Skip to content
Flamekite
ContactFree fire NOC check

IS codes 18 min read

IS 2189:2026: the fire detection and alarm code, with its detector spacing, call point and maintenance values

Updated By Flamekite Editorial DeskFacts checked against official sources on

Quick answer

IS 2189:2026 is the Indian code of practice for choosing, installing and maintaining automatic fire detection and alarm systems. It is the fifth revision, published in March 2026 by the Fire Fighting Sectional Committee, CED 22, and it replaced IS 2189:2008, which BIS withdrew on 17 September 2026.

The values most searched are in clauses 6.3 and 6.4: a smoke detector at 7.5 m and a heat detector at 5.3 m on a flat ceiling up to 7 m and 5 m high, manual call points 1.4 m above the floor and no more than 30 m of travel from anyone, and detector cleaning at least every 3 months (cl. 7.5). No Quality Control Order makes the code compulsory, so it binds only through a rule, NOC condition or contract that names it.

Smoke detector spacing, flat ceiling
7.5 m
Heat detector 5.3 m; cl. 6.3.2.1
Spacing
Manual call point height
1.4 m
Travel to a call point at most 30 m; cl. 6.4
Call points
Detector cleaning, at most every
3 months
Smoke sensitivity tested twice a year; cl. 7.5
Maintenance
Edition replaced
IS 2189:2008
Withdrawn 17 September 2026
Editions

IS 2189:2026 at a glance: 12 facts

IS 2189:2026 in 12 facts with their sources. Values were read from the standard's text on 26 October 2026; clause numbers are those of the 2026 edition.
WhatThe ruleSource
TitleSelection, Installation and Maintenance of Automatic Fire Detection and Alarm System, Code of PracticeBIS record
EditionFifth revision, March 2026; first published 1962, revised 1976, 1988, 1999 and 2008BIS, IS 2189:2026
CommitteeFire Fighting Sectional Committee, CED 22, of the Civil Engineering DivisionBIS record
ReplacesIS 2189:2008, withdrawn on 17 September 2026 after 6 months alongside the 2026 editionBIS standards database
ScopePlanning, design, selection, installation and maintenance, from a few call points to addressable panels, including industry (cl. 1.1); it sets a minimum level of protection (cl. 1.2)BIS, IS 2189:2026
Not coveredThe ancillary services a detection signal triggers, such as sprinklers or smoke control (cl. 1.1); detection is not a substitute for automatic extinguishing (foreword)BIS, IS 2189:2026
Zone sizeAt most 2,000 m2 conventional and 3,000 m2 addressable; search distance at most 30 m (cl. 4.4.2)BIS, IS 2189:2026
PanelIn the entrance lobby, in plain view, never in a small lockable room or shaft (cl. 4.6)BIS, IS 2189:2026
WirelessAllowed as fully wireless or hybrid, on licence-exempt bands such as 865 to 867 MHz and 2.4 GHz (cl. 4.9)BIS, IS 2189:2026
Product standardsDetectors, call points, sounders and power supplies follow the IS/ISO 7240 parts, such as Part 11 for call points and Part 3 for audible alarmsBIS, IS 2189:2026
Compulsory BIS markNone: no Quality Control Order for detection or alarm products was on BIS's list on 24 October 2026BIS compulsory list
Where it is namedMaharashtra's October 2026 circular on wireless detection refers to IS 2189:2026, and its July 2026 Form B guidelines still named the 2008 editionMFS circular 1420

