Skip to content
Flamekite
ContactFree fire NOC check

Glossary 17 min read

Refuge area: what it is, when a high-rise needs one, and how big it must be

Updated By Flamekite Editorial DeskFacts checked against official sources on

Quick answer

A refuge area is the fire-safe staging space a building over 24 m keeps every 15 m or so: 0.3 m² a person for two floors, never under 15 m², per NBCS 2026.

It sits on the outer edge of a floor, open to the air on one side, and connects to the firefighting shaft so people who cannot use the stairs can wait there and be brought down by the fireman's lift. High-rise flats with balconies are exempt. NBCS 2026 is voluntary: your state's rules decide, and several set their own numbers, such as Rajasthan's 10% of the floor and Goa's 15 m².

Required in buildings
Over 24 m
Then every 15 m or so
At a glance
Space for each person
0.3 m²
Counting two floors of occupants
The numbers
Never smaller than
15 m²
Goa uses the same figure
State rules
Rajasthan minimum
10%
Of the floor's gross built-up area
State rules

Refuge area at a glance

The refuge area as NBCS 2026 Part F defines and sizes it, with the source of each fact.
WhatThe ruleSource
MeaningA space inside the building, protected from fire and smoke, used for a short time during escape as a staging areaBIS, SP 7:2026
Where the rule isDefinition in clause 2.57 of NBCS 2026 Part F; the requirement in Annex D-4.2, the high-rise annexBIS, SP 7:2026
Required inBuildings over 24 m; Part F calls a building of 24 m or above a high rise (clause 2.39)BIS, SP 7:2026
Where it goesAt or just above 24 m, then every 15 m or so, on the edge of the floor and open to air on at least one sideBIS, SP 7:2026
How big0.3 m² a person for the occupants of two floors, plus a 0.9 m² wheelchair space for every 200 people, or 15 m², whichever is moreBIS, SP 7:2026
The alternativeRefuge spaces in the firefighting-shaft lift lobby on every floor: 12 m², or 5% of the floor's occupants at 0.45 m² each, whichever is moreBIS, SP 7:2026
ExemptHigh-rise apartment buildings whose flats have balconiesBIS, SP 7:2026
Floor area ratioRefuge area beyond what the rule needs counts towards FARBIS, SP 7:2026
Malls and similarFrom 18 m: 10% of the gross floor area, in pieces of at least 100 m²BIS, SP 7:2026
Legal forceNBCS 2026 is voluntary; state instruments such as Tripura's Fire Safety Rules 2026 make a refuge area compulsoryDirectorate of Fire and Emergency Services, Tripura

Refuge area in NBC 2016 and NBCS 2026

What changed for refuge areas when NBCS 2026 replaced NBC 2016 on 30 April 2026. The NBC 2016 column comes from BIS's own history of the 2016 revision and from state documents that applied it; Flamekite did not read the 2016 text itself.
OptionNBC 2016NBCS 2026 Part FSource
StatusWithdrawn by BIS on 30 April 2026Current from 30 April 2026, voluntaryGazette of India
Starts above24 m, as Odisha's 2023 fire safety recommendation applied it24 mOFES Form-II, Cuttack
Repeats every15 m15 m or soOFES Form-II, Cuttack
Apartments above 60 m with balconiesRefuge introduced in the 2016 revision: at 60 m, then every 30 mOnly where refuge areas are chosen over refuge spaces: around 60 m, then about every 30 mBIS, SP 7:2026
Mixed assembly and mallsRule updated for D-6 mixed assembly occupancyMall-like occupancy: from 18 m, 10% of the floorBIS, SP 7:2026
Refuge spaces in the shaft lobbyNot confirmed: the 2016 text was not readAllowed: 12 m², or 5% of occupants at 0.45 m² eachBIS, SP 7:2026
Link to the firefighting shaftShaft and refuge staging brought together in the 2016 revisionRefuge must open to the shaft without sending people back through the floorBIS, SP 7:2026
Wording"shall""should"The Times of Indianews report

How to size a refuge area in five steps

  1. Find the occupant load of one floor

    Divide the floor area by the Table 2 factor of Part F: 7.1 m² a person (net) for offices, 12.5 m² for homes, 3.0 m² for schools. Round up.

