IS 15105:2021: the sprinkler code, with its hazard classes, head spacing, water storage and maintenance values

Updated By Flamekite Editorial DeskFacts checked against official sources on

Quick answer

IS 15105:2021 is the Indian code of practice for the design, installation and maintenance of fixed automatic sprinkler fire extinguishing systems. It is the first revision, published in July 2021 by the Fire Fighting Sectional Committee, CED 22, and it replaced IS 15105:2002, which BIS withdrew on 14 March 2022.

The values most searched: design density of 2.25, 5 and 12.2 lpm per m2 over 84, 360 and 260 m2 for light, ordinary and high hazard (cl. 8.1); a standard head covering at most 21, 12 and 9 m2 (cl. 9.17.1); and sprinkler water for at least 30, 60 and 120 minutes of pump running (Table 30). For most building types, the building code's own table sets water and pumps instead (cl. 1.6). No Quality Control Order makes the code or sprinkler heads compulsory to certify.

Design density, ordinary hazard
5 lpm/m2
Over 360 m2 area of operation; cl. 8.1.2
Design values
Standard head coverage, ordinary hazard
12 m2
At most 4.5 m between heads; cl. 9.17
Spacing
Ordinary hazard water storage
60 min
Or 150 m3, whichever is greater; Table 30
Water tank
Edition replaced
IS 15105:2002
Withdrawn 14 March 2022
Myths

IS 15105:2021 at a glance: 12 facts

IS 15105:2021 in 12 facts with their sources. Values were read from the standard's text on 26 October 2026; clause numbers are those of the 2021 edition.
WhatThe ruleSource
TitleDesign, Installation and Maintenance of Fixed Automatic Sprinkler Fire Extinguishing Systems, Code of PracticeBIS, IS 15105:2021
EditionFirst revision, July 2021; first published in 2002 with pre-calculated systems only. The revision keeps pre-calculated sizing for small systems, requires hydraulic calculation for high hazard, adds high-rise rules (Annex B, 45 m per installation), wider storage classes and ESFR and large drop heads (foreword)BIS, IS 15105:2021
CommitteeFire Fighting Sectional Committee, CED 22, of the Civil Engineering DivisionBIS, IS 15105:2021
ReplacesIS 15105:2002, withdrawn on 14 March 2022BIS standards database
ScopeDesign, installation and maintenance of sprinkler systems in buildings including industrial and storage, and any later addition or repair (cl. 1.1, 1.3)BIS, IS 15105:2021
Not coveredWater spray and deluge systems (IS 15325, IS 15519), and ships, aircraft, vehicles and mines (cl. 1.4, 1.5)BIS, IS 15105:2021
Building groups A to FWater and pumping capacity come from Table 7 of SP 7 (Part 4); the code's own pump and water clauses apply only to occupancies that table does not cover (cl. 1.6)BIS, IS 15105:2021
Hazard classesLight, ordinary (moderate), high, and storage (cl. 5.1)BIS, IS 15105:2021
Maximum pressure7 bar in the installation (cl. 10.3.3)BIS, IS 15105:2021
Pre-calculated pipe sizingAllowed only for light and ordinary hazard with 5,000 m2 or less of floor area, and not for gridded or looped layouts (cl. 10.3.1)BIS, IS 15105:2021
Compulsory BIS markNone for the code; sprinkler heads (IS 9972) had only a draft order on 24 October 2026BIS compulsory list
Where it is namedFire rules and NOC conditions that cite it, such as Maharashtra's Note 21(a), use the code for sprinkler design; the code itself binds only through such a rule or contractBIS standards database