IS 2189:2026 and the standards beside it: who covers what

IS 2189:2026 is the system code of practice; the product and building standards it points to do other jobs. Part years as listed on /is-codes.
OptionTypeWhat it coversIts role next to IS 2189:2026Source
IS 2189:2026Code of practiceSelection, siting, installation, testing and maintenance of the whole detection and alarm systemThe design and upkeep codeBIS, IS 2189:2026
IS/ISO 7240 Part 5:2018 and Part 7:2023Product standardsPoint-type heat detectors; point-type smoke detectorsProduct requirements for the detectors that IS 2189 placesBIS, SP 7:2026
IS/ISO 7240 Part 11:2011Product standardManual call pointsRequired by cl. 6.4(a) for every call pointBIS, SP 7:2026
IS/ISO 7240 Part 3 and Part 23Product standardsAudible alarm devices; visual alarm devicesRequired by cl. 4.5.1 and cl. 4.5.6 for sounders and beaconsBIS, IS 2189:2026
IS 15908:2021Product standardControl and indicating equipment, the alarm panelPanel product standard; the 2011 edition was withdrawn on 14 March 2022BIS standards database
SP 7 (Part 4)Building code partFire and life safety part of the National Building CodeCl. 4.7 sends the fire command centre to itBIS, IS 2189:2026
IS 12456Application standardFire protection of electronic data processing equipment in air-conditioned areas, as named in cl. 6.5Prevails over IS 2189:2026 where the two differBIS, IS 2189:2026
IS 11360:1985 and IS 2175:1988Withdrawn productsOld smoke and heat detector product standardsWithdrawn on 18 July 2025; detector products now follow IS/ISO 7240BIS standards database

How to check a fire alarm system against IS 2189:2026: 6 steps

  1. Name the edition

    Write IS 2189:2026 on the drawing, AMC and audit report; the 2008 edition was withdrawn on 17 September 2026.

  2. Check zones

    Confirm no zone exceeds 2,000 m2 (conventional) or 3,000 m2 (addressable) and no search distance exceeds 30 m (cl. 4.4.2).

  3. Check detector siting

    Measure ceiling height against the 7 m and 5 m limits, then check the 100 m2 and 50 m2 cross-check and the 500 mm and 1.5 m clearances (cl. 6.3).

  4. Check call points and sounders

    Call points at 1.4 m and within 30 m of travel; sound level at least 75 dB(A) at the bed head and never above 120 dB(A) (cl. 6.4, 4.5).

  5. Check the panel

    Panel in the entrance lobby, device numbers recorded, latest drawing on the wall of the command centre (cl. 4.6, 4.7, 6.1).

  6. Check records

    Log book, daily and quarterly checks, yearly tests, 3-month cleaning and any written impairment notices (cl. 7.4, 7.5).

Smoke and heat detector spacing in IS 2189:2026

On a flat ceiling the code lists 7.5 m for a smoke detector and 5.3 m for a heat detector, valid only up to 7 m and 5 m of ceiling height (cl. 6.3.2.1 and 6.3.3.1).

ClauseSmoke detectorHeat detector
Listed distance, flat ceiling BIS, IS 2189:20266.3.2.17.5 m5.3 m
Spacing valid up to a ceiling height of BIS, IS 2189:20266.3.3.17 m5 m
Spacing at the next height band BIS, IS 2189:20266.3.3.15 m for 7 m to 10 m3.5 m for 5 m to 10 m
Above 10 m BIS, IS 2189:20266.3.3.1Beam or aspirating detectors onlyHeat detectors prohibited; beam or flame detectors
Corridor narrower than 2 m BIS, IS 2189:20266.3.2.812 m apart8 m apart
Sensing element below the ceiling BIS, IS 2189:20266.3.2.125 mm to 600 mm25 mm to 150 mm
Cross-check on the finished layout BIS, IS 2189:20266.3.4At least 1 per 100 m2At least 1 per 50 m2
Pitched roof, apex over 600 mm BIS, IS 2189:20266.3.2.27.5 m to 8.5 m near the apexNot set separately

Heat-detector coverage is a design value, not a smoke-detector coverage in m2: the code frames spacing as a distance and adds a 0.7 factor for the furthest point (cl. 6.3.4(b)). Work the layout from the standard.

Manual call point height and distance in IS 2189:2026

Clause 6.4 puts manual call points 1.4 m above the floor and within 30 m of travel from every person, 45 m where they are also outside the building.

The call point must comply with IS/ISO 7240 Part 11 (cl. 6.4(a)). It sits where it is easy to reach, well lit and unobstructed, preferably near stair entries on each level, and may need a shorter travel distance where access is difficult or the risk is dangerous (cl. 6.4(c), (d), (g)).