  2. Add the floor above

    A refuge area holds the people of two floors: the floor it is on and the floor above it.

  3. Multiply and add wheelchair space

    Allow 0.3 m² for each person, then add 0.9 m² for every 200 people or part of 200.

  4. Compare with 15 m² and your state's figure

    Take the larger of your result and 15 m². Then check your state: Rajasthan, for example, asks for 10% of the floor's gross built-up area if that is more.

  5. Place it

    Put the first one at or just above 24 m and the next about 15 m higher, on the outer edge, open to air on one side, opening straight into the firefighting shaft.

Refuge area definition in NBCS 2026 clause 2.57

The national standard defines a refuge area in two sentences, and adds an alternative that most older definitions lack.

Word for word

An area within the building for a temporary use during egress.

SP 7:2026, National Building Construction Standards 2026, Part F, clause 2.57 BIS, SP 7:2026

The clause goes on to call it a staging area protected from fire and smoke, and says lift-lobby spaces of enough size inside the firefighting shaft on every floor, called refuge spaces, can take its place. Its note says these spaces give people who cannot get themselves out a place to wait on any floor. A refuge area is a waiting point on the way out, not a shelter to stay in.

Refuge area numbers in NBCS 2026

Every figure in Annex D-4.2 and the clauses around it.

  • 24 m

    Height above which a refuge area is required, and where the first one goes BIS, SP 7:2026

  • 15 m

    Approximate spacing between refuge areas above the first BIS, SP 7:2026

  • 0.3 m²

    Space for each person, counting the refuge floor and the floor above BIS, SP 7:2026

  • 15 m²

    Smallest refuge area allowed, whatever the head count BIS, SP 7:2026

  • 0.9 m²

    Wheelchair space added for every 200 occupants or part of 200 BIS, SP 7:2026

  • 12 m²

    Smallest refuge space in a firefighting-shaft lift lobby, the alternative route BIS, SP 7:2026

  • 75 mm

    Minimum letter height of the REFUGE AREA sign at the entry BIS, SP 7:2026

  • 18 m

    Height of the first refuge area in a mall-like building, sized at 10% of the floor BIS, SP 7:2026

Refuge area rules by state

NBCS 2026 is only a guide, so the rule that binds your building is your state's. These are the instruments Flamekite read; a state not listed here was not checked for refuge numbers.

First refugeThen everyMinimum sizeFlats with balconies
NBCS 2026 Part F (national guide) BIS, SP 7:2026Above 24 m15 m or so0.3 m² a person for 2 floors, or 15 m²Exempt; above 60 m, optional refuge every 30 m
Tripura, Fire Safety Rules 2026 Directorate of Fire and Emergency Services, TripuraAbove 24 m15 m or soSame formula, or 15 m²Exempt up to 60 m; above 60 m, at 60 m and every 30 m
Goa, DFES inspection checklist Directorate of Fire and Emergency Services, GoaAbove 24 mNot stated15 m² for buildings of 24 to 39 mNot stated
Gujarat, Regulations 2023 (15.27) Gujarat Fire Safety Compliance PortalJust above 25 m (clause b also says every 18 m)15 m, above 39 m15 m², at least 0.75 m wide; a second one on floors over 1,000 m²Exempt
Rajasthan, Model Regulations 2025 (5.4) Rajasthan UDHJust above 24 m15 m, above 39 m10% of the floor's gross built-up area, or 15 m²Exempt if every unit has a terrace or balcony
Odisha, fire safety recommendation 2023 OFES Form-II, CuttackAbove 24 m15 mNot stated in the documentAbove 60 m: at 60 m and every 30 m
Delhi, Fire Service Rules 2010 (rule 33) Delhi Fire ServiceAs the bye-laws or NBC 2005 setAs the bye-laws setNot in the rulesNot in the rules
Meghalaya, Building Bye-Laws 2021 (B9.10) Bye-Laws 2021As NBC 2016 recommendsAs NBC 2016 recommendsAs NBC 2016 recommendsAs NBC 2016 recommends

