 occupants, under 300 m² and up to 15 m high; high is over 250 occupants, over 3,000 m² or over 15 m.

Worked examples: IS 2190 extinguisher count by floor area

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's own arithmetic from the clause 7 limits. The number is the larger of the area count and what the travel distance needs, so check the walking distance on the plan.

  1. Case 1

    A small shop

    One floor of 80 m², light hazard

    What applies Under 100 m², so one 2A extinguisher may be provided (cl. 7.2.2). Two is still the safer plan when the floor has two exits. IS 2190:2024

  2. Case 2

    An open-plan office floor

    One floor of 1,200 m², light hazard

    What applies 1,200 divided by 300 is 4 extinguishers of at least 2A, no point more than 20 m from one (cl. 7.2, Table 1 limits). Walls and corridors often push the count higher. IS 2190:2024

  3. Case 3

    A workshop with paint and solvents

    600 m² floor, moderate hazard, flammable liquids present

    What applies 600 divided by 150 is 4 extinguishers of at least 3A, plus Class B units of at least 144B within 15 m of the liquids (cl. 7.1.6, 7.3). A dip or quench tank adds 144 units of B rating per square metre of fire area (cl. 7.4.1). IS 2190:2024

  4. Case 4

    A storeroom

    400 m² floor, high hazard

    What applies 400 divided by 100 is 4 extinguishers of at least 4A, none more than 15 m away (cl. 7.2.1), with 233B units for any flammable liquid hazard. IS 2190:2024

  5. Case 5

    A restaurant fryer

    Cooking area of 0.04 m²

    What applies Class F units are sized by cooking area: 5F covers up to 0.03 m², 15F up to 0.05 m², 25F up to 0.08 m² and 75F up to 0.25 m², so 15F is the smallest fit, within 10 m (cl. 7.7). IS 2190:2024

IS 2190 vs IS 15683, IS 16018 and the 2023 QCO

IS 2190 tells you how to choose, place and look after extinguishers. The product standards and the Quality Control Order decide what an extinguisher must be to be sold.

IS 2190:2024
Code of practice: selection, installation, maintenance, testing and records. It sets counts, distances, intervals, test pressures and life. It is not a product test standard. IS 2190:2024
IS 15683:2018
Portable extinguisher performance and construction specification, for units not above 17 kg when fully charged. It defines the classification and ratings (2A, 55B, 5F) that IS 2190 relies on. The 2006 edition was withdrawn on 20 May 2024. BIS blog
IS 16018:2012
Wheeled extinguisher specification, for units over 17 kg and under 450 kg with accessories. IS 2190 covers both portable and wheeled units (cl. 4.2). BIS blog
QCO, S.O. 3585(E)
The Fire Extinguishers (Quality Control) Order, 2023 (9 August 2023, Gazette No. 3431 of 10 August 2023) makes the ISI mark compulsory for extinguishers sold in India, with export goods exempt. It governs the product, not the upkeep. Gazette of India
IS 4308, IS 4989, IS 15222
Referred standards for dry powder (BC, ABC, D types, 2019 edition), foam concentrate (2018) and CO2 as an extinguishing medium (2002). IS 2190 requires CO2 refills to meet IS 15222 and to come from an approved filling agency (cl. 9.14). IS 2190:2024

Installing extinguishers to IS 2190: height, cabinets, signs

Clause 5 sets how and where a unit hangs. The two numbers to remember are 1.5 m and 30 mm.

Do

  • Hang units of 17 kg or less so the top is not above 1.5 m from the floor, with at least 30 mm between the bottom and the floor (cl. 5.8). IS 2190:2024
  • Place them on normal paths of travel, including exits, where they are readily accessible (cl. 5.2). IS 2190:2024
  • Turn the operating instructions outward and keep the maintenance and hydro-test labels clear of them (cl. 5.9); service labels never go on the front (cl. 10.4). IS 2190:2024
  • Use specially designed brackets where vibration or dislodgement is likely and impact protection where damage is likely (cl. 5.6, 5.7). IS 2190:2024
  • Fit outdoor or hot-area cabinets with vent openings, a bottom drain and a mesh screen (cl. 5.10). IS 2190:2024
  • Put a location sign close to the unit and visible from the normal path where the unit cannot be seen (cl. 5.4). IS 2190:2024

Don’t

  • Lock a cabinet, unless vandalism is a risk and the lock has an emergency access means (cl. 5.3). IS 2190:2024
  • Mount a unit where the temperature leaves the range marked on it, or near heat sources (cl. 5.11). IS 2190:2024
  • Treat fire buckets as a replacement: the foreword does not recommend them in place of extinguishers, though they may be added on top. IS 2190:2024
  • Mix powder types such as BC, ABC and D, or convert an extinguisher to another type or medium (cl. 9.7, 9.8). IS 2190:2024
  • Pressurise a stored-pressure powder or clean agent unit with compressed air, or from an unregulated cylinder (cl. 9.17, 9.18). IS 2190:2024
  • Reuse the powder left in a discharged extinguisher (cl. 9.9). IS 2190:2024

IS 2190 extinguisher upkeep: quarterly check to 5-year test

Seven stages, from the first placement to the end of life. The owner or the owner's agent is responsible for all of them (cl. 8.2.1).