Where a call point cannot be seen from the front, as in a long corridor, it is surface mounted or semi-recessed so that at least 15 mm of its side shows (cl. 6.4(e)). The enclosure is dust and moisture proof (cl. 6.4(f)).

A breakable glass element must be at least 30 cm2 and not thicker than 2 mm. Once it breaks, the alarm sounds on the floor and at the panel, an indicator lights, and the panel keeps the alarm even if the button is pressed again (cl. 6.4(h)).

Manual call point values in IS 2189:2026, clause 6.4
WhatThe ruleSource
Height above floor1.4 m (cl. 6.4(d))BIS, IS 2189:2026
Maximum travel to a call point30 m inside; 45 m where call points are also fitted outside (cl. 6.4(b))BIS, IS 2189:2026
Visible side profile if not seen from the frontAt least 15 mm (cl. 6.4(e))BIS, IS 2189:2026
Glass area and thicknessAt least 30 cm2 and at most 2 mm (cl. 6.4(h))BIS, IS 2189:2026
Annual test (Table 4)Operate every call point once a year; on this page the same test list is in the maintenance sectionBIS, IS 2189:2026

Fire alarm zone size and sounder levels in IS 2189:2026

Zones are capped by area and search distance, and sounders by decibel level, spacing and mounting height.

  • 2,000 m2

    largest single zone, conventional system (cl. 4.4.2(a)) BIS, IS 2189:2026

  • 3,000 m2

    largest single zone, addressable system (cl. 4.4.2(a)) BIS, IS 2189:2026

  • 30 m

    longest search distance inside a zone, in a straight line (cl. 4.4.2(d)) BIS, IS 2189:2026

  • 75 dB(A)

    minimum at the bed head with doors shut, and the basis for sounder spacing (cl. 4.5.2, 4.5.3) BIS, IS 2189:2026

  • 120 dB(A)

    ceiling for sound level in occupied areas (cl. 4.5.3) BIS, IS 2189:2026

  • 30 m

    largest hooter centre-to-centre distance (cl. 4.5.2) BIS, IS 2189:2026

  • 2,290 mm

    least height of a wall hooter above the finished floor (cl. 4.5.2) BIS, IS 2189:2026

  • 300 m2

    total building area below which one zone may cover more than one floor (cl. 4.4.2(b)) BIS, IS 2189:2026

Where IS 2189:2026 wants a detector: stairs, shafts, voids and beams

Clause 6.3.2.6 and 6.3.2.7 list the places beyond the open ceiling where a detector is needed, and the obstructions that change where it can sit.

  1. If An enclosed staircase

    A detector at the top of the stairway and on each main landing (cl. 6.3.2.6(a)). Stairwells, lift wells and shafts are each a separate zone (cl. 4.4.2(e)). BIS, IS 2189:2026

  2. If An open staircase, lift, escalator or hoist shaft

    A detector at each level within 1.5 m of the floor penetration; a detector in the lift machine room (cl. 6.3.2.6(b), (d)). BIS, IS 2189:2026

  3. If A false ceiling or floor void

    Voids over 800 mm are protected like a normal ceiling; voids under 800 mm need cover only if fire products can spread through them; concealed spaces under 5 m2 need none (cl. 6.3.2.6(j), (k)). Bathrooms and WCs need not be protected. BIS, IS 2189:2026

  4. If Cable tunnels, ducts, AHU rooms and distribution boards

    A detector in each (cl. 6.3.2.6(e)); every room or cabin also gets one at ceiling level and under a false ceiling (cl. 6.3.2.6(f)). BIS, IS 2189:2026

  5. If A structural beam or duct deeper than 250 mm

    No detector within 500 mm of it (cl. 6.3.2.7(a)); a beam deeper than 10 percent of the ceiling height makes each bay its own enclosure (cl. 6.3.2.7(d)). BIS, IS 2189:2026

  6. If A shallower obstruction, up to 250 mm deep

    Keep a detector at least twice the obstruction's depth away from it (cl. 6.3.2.7(c)). BIS, IS 2189:2026

  7. If An air supply inlet

    At least 1 m away under cl. 6.3.2.7(e), but 1.5 m under cl. 6.3.3.2(b); use the larger distance until your fire office says otherwise. BIS, IS 2189:2026

Fire alarm system maintenance as per IS 2189:2026

Clause 7.4 and Table 4 split upkeep between the user, who checks daily to quarterly, and a competent contractor, who tests yearly; detectors are cleaned at least every 3 months.