Maharashtra enforces NBC 2016 Part 4 by circular MFS/2017/60 and checks refuge areas twice a year through Form B; Kerala's fire service checks the refuge area at high-rise inspections. Their own size rules were not confirmed.

What every refuge area must have under NBCS 2026

Annex D-4.2 lists ten conditions. An inspector can fail a refuge area on any one of them.

  • On the edge of the floor, open to air on at least one side, with railings BIS, SP 7:2026
  • A REFUGE AREA sign at the entry in letters of at least 75 mm, saying where the refuge areas above and below are, repeated inside BIS, SP 7:2026
  • Ventilation, a first-aid box, fire extinguishers, a public address speaker, fireman's talk-back, emergency lighting and drinking water BIS, SP 7:2026
  • An accessible route to it from the space it serves BIS, SP 7:2026
  • A direct connection to the firefighting shaft (fireman's lift, lobby and staircase) BIS, SP 7:2026
  • Kept clear: no combustible storage and no electrical or mechanical equipment BIS, SP 7:2026
  • Drainage for rainwater BIS, SP 7:2026
  • Sprinklers over the whole area BIS, SP 7:2026
  • Ramps no steeper than 1 in 12 where levels differ, and no steps BIS, SP 7:2026
  • No gas lines through it (clause 4.7.8) BIS, SP 7:2026

Refuge area worked out for four buildings

Flamekite’s working from the official rules; no government publishes this figure.

Flamekite's own arithmetic from Annex D-4.2 and the Table 2 occupant loads. Your architect's figures and the fire service's approval decide.

  1. Case 1

    40 m office tower

    1,000 m² net per floor, business occupancy at 7.1 m² a person: 141 people a floor, 282 for two floors.

    What applies 282 x 0.3 = 84.6 m², plus 2 wheelchair spaces of 0.9 m² = 86.4 m² at each refuge level: one at or just above 24 m and one near 39 m. BIS, SP 7:2026

  2. Case 2

    30 m office on a small plot

    150 m² net per floor: 22 people a floor, 44 for two floors.

    What applies 44 x 0.3 = 13.2 m², plus 0.9 m² = 14.1 m². That is under the floor of 15 m², so 15 m² applies. BIS, SP 7:2026

  3. Case 3

    50 m apartment block without balconies

    800 m² per floor at 12.5 m² a person: 64 people a floor, 128 for two floors.

    What applies 128 x 0.3 = 38.4 m², plus 0.9 m² = 39.3 m², at about 24 m and 39 m. Give every flat a balcony and NBCS asks for no refuge area at all. BIS, SP 7:2026

  4. Case 4

    The same office tower in Rajasthan

    1,000 m² floor (taken as gross built-up area for this comparison), 40 m, in a city under the Model Building Regulations 2025.

    What applies Regulation 5.4(iii) asks for 10% of the floor or 15 m², whichever is more: 100 m², above the 86.4 m² NBCS gives. The stricter state figure binds. Rajasthan UDH

Refuge area, refuge space and the other routes in NBCS 2026

Part F gives a building more than one way to stage people who cannot use the stairs. The building type decides which apply.