IS 15105:2021 and the standards beside it: who covers what

IS 15105:2021 is the sprinkler system code; the standards it points to do other jobs. Part years as listed on /is-codes.
OptionTypeWhat it coversIts role next to IS 15105:2021Source
IS 15105:2021Code of practiceDesign, installation and maintenance of the sprinkler systemThe sprinkler design and upkeep codeBIS, IS 15105:2021
SP 7 (Part 4)Building code partFire and life safety; Table 7 sets water and pump capacity for building groups A to FPrevails for those groups over cl. 12 and 13 of IS 15105 (cl. 1.6)BIS, IS 15105:2021
IS 9972:2023Product standardSprinkler headsThe heads that IS 15105 places; no compulsory mark yetBIS standards database
IS 15325 and IS 15519Design standardsWater spray and deluge systemsNot covered by IS 15105; high-hazard areas may need them (cl. 1.4, 5.4.2)BIS, IS 15105:2021
IS 13039:2014Design standardExternal hydrant systemsWhere a hydrant system backs the sprinklers, its reservoir rules apply to combined tanks (cl. 13.1, 13.3)BIS, IS 15105:2021
IS 2189:2026Code of practiceDetection and alarmDetection is no substitute for sprinklers; see /is-codes/is-2189BIS, IS 15105:2021

How to check a sprinkler system against IS 15105:2021: 6 steps

  1. Name the edition

    Write IS 15105:2021 on the drawing, AMC and audit report; the 2002 edition was withdrawn on 14 March 2022.

  2. Fix the hazard class

    Check each area against cl. 5 and the 126 m2 light hazard compartment limit, and note any storage above the heights in Table 6.

  3. Check design values

    Match density and area of operation to cl. 8.1, and head area and spacing to cl. 9.17 (21, 12 or 9 m2; 4.5 or 3.75 m).

  4. Check the water

    Confirm tank and pumps against SP 7 (Part 4) Table 7 first, otherwise Tables 29 and 30, with the 20 percent pump margin (cl. 12.1).

  5. Check pipes and pressure

    Pipe sizing method per cl. 10.3, maximum pressure 7 bar, velocity at most 6 and 10 m/s.

  6. Check records

    Daily pump runs, weekly gauge log, 6-monthly head inspection and discharge test, yearly flushing, and 2-yearly tank cleaning (cl. 15.6).

IS 15105 design density and area of operation by hazard

Clause 8.1 sets the minimum water density and the largest area assumed to operate at once: 2.25 lpm/m2 over 84 m2 for light hazard, 5 over 360 m2 for ordinary and 12.2 over 260 m2 for high.

The density is never reduced because a room is smaller than the design area (cl. 8.1.1 to 8.1.3). Storage hazards are driven by the head chosen and Annex C, with densities normally in the range of 25 to 50 lpm/m2 (cl. 8.1.4).

Hotels and homes divided into rooms use the room plus its communicating corridor as the design area (cl. 8.1.5, 8.8). Special heads change the area: extended coverage heads use the hazard area or the area of five heads, whichever is greater; ESFR heads use 12 heads, 4 on each of adjoining branch lines; large drop heads use a rectangle at least 1.2 times the square root of the operating area long (cl. 8.2).

Goods may be kept in ordinary hazard areas at the same density only in blocks of at most 50 m2 with 2.4 m clear around, and below 4.0, 3.0, 2.1 and 1.25 m for commodity categories I to IV (cl. 8.1.2, Table 6). Otherwise the whole occupancy is treated as high hazard.

Design density and area of operation in IS 15105:2021, clause 8.1
WhatThe ruleSource
Light hazard2.25 lpm/m2 over at most 84 m2 (cl. 8.1.1)BIS, IS 15105:2021
Ordinary hazard5 lpm/m2 over at most 360 m2 (cl. 8.1.2)BIS, IS 15105:2021
High hazard12.2 lpm/m2 over at most 260 m2 (cl. 8.1.3)BIS, IS 15105:2021
Storage hazardSet by head type and Annex C; normally 25 to 50 lpm/m2 (cl. 8.1.4)BIS, IS 15105:2021

Sprinkler spacing and coverage area as per IS 15105

For standard pendent and upright heads, one head covers at most 21 m2 in light hazard, 12 m2 in ordinary and 9 m2 in high, at no more than 4.5, 4.5 and 3.75 m apart (cl. 9.17).