  1. Daily (cl. 7.4.3)

    The user checks that the panel shows normal, that yesterday's faults are logged and being fixed, and that the panel is not dead from a blown fuse, bad supply or someone switching it off. BIS, IS 2189:2026

  2. Weekly (cl. 7.4.4)

    A review of the week's events to confirm each was handled correctly and that the system still works with all its features. BIS, IS 2189:2026

  3. Every 3 months at most (cl. 7.5)

    Detectors are cleaned of dust and insects, following the maker's method and with sensitivity checks afterwards. BIS, IS 2189:2026

  4. Quarterly (cl. 7.4.5)

    The user reviews the log book, tests batteries and connections, operates a trigger device in each zone, tests the sounders and any remote link, and confirms a clear radius of at least 750 mm below every detector. BIS, IS 2189:2026

  5. Twice a year (Table 4)

    Smoke detector sensitivity test and flame and spark detector checks; manual call points and heat detectors fall due in the yearly round below. BIS, IS 2189:2026

  6. Yearly (Table 4)

    Functional test of every smoke detector in place, heat detectors by a heat source or as the maker directs, and every manual call point operated. BIS, IS 2189:2026

  7. Yearly, power (Table 4)

    Disconnect mains power and check the trouble signal; run the general alarm for at least 5 minutes, and voice systems for at least 15 minutes. BIS, IS 2189:2026

  8. On any impairment (cl. 7.4.6.2)

    If a deficiency is not fixed at the end of testing, the owner is told in writing within 24 hours. BIS, IS 2189:2026

IS 2189:2026 versus IS 2189:2008: what changed

IS 2189:2026 is the fifth revision and replaced the 2008 edition, which BIS withdrew on 17 September 2026.

  • Current

    IS 2189:2026

    Published March 2026 as the fifth revision. It contains clause 4.9 on wireless systems, clause 6.3.2.9 on positive alarm sequence, an IoT health monitoring option (cl. 7.1.2, 7.3.1) and a fire command centre clause (cl. 4.7). BIS, IS 2189:2026

  • Withdrawn 17 September 2026

    IS 2189:2008

    The fourth revision. Its foreword in the 2026 text lists the 2008 additions as terminology, a probe-type high-temperature bi-metal heat detector, optical smoke, spark and ember, UV and IR flame detectors, and figures for smoke detector arrangement and addressable systems. BIS standards database

  • Superseded

    Earlier editions

    First published in 1962 and revised in 1976, 1988 and 1999. The foreword names no 2006 edition, although some web pages label old values that way. BIS, IS 2189:2026

Positive alarm sequence under IS 2189:2026 clause 6.3.2.9

Positive alarm sequence lets trained staff investigate a first alarm for up to 180 seconds before general evacuation sounds, and only where the AHJ approves it.

  1. Where it may be used

    Occupancies with trained staff on site, such as hospitals, hotels, business buildings, campuses and industrial buildings (cl. 6.3.2.9.2). Not in high-risk industrial or hazardous storage areas, or buildings without trained supervisors. BIS, IS 2189:2026

  2. Stage 1: the first detector operates

    The alarm reaches the panel and a continuously attended point, and public evacuation alarms stay inhibited (cl. 6.3.2.9.3(a)). BIS, IS 2189:2026

  3. Stage 2: investigation, 180 seconds at most

    Trained staff check the cause; the AHJ may permit a longer period (cl. 6.3.2.9.3(b)). BIS, IS 2189:2026

  4. Stage 3: confirmation or timeout

    A second detector, or any manual call point, starts full evacuation at once; so does a timer that runs out without acknowledgement (cl. 6.3.2.9.3(c)). BIS, IS 2189:2026

  5. Fail-safe rules

    Any fault, power failure or control malfunction triggers full alarm, and the sequence never inhibits call points, waterflow switches, or the signal to the brigade or remote monitoring (cl. 6.3.2.9.5). BIS, IS 2189:2026

Wireless fire alarm systems under IS 2189:2026 clause 4.9

Clause 4.9 allows fully wireless or hybrid systems on licence-exempt bands, as long as supervision, fault monitoring and alarm integrity equal a wired system.