  • Annex D-4.2(c)

    Refuge area on the edge of the floor

    The classic form: one open-sided area every 15 m or so above 24 m, sized for two floors. BIS, SP 7:2026

  • Annex D-4.2(b)

    Refuge space in every shaft lobby

    Space in the firefighting-shaft lift lobby on each floor: 12 m² or 5% of the floor's occupants at 0.45 m² each. The 12 m² governs until a floor holds about 534 people. BIS, SP 7:2026

  • Annex D-4.2

    Balconies in every flat

    High-rise apartments whose flats have balconies need no refuge area; flats without balconies need refuge spaces or areas. BIS, SP 7:2026

  • Clause 6.4.2.2

    Malls and multiplexes

    A refuge area of 10% of the floor at or above 18 m and again above 24 m, or refuge spaces for 20% of each floor's occupants. BIS, SP 7:2026

  • Clause 6.3.2

    Hospital refuge terraces

    Covered terraces open to air on alternate patient floors, with medical gas for patients on ventilators, a 2-hour fire door and direct access to the fire tower. BIS, SP 7:2026

  • Clause 2.40

    Horizontal exit

    A 120-minute fire door in a fire wall leading to a refuge area or another compartment on the same level, for defend-in-place staging. BIS, SP 7:2026

Does your building need a refuge area?

Find the first line that matches your building, then check your state's rule in the table above.

  1. If It is a mall, multiplex or similar mix of shops, cinemas and restaurants taller than 18 m

    Yes, from 18 m: 10% of the gross floor area, in pieces of at least 100 m². BIS, SP 7:2026

  2. If It is an apartment block over 24 m and every flat has a balcony

    Not under NBCS 2026, Gujarat or Rajasthan. In Tripura it still needs one at 60 m and every 30 m above that. Directorate of Fire and Emergency Services, Tripura

  3. If It is any other building over 24 m

    Yes: a refuge area every 15 m or so, or refuge spaces in the firefighting-shaft lobby on every floor. BIS, SP 7:2026

  4. If It is a hospital

    Plan refuge terraces on alternate floors that house patients, sized as your local authority sets. BIS, SP 7:2026

  5. If It is in Rajasthan and 24 m or taller

    Yes, mandatory under regulation 5.4(iii): 10% of the floor or 15 m², unless every home has a terrace or balcony. Fire NOC Rajasthan Rajasthan UDH

  6. If It is 24 m or lower and not mall-like

    NBCS 2026 asks for none, but Gujarat's regulation 15.27 also mentions a refuge at every 18 m: read your state's rule. Gujarat Fire Safety Compliance Portal

Refuge area mistakes that fail a fire inspection

The rule is simple to draw and easy to undo once people move in.

  • If Turning the refuge area into a store, gym or lounge

    Part F says it must always be clear of combustible goods and equipment. In Maharashtra the owner signs, every six months, that refuge areas have not been misused. MFS Form B guidelines

  • If Glazing it in to match the facade

    It must be open to air on at least one side. Jammu and Kashmir's bye-laws require every glass panel over a refuge area to open fully from inside and outside. J&K H&UDD

  • If Reaching it only by walking back across the floor

    It must open into the firefighting shaft so people never return through the spaces they fled. BIS, SP 7:2026

  • If Sizing it for one floor

    Count the occupants of two floors: the refuge floor and the one above. BIS, SP 7:2026

  • If Drawing extra refuge area to gain free floor space

    Anything beyond the requirement counts towards FAR. BIS, SP 7:2026

  • If No sign, or a sign that does not say where the next refuge is

    Fix a REFUGE AREA sign with 75 mm letters at the entry and inside, naming the refuge floors above and below. BIS, SP 7:2026

Four refuge area myths

  • You may have read

    A refuge area is where you sit out the fire.

    Myth

    What the sources say

    It is a staging point: people who cannot use the stairs wait there and are taken down by the fireman's lift in the firefighting shaft. BIS, SP 7:2026

  • You may have read

    15 m² is the refuge area size.

    Myth

    What the sources say

    15 m² is only the floor. A busy floor needs much more: 86.4 m² for a 1,000 m² office floor in Flamekite's worked example. BIS, SP 7:2026

  • You may have read

    Every high-rise needs a refuge floor.