ClauseLight hazardOrdinary hazardHigh hazard
Area per standard head, at most BIS, IS 15105:20219.17.121 m212 m29 m2
Spacing between heads, at most BIS, IS 15105:20219.17.24.5 m4.5 m3.75 m
Spacing between heads, at least BIS, IS 15105:20219.17.31.8 m1.8 m1.8 m
Distance to a wall, at most BIS, IS 15105:20219.17.4Half the spacing; 1.5 m cap for combustible or open sidesSameSame
Distance to a wall, at least BIS, IS 15105:20219.17.5100 mm100 mm100 mm
Sidewall head: area, combustible ceiling BIS, IS 15105:20219.18.111 m27.5 m2Not listed
Sidewall head: area, non-combustible ceiling BIS, IS 15105:20219.18.118 m29 m2Not listed
Sidewall head: spacing along the wall, at most BIS, IS 15105:20219.18.24.3 m3 mNot listed
Deflector below ceiling BIS, IS 15105:2021Table 875 to 450 mm non-combustible (300 preferred)75 to 300 mm combustible (150 preferred)Exposed rafters: 75 to 150 mm

These are values for standard heads only. Extended coverage, large drop, ESFR, extended sidewall and obstruction cases have their own clauses (cl. 9.19 to 9.24, Tables 9 to 16); read them in the standard. Area per head is the product of the two spacings or twice the wall distances (cl. 9.4).

Hazard classification as per IS 15105 and what it exempts

Clause 5 puts every occupancy in light, ordinary or high hazard, or storage; clause 6.2 lists the parts of a building where sprinklers are not provided.

  1. If Offices, hotels, hospitals, schools, libraries, museums, places of worship, prisons or homes

    Light hazard, excluding kitchens, stores and utilities, but only where no single compartment exceeds 126 m2 and compartments are separated by 30 minute walls and doors (cl. 5.2.2, 5.6.1). Otherwise design as ordinary hazard. BIS, IS 15105:2021

  2. If Retail shops, car parks inside buildings, airport terminals, metro stations, laboratories, motor garages, electronics, garments, bakeries and similar

    Ordinary hazard (cl. 5.3, 5.6.2). The list is not exhaustive; for an unlisted risk, write to the authority with full particulars before design (cl. 5.6). BIS, IS 15105:2021

  3. If Processes with a high fire load that can spread fast

    High hazard (cl. 5.4.1); some need water spray under IS 15325 instead (cl. 5.4.2). BIS, IS 15105:2021

  4. If Warehouses and stores above the heights allowed in ordinary hazard

    Storage hazard by commodity category, protected by Annex C densities (cl. 5.5, 8.1.4); ESFR heads reach storage up to 13.7 m (Table 1). BIS, IS 15105:2021

  5. If Stairs, spaces under stairs, lift wells, or toilets under 5 m2

    May be left without sprinklers if separated by walls and 120 minute fire doors (cl. 6.2.3). BIS, IS 15105:2021

  6. If A dry electrical room in a 120 minute enclosure with no storage

    Sprinklers not required if the five conditions of cl. 6.2.4 are all met; server rooms may use other extinguishing systems (cl. 6.2.3). BIS, IS 15105:2021

  7. If Salt baths, metal melt pans, frying ranges or grain silos

    No sprinklers, and no water pipes over them (cl. 6.2.2). BIS, IS 15105:2021

  8. If Mixed hazards in one system

    Size the water for each hazard and take the highest; a higher hazard confined to 40 m2 or less follows the dominant occupancy (cl. 13.2). BIS, IS 15105:2021

Sprinkler water tank capacity and pump duty in IS 15105

Table 30 sets exclusive sprinkler storage at 30, 60 or 120 minutes of pump running by hazard, with floors of 60 and 150 m3, and Table 29 gives the pump sizes; both apply only where SP 7 (Part 4) Table 7 is silent.

  • 30 min

    light hazard storage at pump capacity, or 60 m3 if greater (Table 30) BIS, IS 15105:2021

  • 60 min

    ordinary hazard storage at aggregate pump capacity, or 150 m3 if greater (Table 30) BIS, IS 15105:2021

  • 120 min

    high hazard and storage at aggregate pump capacity (Table 30) BIS, IS 15105:2021

  • 2,850 lpm

    ordinary hazard pump at 7.0 bar, the larger listed size (Table 29) BIS, IS 15105:2021

  • 4,550 lpm

    largest listed pump for high hazard and storage (Table 29) BIS, IS 15105:2021

  • 20 percent

    margin a pump must exceed the calculated flow and pressure (cl. 12.1(e)) BIS, IS 15105:2021

  • 225 m3

    reservoir size from which two interconnected compartments are needed (cl. 13.3(e)) BIS, IS 15105:2021

  • 2 years

    longest gap between reservoir cleanings (cl. 13.3(g)) BIS, IS 15105:2021

Sprinkler head selection under IS 15105: K-factor and temperature

Table 1 matches head K-factor to hazard and building height, and clause 7.7 sets the rating at least 30 degrees C above the hottest expected ceiling.