Do

  • Use licence-exempt bands permitted in India, such as 865 to 867 MHz, 868 MHz and 2.4 GHz, and equipment that meets WPC rules (cl. 4.9.6). BIS, IS 2189:2026
  • Keep components compatible with the IS/ISO 7240 requirements and make hybrid systems perform as a wired one does (cl. 4.9.2). BIS, IS 2189:2026
  • Verify radio reliability, power supply and battery life, interference immunity and supervision intervals, and hand the test papers to the AHJ on request (cl. 4.9.3, 4.9.5). BIS, IS 2189:2026
  • Consider wireless for heritage buildings, temporary structures, retrofits and large campuses where cabling is impractical (cl. 4.9.7). BIS, IS 2189:2026

Don’t

  • Assume a state accepts it everywhere: Maharashtra's circular 1420 of 16 October 2026 accepts wireless detectors under clause 4.9 but not in high-rise buildings. MFS circular 1420
  • Rely on the standard to cap frequency, power, device count or topology: the code takes a performance-based approach and sets no such limits (cl. 4.9.4). BIS, IS 2189:2026

Myths about IS 2189 and fire alarm detectors

Five common claims about IS 2189 that the 2026 text does not support.

  • You may have read

    IS 2189:2008 is still the current code.

    Myth

    What the sources say

    BIS withdrew the 2008 edition on 17 September 2026; IS 2189:2026 is the only edition, though Maharashtra's July 2026 guidelines still named the old one. BIS standards database

  • You may have read

    IS 2189 is compulsory because the BIS mark is.

    Myth

    What the sources say

    The code is a code of practice. No Quality Control Order covered detectors, panels or alarms on 24 October 2026; it binds only when a rule, NOC condition or contract names it. BIS compulsory list

  • You may have read

    A fire alarm replaces sprinklers.

    Myth

    What the sources say

    The foreword says automatic detection is no substitute for automatic sprinklers or other extinguishing systems. BIS, IS 2189:2026

  • You may have read

    A can of test spray proves a smoke detector is sensitive.

    Myth

    What the sources say

    Clause 7.2.7 asks for a calibrated sensitivity test, and a note says an unmeasured dose of aerosol cannot test sensitivity. A smoke-entry test is separate. BIS, IS 2189:2026

  • You may have read

    Heat detectors are fine for escape routes and offices.

    Myth

    What the sources say

    Clause 5.3.2.1 calls heat detectors unsuitable for life safety and air-conditioned premises; they suit kitchens, pantries and low-value closets. BIS, IS 2189:2026

IS 2189:2026 traps: values that differ between clauses

Four places where the 2026 text gives two values or an ambiguous one, so the safer reading matters.

  • If Air inlet distance is 1 m in cl. 6.3.2.7(e) and 1.5 m in cl. 6.3.3.2(b).

    Keep 1.5 m unless your fire office accepts 1 m in writing. BIS, IS 2189:2026

  • If Clause 6.3.2.1 mixes a listed distance of 7.5 m and 5.3 m with a circle-radius sentence that reads unclearly.

    Use 7.5 m and 5.3 m as the listed spacing and apply the 0.7 factor in cl. 6.3.4(b) to the furthest point; confirm with the consultant. BIS, IS 2189:2026

  • If High air movement shortens spacing: the factor falls from 1.00 below 7.5 air changes an hour to 0.50 at 30 changes for smoke detectors (cl. 6.3.3.2).

    Take the air-change rate from the HVAC design, and keep the detector count worked as if the air handlers were off. BIS, IS 2189:2026

  • If A contract or audit report quotes a 20 percent yearly sample or 5-year cycle 'as per IS 2189'.