    Myth

    What the sources say

    Apartments with balconies are exempt under NBCS 2026, and other buildings may use refuge spaces in the shaft lobby instead. BIS, SP 7:2026

  • You may have read

    Withdrawing NBC 2016 ended the refuge area rule.

    Myth

    What the sources say

    State instruments still require it: Tripura's Fire Safety Rules 2026 and Rajasthan's Model Building Regulations 2025 both do. Directorate of Fire and Emergency Services, Tripura

How the refuge area rule developed, 2016 to 2026

  1. 2016

    The NBC 2016 revision updates the refuge area rules, including for mixed assembly buildings, and brings them to apartment buildings of 60 m and above. BIS, SP 7:2026

  2. 17 May 2017

    Maharashtra Fire Services circular MFS/2017/60 tells every municipal body to enforce NBC 2016 Part 4. Maharashtra Fire Services

  3. 28 August 2020

    Odisha's relaxation scheme for older buildings accepts a 10 m² refuge area where a high-rise's two stairs are narrower than 1.5 m. Notification 28550 of 2020

  4. 25 March 2021

    Meghalaya's Building Bye-Laws tie refuge areas in high-rise and special buildings to NBC 2016. Bye-Laws 2021

  5. 13 December 2023

    Gujarat publishes its Fire Prevention and Life Safety Measures Regulations, with refuge rules in regulation 15.27. Gujarat Fire Safety Compliance Portal

  6. 12 May 2025

    Rajasthan's Model Building Regulations make a refuge area of 10% of the floor or 15 m² mandatory at 24 m and above. Rajasthan UDH

  7. 30 April 2026

    NBCS 2026 replaces NBC 2016; the refuge rule moves to Annex D-4.2 of Part F and adds lobby refuge spaces. Gazette of India

  8. 2 June 2026

    Tripura's Fire Safety Rules 2026 are published with a compulsory refuge area above 24 m. Directorate of Fire and Emergency Services, Tripura

  9. 7 July 2026

    Maharashtra's Form B guidelines require licensed agencies to show refuge areas free of obstruction and misuse. MFS Form B guidelines

Words used with refuge area

Plans and rules use these terms around the refuge area. Six are defined in Part F itself.

Refuge space
Staging space in the firefighting-shaft lift lobby on every floor, an alternative to a refuge area; at least 12 m². BIS, SP 7:2026
Refuge floor
A floor that carries the refuge area. Part F says exits run continuously from refuge floors down to the exit discharge. BIS, SP 7:2026
Skip floor
Gujarat's word, paired with refuge area, for buildings of 45 to 70 m, where its regulations defer to the CGDCR. Gujarat Fire Safety Compliance Portal
Staging
Holding people safely for a short time before assisted evacuation, the job a refuge area does. BIS, SP 7:2026
Horizontal exit
A 120-minute fire door in a fire wall to a refuge area or another compartment at the same level (clause 2.40). BIS, SP 7:2026
Firefighting shaft
The protected lobby, stair and fireman's lift every refuge area must open into, also called a fire tower (clause 2.24). BIS, SP 7:2026
Fireman's lift
The lift in the shaft that fire fighters use, and that brings people down from a refuge area (clause 2.27). BIS, SP 7:2026
Refuge area (Rajasthan)
Regulation 2.76: a space in the building used as a temporary staging area, safe from fire and smoke, during escape. Rajasthan UDH

Refuge area upkeep for owners and residents' associations

Do

  • Test the public address speaker, the fireman's talk-back and the emergency lights in the refuge area with every fire drill. BIS, SP 7:2026
  • Keep the drain clear and the sprinklers unobstructed: Part F requires both over the whole area. BIS, SP 7:2026
  • Keep photographs of clear refuge areas: Maharashtra's licensed agencies must show them free of misuse twice a year. MFS Form B guidelines

Don’t

  • Don't let anyone enclose, rent out or store goods in the refuge area. BIS, SP 7:2026
  • Don't lock the route from the floor to the refuge area: it must be an accessible way out. BIS, SP 7:2026
  • Don't remove the sign that names the refuge floors above and below. BIS, SP 7:2026

What Flamekite could not confirm about refuge area rules

Five things a reader may expect here were not verified on 24 October 2026, so the page does not state them.