  • K 57 or 80, up to 9 m

    Light hazard heads

    K 57 or 80 up to 9 m of building height and K 115 above 9 m and within 15 m, pendent, upright or sidewall, quick or standard response (Table 1). BIS, IS 15105:2021

  • K 80 or 115, up to 9 m

    Ordinary hazard heads

    K 80 or 115 up to 9 m, K 115 for 9 to 15 m, pendent or upright (Table 1). BIS, IS 15105:2021

  • K 115 or 160, up to 9 m

    High hazard heads

    K 115 or 160 up to 9 m, K 160 and above for 9 to 15 m (Table 1). BIS, IS 15105:2021

  • ESFR, K 200 to 400

    High storage heads

    ESFR heads of K 200 to 400 up to 13.7 m, and in-rack heads of K 80 or more (Table 1). Orifices are 10, 15, 20 or 25 mm (cl. 7.4). BIS, IS 15105:2021

  • 30 degrees C margin

    Temperature rating

    At least 30 C above the highest expected ceiling temperature (cl. 7.7.1); 141 C roof heads over high-piled storage (cl. 7.7.2); heads kept 750 to 2,000 mm from hot sources. BIS, IS 15105:2021

  • 5 to 50 of each type

    Spare heads

    Light 5, ordinary 15, high 30 near a state capital (within 200 km), and 15, 25 or 50 elsewhere, kept at or below 38 C with a wrench (cl. 7.10, Table 5). BIS, IS 15105:2021

Sprinkler pipe size and pressure rules in IS 15105

Clause 10 says when pipe may be sized from tables and when a full hydraulic calculation is required, and caps pressure at 7 bar and water speed at 6 or 10 m/s.

Do

  • Use a fully calculated system for high hazard, storage, any ESFR, large drop, extended coverage or intermediate heads, and any light or ordinary occupancy above 5,000 m2 of floor area (cl. 10.3.2). BIS, IS 15105:2021
  • Keep arm and drop pipes feeding heads to 32 mm bore or less where the feeding pipe is over 65 mm (cl. 10.1(c)); use 32 mm minimum for rooms in offices and hotels (cl. 10.1(d)). BIS, IS 15105:2021
  • Keep water velocity to 6 m/s through valves and flow devices and 10 m/s elsewhere (cl. 10.5). BIS, IS 15105:2021
  • Keep the maximum installation pressure at or below 7 bar (cl. 10.3.3). BIS, IS 15105:2021

Don’t

  • Pre-calculate a gridded or looped layout: tables are only for non-looped light and ordinary systems up to 5,000 m2 (cl. 10.3.1). BIS, IS 15105:2021
  • Connect heads directly to distribution pipes, except light hazard on pipe up to 50 mm (cl. 10.1(b)). BIS, IS 15105:2021
  • Assume pre-calculated pressure is the same everywhere: Table 22 gives 225 lpm at 2.2 bar for light and 1,800 lpm at 2.02 bar for ordinary, both plus static losses, at the installation valve. BIS, IS 15105:2021

Sprinkler system maintenance as per IS 15105

Clause 15.6 and Table 31 run from a daily pump run to a two-yearly painting; heads are inspected and discharge-tested at least every 6 months and the system is flushed at least yearly.