    The 2026 Table 4 tests every smoke detector in place each year; a sampling rule is from state guidelines, not the code. Ask for the clause. BIS, IS 2189:2026

IS 2189 terms: zone, search distance, AHJ, FACIE and stratification

Six terms from the 2026 text that tenders and audit reports use.

Detection zone
A sub-division of the protected premises that raises one fire indication, capped at 2,000 m2 conventional and 3,000 m2 addressable (cl. 4.4.2). BIS, IS 2189:2026
Search distance
The straight-line distance a responder walks after entering a zone to find the fire by eye; 30 m at most (cl. 4.4.2(d)). BIS, IS 2189:2026
AHJ
The authority having jurisdiction, in practice your fire office; it approves the device count, zoning and cable routes and must permit later changes (cl. 7.1.3). BIS, IS 2189:2026
FACIE
Fire alarm control and indicating equipment, the panel that receives signals and runs the sequence (cl. 6.3.2.9.3). BIS, IS 2189:2026
Stratification
Smoke that stops below the ceiling; the level is found by measuring the vertical smoke gradient and extra detectors fitted below it if the site test shows need (cl. 6.2). BIS, IS 2189:2026
Positive alarm sequence
Delayed general evacuation of at most 180 seconds while trained staff investigate the first alarm (cl. 6.3.2.9). BIS, IS 2189:2026

IS 2189:2026 applied: a 1,000 m2 office, a ward, a data hall and a 12 m atrium

Flamekite’s working from the official rules; no government publishes this figure.

Four worked readings of the clauses. They are Flamekite's own arithmetic from the code's values, not design drawings.

  1. Case 1

    Open office floor

    1,000 m2 flat ceiling, 3 m high, one conventional zone

    What applies The 100 m2 cross-check (cl. 6.3.4) needs at least 10 smoke detectors, and each must meet the 7.5 m limit; the 2,000 m2 zone ceiling is not exceeded (cl. 4.4.2(a)). Offices follow /fire-noc/offices for the NOC side. BIS, IS 2189:2026

  2. Case 2

    Hospital ward with a trained night team

    Staffed ward corridor under 2 m wide

    What applies Corridor spacing may stretch to 12 m for smoke (cl. 6.3.2.8(a)); positive alarm sequence may be proposed, with AHJ approval (cl. 6.3.2.9.2), and an engineer must be on call 24 hours (cl. 7.3.2). BIS, IS 2189:2026

  3. Case 3

    Data hall with high-value equipment

    Electronic equipment in an air-conditioned room

    What applies Aspirating or multi-criteria detection is preferred (cl. 5.4.2) and IS 12456 prevails where it differs (cl. 6.5). BIS, IS 2189:2026

  4. Case 4

    Atrium 12 m high

    Ceiling above 10 m

    What applies Point smoke detectors fall outside the table (cl. 6.3.3.1): beam or aspirating detectors only, and heat detectors are prohibited. BIS, IS 2189:2026

IS 2189:2026 details this page could not confirm

Gaps are listed rather than guessed.

  • Which clauses are new in 2026: the 2026 foreword lists no changes, and the 2008 text was not compared, so the options section above says what the 2026 edition contains, not what it added.
  • Whether 7.5 m and 5.3 m are a spacing or a radius: clause 6.3.2.1 reads both ways, so no m2 coverage per detector is stated here. BIS, IS 2189:2026
  • The exact publication date of 17 March 2026 is carried from the BIS database record used on /is-codes; the BIS record page read for this page shows no date. BIS standards database
  • Which state fire rules name IS 2189:2026: only Maharashtra's October 2026 circular was found; others may cite the 2008 edition. Maharashtra Fire Services
  • Annexes, figures and the full Table 3 and Table 4 are not reproduced; read them in the standard, free after registration with BIS. BIS, IS 2189:2026

Questions about IS 2189:2026

What is IS 2189?

IS 2189 is the Indian Standard code of practice for selecting, installing and maintaining automatic fire detection and alarm systems. The current edition is IS 2189:2026, the fifth revision, from the Fire Fighting Sectional Committee, CED 22.