  1. Placement and about every 90 days

    Check a unit when first placed and at approximately 90 day intervals, more often if conditions need it (cl. 8.3.1). The check covers place, visibility, legible instructions, intact seals, full charge by weighing or hefting, no damage or clogged nozzle, gauge in the operable range, secure bracket, intact tags and hose band (cl. 8.3.2). Servicing needs a competent person (cl. 8.2.2). IS 2190:2024

  2. Yearly maintenance

    Once a year, not less than six months apart, at hydro testing, and whenever an inspection calls for it (cl. 8.4.1). Each service checks whether the seal or safety device shows use, fits a new seal and labels the unit. Five categories of unit get different procedures; a gas cartridge below 10 percent of its gross weight or leaking is withdrawn (Table 4). IS 2190:2024

  3. Refill or discharge test: 3 or 5 years

    Annex E puts water, foam and cartridge-type powder units on a 3 year cycle, and CO2, stored-pressure powder and clean agent units on a 5 year cycle, spread across the year. In corrosive environments the discharge test is better done at half the interval (Annex E note 1). IS 2190:2024

  4. Five-year maintenance

    Stored-pressure water, foam, powder and clean agent units (categories 1 and 2) and CO2 units (category 5) get a full discharge, internal inspection, new seals where needed, reassembly and recharge at intervals not above 5 years (cl. 8.4.2.5, Table 5). The safety device is replaced once in five years (cl. 8.4.2.1). IS 2190:2024

  5. Hydrostatic test

    Interval and pressure by type in Annex F; the test must show no leakage or visible distortion. Rupture discs are replaced after every hydro test or at 5 years, whichever is sooner, and gauges are replaced or calibrated at the test (cl. 10.6, 10.7). CO2 units are always hydro-tested before a refill (cl. 10.8). IS 2190:2024

  6. Recharge after any use

    Recharge after any discharge or when a check finds a defect, to the mass on the label and with a leak test for stored-pressure units (cl. 9.1, 9.3, 9.4). A unit out of service is replaced at once by a spare of equal type and rating (cl. 8.2.4). IS 2190:2024

  7. End of life

    Life counts from the date of manufacture: 10 years for water, foam, powder and clean agent and 15 years for CO2 (Annex G). Non-rechargeable units are discharged and discarded within 5 years of manufacture (cl. 8.4.2.5). IS 2190:2024

Which extinguisher IS 2190 selects by fire class and hazard

Clause 6 matches the extinguisher to the fire class first, then clause 7 sizes it by hazard.

  1. If Wood, paper, cloth and other solids (Class A)?

    Use an extinguisher with a Class A rating. Every building needs Class A units for the building itself, even where flammable liquids or gases are present (cl. 6.3.2, 7.1.3, 7.1.6). IS 2190:2024

  2. If Flammable liquids or gases (Class B or C)?

    Choose on the Class B rating; Class C uses the same selection as Class B (cl. 6.3.3, 6.3.4). Burning liquid in motion, or a pressurised gas or liquid jet, is outside the rating system: powder is the only relatively effective medium, and the choice rests on a qualified fire professional, the authority or the maker. Shut off the fuel first (cl. 6.4). IS 2190:2024

  3. If Alcohol or other water-soluble liquids?

    AFFF and film-forming fluoroprotein foam units are not suitable unless the nameplate says so; use alcohol-resistant or multipurpose foam (cl. 6.4.3). IS 2190:2024

  4. If Live electrical equipment?

    CO2, powder, clean agent or water mist units that are tested and marked for it. CO2 units with metal horns are not safe on energised equipment (cl. 6.3.7). IS 2190:2024

  5. If Delicate electronics or a server room?

    Use a clean agent where a clean medium is needed. Powder can put out the fire but its residue can badly damage the equipment (cl. 6.2, 6.3.7). IS 2190:2024

  6. If Combustible metals (Class D)?

    A type marked for that specific metal; the size and number depend on the metal and its particle size (cl. 6.3.5, 7.6). IS 2190:2024

  7. If Cooking oil or fat (Class F)?

    An extinguisher with a marked Class F rating, within 10 m (cl. 6.3.6, 7.7). IS 2190:2024

  8. If High hazard needing more flow, throw or capacity?

    Consider wheeled extinguishers (cl. 6.4.4); for a big flammable liquid hazard they sit alongside, not instead of, portable Class B units (cl. 7.4.3). IS 2190:2024

When IS 2190 says discard, destroy or cut up an extinguisher

The standard lists 11 conditions at which a shell is destroyed rather than hydro-tested, plus rules for failures, old types and disposal.