  1. Daily (cl. 15.6.3, 15.6.4)

    Run every fire pump for at least 5 minutes and log priming tank level, pressures and speed; read the gauges above and below the installation valve at the start of the first shift. BIS, IS 15105:2021

  2. Weekly (cl. 15.6.1, 15.6.2)

    Visual check of the system, gauge readings recorded, reservoir level recorded and kept full, pump glands and starter contacts checked, and the alarm gong timed after the drain valve is opened. BIS, IS 15105:2021

  3. Every 3 months (cl. 15.6.4)

    The alarm gong assembly is checked thoroughly; Table 31 adds quarterly sprinkler cleaning, flow test and a performance check. BIS, IS 15105:2021

  4. Every 6 months (cl. 15.6.4)

    Every head is inspected for position, loading and corrosion, a discharge test is made, and pump motor insulation resistance is measured. BIS, IS 15105:2021

  5. Yearly (cl. 15.6.4)

    Pipework is examined, installation valves are serviced and tested by qualified people, and the system is flushed. BIS, IS 15105:2021

  6. Twice a year (cl. 15.6.4)

    Manual checking devices are operated at least twice annually. BIS, IS 15105:2021

  7. Every 2 years (cl. 13.3, 15.6.4)

    Reservoir cleaning at least this often and painting of all sprinkler equipment. BIS, IS 15105:2021

  8. Always (cl. 15.2 to 15.5)

    A shutdown needs planning, notice to the authority and extra fire precautions; reopen every closed valve and replace operated heads after a fire. BIS, IS 15105:2021

IS 15105:2021 acceptance tests before a system goes live

Clause 14 puts a 120 minute pressure test at 150 percent of working pressure, flushing, a flow test and a diesel pump start sequence between installation and use.

  1. Documents

    The installer checks working drawings against what was built and lists deviations for the authority's approval (cl. 14.1). BIS, IS 15105:2021

  2. Pressure test

    Pipework from the pump house to the installation valve and the head pipework must hold 150 percent of maximum working pressure for 120 minutes (cl. 14.2(a)). Pre-action systems also take a 3 bar air leak test for 24 hours (cl. 14.2(c)). BIS, IS 15105:2021

  3. Flushing and balance

    Flush all piping at the maximum flow available; where a building and its connected buildings exceed 500 heads, check hydraulic balance at the best and worst locations (cl. 14.4). BIS, IS 15105:2021

  4. Flow test

    Prove by a full-flow test that the water supply matches the accepted drawings, by operating a bulb or the pump-room test line, and record the results (cl. 14.5). BIS, IS 15105:2021

  5. Pump start

    Diesel pump: isolate fuel and run 6 cycles of at least 15 s cranking and at most 15 s rest; the fail-to-start alarm sounds; restore fuel and start manually (cl. 14.7). BIS, IS 15105:2021

  6. Alarms

    The gong must sound within 45 to 60 seconds of flow (cl. 11.10(b)) and be 85 dB above background noise (cl. 14.8(b)); signals must reach the panel (cl. 14.9). BIS, IS 15105:2021

IS 15105 vs NFPA 13: how the two sprinkler codes compare

Both codes classify hazard, cap area per head and the spacing; the IS 15105 limits of 21, 12 and 9 m2 sit close to the US figures of about 21, 12 and 9 m2 reported for NFPA 13, but Flamekite has not read NFPA 13.

Hazard classes
IS 15105 has four (light, ordinary, high, storage; cl. 5.1). NFPA 13 uses light, ordinary and extra hazard with sub-groups; the exact mapping to IS 15105's high hazard is not confirmed. NFPA 13 summarynews report
Area per head
IS 15105: 21 m2 light, 12 m2 ordinary, 9 m2 high (cl. 9.17.1). A secondary summary of NFPA 13 gives 225, 130 and 100 ft2, about 21, 12 and 9 m2, with 15 ft (about 4.6 m) maximum spacing for light and ordinary. NFPA 13 summarynews report
Design density
IS 15105 fixes 2.25, 5 and 12.2 lpm/m2 (cl. 8.1). NFPA 13 sets density and area from curves; its values were not verified here, so no conversion is offered. BIS, IS 15105:2021
Which one applies in India
IS 15105 is the Indian standard named in Indian fire rules; NFPA 13 appears in insurer and multinational specifications. A tender must say which one governs. BIS, IS 15105:2021

Myths about IS 15105 and sprinkler design

Five common claims about IS 15105 that the 2021 text does not support.

  • You may have read

    IS 15105:2002 is still the current sprinkler code.