What is the latest version of IS 2189?

IS 2189:2026, published in March 2026. It replaced IS 2189:2008, which BIS withdrew on 17 September 2026.

Is IS 2189:2008 still valid?

No. BIS withdrew it on 17 September 2026. Some state guidelines, such as Maharashtra's July 2026 Form B guidelines, still name it; ask the fire office in writing which edition it accepts.

What is the smoke detector spacing as per IS 2189?

On a flat ceiling the code lists 7.5 m between a point and the nearest smoke detector, valid up to 7 m of ceiling height, reducing to 5 m between 7 m and 10 m (cl. 6.3.2.1, 6.3.3.1). The layout must also give one smoke detector per 100 m2 at least.

What is the heat detector spacing as per IS 2189?

5.3 m on a flat ceiling up to 5 m high and 3.5 m between 5 m and 10 m; heat detectors are prohibited above 10 m. At least one heat detector per 50 m2 (cl. 6.3.2.1, 6.3.3.1, 6.3.4).

At what height is a manual call point fixed under IS 2189?

1.4 m above the surrounding floor level, with no person more than 30 m from a call point inside, or 45 m where call points are also outside (cl. 6.4).

How often should a fire alarm system be maintained as per IS 2189?

The user checks the panel daily, reviews the week's events weekly and tests quarterly; detectors are cleaned at least every 3 months; smoke detector sensitivity is tested twice a year and every smoke detector, heat detector and call point is tested yearly (cl. 7.4, 7.5, Table 4).

Does IS 2189:2026 allow wireless fire alarms?

Yes, clause 4.9 allows fully wireless or hybrid systems on licence-exempt bands such as 865 to 867 MHz and 2.4 GHz. Maharashtra's circular accepts them but not in high-rise buildings.

Is IS 2189 mandatory?

Not by itself. No Quality Control Order covered detectors or alarms on 24 October 2026. It binds when a state rule, NOC condition, tender or contract names it.

Keep reading

Sources

Each source was opened and read on the date shown. How Flamekite checks its sources

  1. Bureau of Indian Standards: IS 2189:2026, Selection, Installation and Maintenance of Automatic Fire Detection and Alarm System, Code of Practice (fifth revision), March 2026; free download after registration; clause numbers cited on the page (opens in a new tab)checked 26 October 2026
  2. Bureau of Indian Standards (BIS Know Your Standards record): BIS record for IS 2189:2026, fifth revision, superseding IS 2189:2008 (opens in a new tab)checked 26 October 2026
  3. Bureau of Indian Standards, Know Your Standards database: Status records read 25 October 2026 for IS 2189, IS 2190, IS 15683, IS 16018, IS 3844, IS 13039, IS 15105, IS 15301, IS 9668, IS 12349, IS 3614, IS 2175 and IS 11360 (current or withdrawn, with dates) (opens in a new tab)checked 25 October 2026
  4. Bureau of Indian Standards, Know Your Standards database: Status, publication and withdrawal dates of the fire standards named on /is-codes (IS 2190, 15683, 16018, 2189, 15105, 9972, 3844, 13039, 9668, 15301, 15908, 636, 884, 903, 5290, 9457, 3614, 11360, 2175 and others), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  5. Bureau of Indian Standards: Products under compulsory certification, Scheme-I list (orders up to S.O. 5480(E) of 6 October 2026), read 24 October 2026 (opens in a new tab)checked 24 October 2026
  6. Bureau of Indian Standards (copy hosted by Goa Directorate of Fire and Emergency Services): SP 7:2026 National Building Construction Standards 2026, Part F: Fire and Life Safety (opens in a new tab)checked 25 October 2026
  7. Maharashtra Fire and Emergency Services: Circular No. MFS-2026/1420, 16 October 2026: Wireless Detection System, under IS 2189:2026 clause 4.9 (number and date read from the page image) (opens in a new tab)checked 25 October 2026
  8. Maharashtra Fire Services: Circulars (read through the entry of 16 October 2026; includes circular MFS/2017/60 of 17 May 2017 on NBC 2016 Part 4) (opens in a new tab)checked 25 October 2026