  • If Shell repaired by soldering, welding, brazing or patching; worn, corroded or cracked threads; pitting; exposure to fire or excessive heat; dents deeper than 1/10 of their longest dimension (6 mm in a weld); more than 10 percent of wall thickness lost; or used for another purpose.

    Do not hydro-test. The owner destroys the cylinder (cl. 11.1.3). IS 2190:2024

  • If A cylinder, shell or cartridge fails the hydro test, which means leakage or visible distortion.

    Condemn and destroy it, and replace it with the same type and fire rating (cl. 11.4, Annexes F and G). IS 2190:2024

  • If A non-rechargeable unit is more than 5 years from its date of manufacture.

    Discharge and discard it; a non-rechargeable clean agent unit goes to a recycling centre for recovery (cl. 8.4.2.5). IS 2190:2024

  • If Soda-acid, chemical foam, carbon tetrachloride or chlorobromomethane, inverting, and soft-soldered or riveted copper, brass or steel shells.

    Remove from service as obsolete (Annex D). IS 2190:2024

  • If A gas cartridge is under 10 percent of its gross weight or leaking, or powder is caked, lumpy or past the maker's shelf life.

    Withdraw or replace the cartridge; discard all the powder and recharge with the original maker's powder (Table 4). IS 2190:2024

  • If A rejected extinguisher is headed for scrap.

    Cut it across the body so it cannot be used again, and record the date and mode of disposal in the register (cl. 13). IS 2190:2024

IS 2190 myths on refilling, hydro tests and the 2010 edition

Five claims that circulate about the code, set against its text.

  • You may have read

    IS 2190:2010 is still the code.

    Myth

    What the sources say

    BIS withdrew it on 9 April 2025. The 2024 edition is current, though the fire services' standards list still shows 2010. BIS standards database

  • You may have read

    Every extinguisher is hydro-tested every 5 years.

    Myth

    What the sources say

    Annex F sets 3 years for water and foam types and 5 for powder, CO2 and clean agent. CO2 and clean agent cylinders are also tested each time they are sent for recharging. IS 2190:2024

  • You may have read

    IS 2190 asks for a monthly check.

    Myth

    What the sources say

    The 2024 edition removed the monthly inspection. The check is about every 90 days, with yearly maintenance (cl. 8.3.1, 8.4.1). A hospital or state order may still ask for monthly checks. IS 2190:2024

  • You may have read

    Refill every year.

    Myth

    What the sources say

    Yearly is the maintenance cycle. Refill or discharge test is 3 or 5 years by type (Annex E), and any use triggers a recharge (cl. 9.1). IS 2190:2024

  • You may have read

    The rule is one extinguisher per 200 m².

    Myth

    What the sources say

    IS 2190 gives 100, 150 or 300 m² per extinguisher by hazard, with a two-per-floor minimum. The 200 m² figure is Mizoram's draft rule 57(B), which is not yet Gazetted. IS 2190:2024

Who names IS 2190: state rules, NBCS 2026 and tenders

The code binds only through something that names it. These are the instruments found on 26 October 2026.

None of these changes the standard's numbers; where a state asks for more, the stricter figure governs for that state.

Instruments that cite IS 2190, and where they differ from the 2024 text.
WhatThe ruleSource
NBCS 2026 (SP 7:2026), Part FIS 2190:2024 appears in the code's reference list of standards.BIS, SP 7:2026
Maharashtra Form B guidelines, 7 July 2026List IS 2190:2024 and ask owners to follow clause 8 and Annexes E and F; recharge on a loss of more than 10 percent of mass or pressure; water stored-pressure units discharge-tested every 2 years (the standard's Annex E cycle is 3 years); gauges and safety valves on large units calibrated once in 3 years.MFS Form B guidelines
Gujarat Regulations 2023, Annexure 12Inspector checklist: hydro test every 5 years for CO2 and every 3 years for DCP, foam and water extinguishers. The standard's Annex F gives 5 years for powder.Gujarat Fire Safety Compliance Portal
Mizoram Amendment Rules 2026, r.57(B)Extinguishers per IS 2190, one per 200 m². Not in force until Gazetted; the 2019 rules apply meanwhile.Mizoram Home Dept
IISc tender, 31 August 2026Records per clauses 13 and 14.1 of IS 2190:2024. The 2024 text ends at clause 13 (rejected extinguishers); record-keeping is clauses 10 and 12 and Annex H.IISc tender
University rate contract, 19 January 2023Cites IS 2190:2010 for refilling, maintenance and hydraulic testing; that edition is now withdrawn.CURAJ rate contract

IS 2190:2024 details we could not confirm

Gaps in this page, so you do not rely on them.