The clause numbers of the refuge area rule in NBC 2016 Part 4. BIS sells the 2016 text and Flamekite did not read it; the 2016 column above rests on BIS's own history of that revision and on Odisha's 2023 recommendation that applied it.

Maharashtra's own sizes in UDCPR 2020 and Mumbai's DCPR 2034, and Delhi's in its Unified Building Bye-Laws 2016. Delhi's Fire Service Rules 2010 list the refuge area as 1 of 20 minimum measures but leave the numbers to the bye-laws or NBC 2005.

Kerala's refuge numbers in KMBR 2019 and Telangana's in its building rules as amended by G.O.Ms.No.95 of 21 March 2026. Kerala's fire service names the refuge area on its high-rise inspection checklist.

Gujarat's regulation 15.27 says both every 18 m and immediately above 25 m. Both readings are shown; ask the Gujarat fire service which it applies to your plans.

NBCS 2026 itself binds no one. Only Assam had written NBCS 2026 into its fire law by 24 October 2026, and Uttar Pradesh's OSH Rules 2026 apply Part F to workplaces of 5 or more floors or 20 m.

Questions about Refuge area

What is a refuge area in a high-rise building?

A space inside the building, protected from fire and smoke, where people who cannot use the stairs wait for a short time during escape before being brought down by the fireman's lift. NBCS 2026 defines it in clause 2.57 of Part F.

At what height is a refuge area required?

Under NBCS 2026, in buildings over 24 m: the first at or just above 24 m and then every 15 m or so. Malls start at 18 m. Your state may differ: Gujarat's regulations start just above 25 m.

How do you calculate refuge area size?

Count the occupants of the refuge floor and the floor above, allow 0.3 m² each, and add 0.9 m² of wheelchair space for every 200 people. If the result is under 15 m², provide 15 m². Rajasthan asks for at least 10% of the floor's gross built-up area.

Is a refuge area counted in FAR?

Only the part beyond the requirement, under NBCS 2026: refuge area provided in excess counts towards FAR. Whether the required part is free of FAR is set by your state's development rules.

Do apartments with balconies need a refuge area?

Not under NBCS 2026, Gujarat or Rajasthan, if every flat has a balcony (or a terrace, in Rajasthan). Tripura's 2026 rules still require one at 60 m and every 30 m above that.

Is a refuge area mandatory now that NBC 2016 is withdrawn?

It depends on your state. NBCS 2026 is voluntary, but state rules such as Tripura's Fire Safety Rules 2026 and Rajasthan's Model Building Regulations 2025 make it compulsory, and fire services check it before granting a NOC.