    Myth

    What the sources say

    BIS withdrew the 2002 edition on 14 March 2022; IS 15105:2021 is current, though some state lists still show the old edition. BIS standards database

  • You may have read

    Sprinkler tanks must always follow IS 15105 Table 30.

    Myth

    What the sources say

    For building groups A to F and some of G and H, Table 7 of SP 7 (Part 4) governs water and pumps; Table 30 covers only the rest (cl. 1.6, 13.1(a)). BIS, IS 15105:2021

  • You may have read

    Every head in the building opens when one operates.

    Myth

    What the sources say

    Heads open one by one as each is heated; the design area is the largest area assumed to operate, such as 360 m2 for ordinary hazard (foreword, cl. 8.1.2). BIS, IS 15105:2021

  • You may have read

    Sprinklers make hydrants, extinguishers and alarms unnecessary.

    Myth

    What the sources say

    The foreword says sprinklers do not remove the need for other means: egress, alarms, hose reels, hydrants and extinguishers all need consideration. BIS, IS 15105:2021

  • You may have read

    One partial sprinkler zone is fine anywhere.

    Myth

    What the sources say

    The whole block must be sprinklered unless the part is an allowed exception or is cut off by fire walls and doors (cl. 9.1(a), 6.2). BIS, IS 15105:2021

IS 15105:2021 traps: where the code differs from itself

Three places where the 2021 text gives two values, so the stricter reading matters until the fire office says otherwise.

  • If Flushing is at least yearly in cl. 15.6.4(g) but Table 31 lists main piping every 2 years and the sprinkler pipe network every 6 months.

    Follow the yearly clause as a floor, and ask your AMC contractor which table row the contract uses. BIS, IS 15105:2021

  • If Discharge and flow tests are 6-monthly in cl. 15.6.4(c) but Table 31 lists the sprinkler flow test and cleaning as quarterly.

    Plan for quarterly checks on a high-value site and treat 6 months as the minimum. BIS, IS 15105:2021

  • If Ordinary hazard design flow is 1,800 lpm at 2.02 bar in Table 22, but cl. 10.4.6 asks for the pressure loss at 1,000 lpm.

    Have the designer state which rate each calculation sheet uses before the layout is submitted. BIS, IS 15105:2021

IS 15105:2021 applied: an office floor, a store, a tank and a pump

Flamekite’s working from the official rules; no government publishes this figure.

Four readings of the clauses by Flamekite's own arithmetic. They are not design drawings, and the ones on water assume Table 7 of SP 7 (Part 4) does not already cover the building.

  1. Case 1

    Light hazard office

    1,000 m2 floor, standard pendent heads, no compartment over 126 m2

    What applies At 21 m2 a head, at least 48 heads (1,000 / 21, rounded up), and 4.5 m spacing gives 20.25 m2, so about 49 to 60 in practice. Design flow 2.25 x 84 = 189 lpm (cl. 8.1.1, 9.17). Offices follow /fire-noc/offices for the NOC side. BIS, IS 15105:2021

  2. Case 2

    Ordinary hazard retail or car park

    2,400 m2 at 12 m2 a head

    What applies At least 200 heads. Design flow 5 x 360 = 1,800 lpm (cl. 8.1.2), which matches the 1,800 lpm in Table 22 for a pre-calculated system. See /fire-noc/malls for the NOC. BIS, IS 15105:2021

  3. Case 3

    Ordinary hazard tank

    Pump of 2,850 lpm, hazard not in SP 7 Table 7

    What applies 60 minutes gives 171 m3, which exceeds the 150 m3 floor, so 171 m3 (Table 30); a 2,280 lpm pump gives 137 m3, so the 150 m3 floor applies. Add 30 m3 if no hydrant system backs it (cl. 13.1(f)). BIS, IS 15105:2021

  4. Case 4

    High hazard store with a pump

    Storage hazard with a 4,550 lpm pump

    What applies 120 minutes gives 546 m3 of storage (Table 30), well above 225 m3, so two interconnected compartments with a common sump (cl. 13.3(e)). Storage density and head type are from Annex C. See /fire-noc/warehouses. BIS, IS 15105:2021

IS 15105:2021 details this page could not confirm

Gaps are listed rather than guessed.