  • Whether any amendment to the 2024 edition exists: none appears in the copy read. Check the BIS standards database. IS 2190:2024
  • Which editions and extinguisher sizes the 2023 QCO schedule names: read only through BIS's own blog, not the schedule. BIS blog
  • OISD-STD-142 (reported to adopt the 2024 revision for oil and gas sites): its server failed the certificate check, so it was not opened and nothing from it is used. BIS blog
  • Ratings by capacity (for example which size carries 2A or 55B) and each type's factory test pressure: these sit in IS 15683 and IS 16018, not IS 2190, and were not read here (cl. 11.3.1, 4.2). IS 2190:2024
  • Whether any state or Indian body licenses or enforces Annex C competence (3 months of practical experience, a course of at least 32 hours, a 4-hour refresher at least every 5 years). The annex is guidance. IS 2190:2024
  • Whether each state fire service accepts the 2024 edition now: the DGFS list still shows 2010, and no state-by-state position was found. BIS standards database

Questions about IS 2190

What is the latest version of IS 2190?

IS 2190:2024, the fifth revision, published by BIS in October 2024 (18 October on the BIS database). It replaced IS 2190:2010, which BIS withdrew on 9 April 2025.

Is IS 2190:2010 still valid?

No. It was withdrawn on 9 April 2025, but older tenders and state lists still name it. Contracts should name the edition in force on their date.

What is the fire extinguisher refilling period as per IS 2190?

Annex E: every 3 years for water, foam and cartridge-type powder units, and every 5 years for CO2, stored-pressure powder and clean agent units. A unit is recharged after any use (cl. 9.1).

What is the fire extinguisher hydro test period?

Annex F: every 3 years for water and foam types at 35 kg/cm² for 150 seconds; every 5 years for powder (35 kg/cm², 150 seconds), CO2 (225 kg/cm², 30 seconds) and clean agent (35 kg/cm², 150 seconds). CO2 and clean agent are also tested at each recharge.

How often must extinguishers be inspected and maintained?

Checked about every 90 days and maintained once a year, at least six months apart (cl. 8.3.1, 8.4.1). The 2024 edition removed the monthly inspection.

How many fire extinguishers are required per sq m?

One per 100 m² (high hazard), 150 m² (moderate) or 300 m² (light) at most, and at least two per floor, or one under 100 m² (cl. 7.2). Class A travel distance is 20 m, or 15 m in high hazard.

What is the difference between IS 2190 and IS 15683?

IS 2190 is the code of practice for selecting, installing and maintaining; IS 15683:2018 is the product specification for portable extinguishers (IS 16018:2012 for wheeled). The product needs the BIS mark under the 2023 QCO.

How long does an extinguisher last?

Annex G: 10 years for water, foam, powder and clean agent types and 15 years for CO2, counted from manufacture. A unit that fails a hydro test is discarded at once.

Which extinguisher is used on an electrical fire?

CO2, powder, clean agent or water mist types that are tested and marked for energised equipment. CO2 with metal horns is not considered safe on it (cl. 6.3.7).

Keep reading

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards: IS 2190:2024, Selection, Installation and Maintenance of First-Aid Fire Extinguishers (Portable and Mobile), Code of Practice, fifth revision (free download after registration) (opens in a new tab)checked 26 October 2026
  2. Bureau of Indian Standards, Know Your Standards database: Status records read 25 October 2026 for IS 2189, IS 2190, IS 15683, IS 16018, IS 3844, IS 13039, IS 15105, IS 15301, IS 9668, IS 12349, IS 3614, IS 2175 and IS 11360 (current or withdrawn, with dates) (opens in a new tab)checked 25 October 2026
  3. Bureau of Indian Standards (BIS 2.0 blog): Standards on fire extinguishers: IS 2190, IS 15683:2018, IS 16018:2012, fire classes A, B, C, D and F, ISI Mark and the Fire Extinguishers (Quality Control) Order, 2023 (opens in a new tab)checked 26 October 2026
  4. Department for Promotion of Industry and Internal Trade, Gazette of India Extraordinary No. 3431, 10 August 2023: Fire Extinguishers (Quality Control) Order, 2023, S.O. 3585(E), 9 August 2023: IS 15683:2018 and IS 16018:2012 (opens in a new tab)checked 26 October 2026
  5. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  6. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
Show all 10 sourcesShow fewer
  1. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 25 October 2026
  2. Home Department, Government of Mizoram (copy on the Mizoram Fire and Emergency Services site): Notification No. B-20011/2/2026-HM(F&ES), 20 August 2026: Mizoram Fire and Emergency Services (Superintendence and Control of the Fire Force and Fire Safety and Prevention) (Amendment) Rules, 2026, substituting Rule 57 and inserting Rules 57(A) and 57(B) (opens in a new tab)checked 25 October 2026