Keep reading

Words on this page, explained

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  2. Gazette of India (Bureau of Indian Standards notification): Gazette of India Extraordinary, Part III Sec 4, No. 299, 30 April 2026: SP 7:2026 established, SP 7:2016 withdrawn (Ref HQ-PUB013/1/2020-PUB-BIS (1529)) (opens in a new tab)checked 25 October 2026
  3. Delhi Fire Service: Delhi Fire Service Rules, 2010 (consolidated copy) (opens in a new tab)checked 25 October 2026
  4. Local Self Government Department, Government of Kerala (Kerala Gazette copies): Kerala Municipality Building Rules, 2019 (G.O.(P) No.77/2019/LSGD, S.R.O. No.828/2019, 8 November 2019) with the Amendment Rules, 2020 (G.O.(P) No.57/2020/LSGD, S.R.O. No.639/2020): rule 5(4) items 12 and 13, rules 28, 29, 35, 80 and 81, Appendix L (opens in a new tab)checked 25 October 2026
  5. Kerala Fire and Rescue Services: KFRS procedures: mandatory documents for site NOC, completion NOC and renewal (opens in a new tab)checked 24 October 2026
  6. Assam Gazette Extraordinary No. 427, 14 August 2026 (PRS copy of the gazette): The Assam Jan Vishwas (Amendment of Provisions) Act, 2026 (Assam Act No. XIII of 2026): Schedule item 4 amending sections 2, 20, 21 and 31 of the 2025 Act (opens in a new tab)checked 25 October 2026
Show all 18 sourcesShow fewer
  1. Uttar Pradesh Gazette Extraordinary, 27 August 2026, English translation (copy hosted by TeamLease RegTech): Uttar Pradesh Occupational Safety, Health and Working Conditions Rules, 2026, Notification No. 962/XXXVI-03-2026-1903305: rules 12, 16, 43, 45, 46, 47 and 127 (opens in a new tab)checked 25 October 2026
  2. Directorate of Fire and Emergency Services, Tripura: Tripura Fire Safety Rules, 2026 (Tripura Gazette, 2 June 2026) (opens in a new tab)checked 24 October 2026
  3. Directorate of Fire and Emergency Services, Goa: BRAP 2024 item 284: fire NOC fees and timeline (opens in a new tab)checked 25 October 2026
  4. Gujarat Fire Safety Compliance Portal (GujFireSafety CoP): Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (fees in Annexure 8) (opens in a new tab)checked 25 October 2026
  5. Urban Development Department, Rajasthan: Model Rajasthan Building Regulations, 2025, order No. P-11(5)/UDH/Bhavan Viniyam-2025/2025 (listed 12 May 2025): Regs 2.36, 2.75, 2.77, 4.6.2, 5.4, 11.2, 14.5 and Schedules 2 and 3 (opens in a new tab)checked 25 October 2026
  6. Odisha Fire and Emergency Service, Form-II of 1 April 2023 (digitally signed copy filed with a RERA project, hosted by Magicbricks): Fire Safety Recommendation under rule 12(5) for a 21-floor residential project at Nuahat, Cuttack, issued by the I/c Chief Fire Officer (SAG), Fire Prevention Wing (opens in a new tab)checked 24 October 2026
  7. Gazette of Meghalaya No. 12, Part IIA, 25 March 2021 (copy hosted by the Urban Affairs Department): Meghalaya Building Bye-Laws, 2021 (No. UAU.73/2016/Pt/402 of 9 March 2021): A2.30 high-rise, A2.59 special buildings, A4.1.3, A10 occupancy and fire clearance, C11 (opens in a new tab)checked 25 October 2026
  8. Maharashtra Fire and Emergency Services: Guidelines for Form B, Annexure A: to be followed by licensed agencies issuing Form B under section 3(3) and rule 4(2) (circular of 7 July 2026) (opens in a new tab)checked 25 October 2026
  9. Housing and Urban Development Department, J&K (copy hosted by NITI for States): Jammu and Kashmir Unified Building Byelaws 2021 (February 2021): use classes, high-rise and tall buildings, fire access and Fire Consultant on Record (opens in a new tab)checked 25 October 2026
  10. Maharashtra Fire Services: Circulars (read through the entry of 16 October 2026; includes circular MFS/2017/60 of 17 May 2017 on NBC 2016 Part 4) (opens in a new tab)checked 25 October 2026
  11. Home Department, Government of Odisha: Notification No. 28550/CD of 28 August 2020: one-time relaxation scheme for buildings that functioned before the 2017 Rules (opens in a new tab)checked 25 October 2026
  12. The Times of India: Govt replaces building code with a new standard, retains fire safety provisions as 'advisory' (30 April 2026) (opens in a new tab)News report · checked 24 October 2026