  • NFPA 13 values: the NFPA text was not read, only a secondary summary, so no density or area comparison is given. NFPA 13 summarynews report
  • Amendments to IS 15105:2021: none appear in the text read, but the BIS record of amendments was not checked. BIS, IS 15105:2021
  • Which sprinkler thresholds apply to which building: they sit in SP 7 (Part 4), which this page did not read for the table; see /national-building-code-2026. BIS, SP 7:2026
  • Which state fire rules name the 2021 edition: only Maharashtra's Note 21(a) is known, and others may cite the 2002 edition. BIS standards database
  • Obstruction tables (9 to 16), pipe sizing tables (17 to 28), annexes and figures are not reproduced; read them in the standard, free after registration with BIS. BIS, IS 15105:2021

Questions about IS 15105:2021

What is IS 15105?

IS 15105 is the Indian Standard code of practice for the design, installation and maintenance of fixed automatic sprinkler fire extinguishing systems. The current edition is IS 15105:2021, the first revision, from the Fire Fighting Sectional Committee, CED 22.

What is the latest version of IS 15105?

IS 15105:2021, published in July 2021. It replaced IS 15105:2002, which BIS withdrew on 14 March 2022.

What is the sprinkler spacing as per IS 15105?

For standard pendent and upright heads the maximum spacing is 4.5 m for light and ordinary hazard and 3.75 m for high hazard, with a minimum of 1.8 m (cl. 9.17.2, 9.17.3).

What is the sprinkler head coverage area as per IS 15105?

At most 21 m2 for light hazard, 12 m2 for ordinary and 9 m2 for high hazard for standard pendent and upright heads (cl. 9.17.1). Sidewall heads cover 7.5 to 18 m2 depending on hazard and ceiling (cl. 9.18.1).

What are the hazard classes in IS 15105?

Light, ordinary (moderate), high and storage hazard (cl. 5.1). Light hazard compartments are limited to 126 m2 and offices, hotels and homes are listed as light hazard (cl. 5.2.2, 5.6.1).

What is the design density in IS 15105?

2.25 lpm/m2 over 84 m2 for light hazard, 5 lpm/m2 over 360 m2 for ordinary and 12.2 lpm/m2 over 260 m2 for high hazard (cl. 8.1).

What is the sprinkler water tank capacity as per IS 15105?

Table 30 gives 30 minutes of pump capacity or 60 m3 for light hazard, 60 minutes or 150 m3 for ordinary and 120 minutes for high hazard and storage, for occupancies not covered by Table 7 of SP 7 (Part 4).

What pipe size does IS 15105 allow?

The code sets a method, not one size: tables for small light and ordinary systems up to 5,000 m2 and hydraulic calculation for the rest, with arm pipes of 32 mm or less in ordinary and high hazard (cl. 10.1, 10.3).

How often is a sprinkler system maintained as per IS 15105?

Pumps are run daily for 5 minutes, gauges logged weekly, every head inspected and discharge-tested at least every 6 months, and the system flushed at least yearly (cl. 15.6).

Is IS 15105 mandatory?

Not by itself. No Quality Control Order covers the code, and the sprinkler head order was only a draft on 24 October 2026. It binds when a rule, NOC condition or contract names it.

Keep reading

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards: IS 15105:2021, Design, Installation and Maintenance of Fixed Automatic Sprinkler Fire Extinguishing Systems, Code of Practice (first revision), July 2021; free download after registration; clause and table numbers cited on the page (opens in a new tab)checked 26 October 2026
  2. Bureau of Indian Standards, Know Your Standards database: Status records read 25 October 2026 for IS 2189, IS 2190, IS 15683, IS 16018, IS 3844, IS 13039, IS 15105, IS 15301, IS 9668, IS 12349, IS 3614, IS 2175 and IS 11360 (current or withdrawn, with dates) (opens in a new tab)checked 25 October 2026
  3. Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  4. Bureau of Indian Standards: Products under compulsory certification, Scheme-I list (orders up to S.O. 5480(E) of 6 October 2026), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  5. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  6. Callout (code summary site): NFPA 13 2022 section 8.5.1, sprinkler spacing and coverage: a secondary summary, not the NFPA text (opens in a new tab)News report · checked 26 October 2026